Every sign of failure the Technical Library records under Building Code Compliance: 24 signs across 3 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.

Disabled Access (DDA)

Older buildings and alterations

What you seeLikely cause, and what confirms itNext step
Steps at the only entryBuilding predates access requirements. Era; approvals.Plan a ramp, platform lift or regraded path; if it cannot be done at once, set it in an access action plan.
New fit-out with an accessible toilet but steps at the entryPath of travel not upgraded with the alteration. Approval documents; access report.Upgrade the path of travel as the approval requires, and check the access report's conditions.
Doorways too narrow for a wheelchair on the accessible routeClear width below current standards. Clear opening measured with the door at 90 degrees, against the asset’s market (Thresholds by market).Widen the opening or rehang the door at the next alteration.
Ramp that feels steep, or a lip at its top or bottomRamp gradient or level change outside the rules. Gradient and level change measured against the asset’s market (Thresholds by market).Regrade the ramp or fix the lip; add handrails where required.

Wear, doors and lost features

What you seeLikely cause, and what confirms itNext step
Tactile indicators lifting at stairsAdhesive failure from traffic and cleaning. Inspection.Replace the lifted indicators now; they are a trip hazard.
Doors that people in wheelchairs cannot openCloser force too high or no automatic operator. Door force measurement against the asset’s market (Thresholds by market).Adjust the closer to the required force, or fit an automatic operator.

Management and evacuation

What you seeLikely cause, and what confirms itNext step
Accessible toilet full of boxesManagement practice. Observation.Clear it, and put a procedure in place to keep it available.
No refuge or evacuation planEgress for people with disability not addressed. Fire strategy; plans.Review the fire strategy and prepare evacuation plans for people who need assistance.

Hazardous Materials

Works, fire and storms

What you seeLikely cause, and what confirms itNext step
Drilling, cutting or demolition started without a refurbishment surveyAsbestos disturbed without knowing where it is. Survey records against the work area; the HSE survey guide expects a refurbishment and demolition survey before such work (HSG264).Stop the work, isolate the area, survey, and decontaminate if needed.
Fire or storm damage to an older building with cement sheet or laggingAsbestos debris spread by the event. Visual inspection; sampling of debris; air monitoring.Restrict access and arrange licensed clean-up before repairs.
Sanding or stripping old paintLead dust released. Paint testing before work, against the definition of lead paint for the asset’s market (Thresholds by market).Use lead-safe methods and clean-up, and keep occupants away.

Deterioration, leaks and ground hazards

What you seeLikely cause, and what confirms itNext step
Cement sheet roof weathered with exposed fibresAsbestos cement weathering. Sampling; register.Sample if not already identified; plan removal or encapsulation, and keep people off the roof.
Damaged lagging in a plant roomFriable asbestos deteriorating. Sampling; air monitoring.Isolate the area now; licensed removal with air monitoring.
Flaking paint on a pre-1970 buildingPossible lead paint. Paint testing.Test the paint; stabilise or remove it under lead-safe work practices.
Oily residue in old light fittingsLeaking PCB capacitors. Sampling.Isolate the fittings and remove the capacitors as hazardous waste.

Registers and surveys

What you seeLikely cause, and what confirms itNext step
Register shows large areas not accessedIncomplete survey. Register review.Survey those areas before any works; treat suspect materials there as asbestos until sampled.

Occupational Health & Safety (OHS)

Access to plant and confined spaces

What you seeLikely cause, and what confirms itNext step
Ladder marks on walls near plantNo designed access to plant. Inspection.Install fixed access: a caged ladder, a ladder with fall arrest, or a platform with guardrails.
Fixed ladder to plant with uneven rungs or no cage or fall arrestLadder unsafe for regular use. Rung spacing and width measured against the asset’s market (Thresholds by market).Repair or replace the ladder, and add fall protection or a stair where access is frequent.
Roof edges or plant platforms with no guardrailFall from height. Guardrail height and condition against the asset’s market (Thresholds by market).Install guardrails or edge protection before further access.

Stairs, floors and glazing

What you seeLikely cause, and what confirms itNext step
Repeated slips at an entryFloor finish unsuitable when wet. Slip resistance test.Test the slip resistance; treat or replace the finish and add recessed matting.
Falls on one stairUneven risers or worn nosings. Measurement against the asset’s market (Thresholds by market).Measure the risers and nosings; replace worn nosings and correct the flight.
People walking into glass doorsMissing manifestation. Inspection.Apply manifestation at the right heights, and check the glass is safety glass.

Records and contractors

What you seeLikely cause, and what confirms itNext step
Contractors unaware of hazardsNo induction or registers. Records.Set up inductions, permits and registers, and make them available to contractors.
No asbestos register, plant risk assessments or confined space register on siteContractors working without the information they need. Records review.Assemble the registers and include them in contractor induction.