Every sign of failure the Technical Library records under Environmental: 32 signs across 4 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.

Electric Vehicle (EV) Charging

Capacity and load management

What you seeLikely cause, and what confirms itNext step
Chargers trip when several vehicles chargeCapacity exceeded or no load management. Load measurement; maximum demand.Measure maximum demand; add load management before more chargers, or upgrade the supply.
Car park with no dedicated distribution board or spare capacity for chargingNot ready for charging demand. Boards and capacity against the asset’s market (Thresholds by market).Plan board and supply upgrades before chargers are requested.

Installation, damage and fire safety

What you seeLikely cause, and what confirms itNext step
Charger warm at terminals, faults recordedPoor terminations or undersized cabling. Thermography; inspection.Isolate the charger; remake the terminations and check the cabling and protection.
Residents charging from general outlets with extension leadsLack of approved charging. Observation.Stop the practice now, and provide approved charging after a capacity check.
Chargers mounted where vehicles strike them, or blocking escape routesDamage and egress risk. Layout review; impact protection; escape route widths.Relocate or protect the chargers with bollards or wheel stops.

Software, billing and fairness

What you seeLikely cause, and what confirms itNext step
Chargers offline and unusableBack-end or communications failure. Network status; vendor.Check the network and the vendor contract; prefer open-protocol chargers at replacement.
Disputes over electricity costsUnmetered charging on common supply. Metering arrangement.Meter each charger or user, and set billing in the by-laws or lease.
No metering of individual charging circuitsCosts cannot be allocated. Metering arrangement against the asset’s market (Thresholds by market).Fit sub-meters or networked chargers that record use per user.

Energy Efficiency Upgrades

The performance gap and drift

What you seeLikely cause, and what confirms itNext step
No saving after a drive retrofitDrive bypassed or controls not changed. Drive status; trend data.Take the drive out of bypass and change the control sequence so it varies speed.
Savings fading after recommissioningOverrides and drift. BMS overrides; trend data.Remove the overrides, restore schedules, and add fault detection so drift is caught early.
Savings claimed but no measured before-and-after dataUnverified result. Interval data across the change, adjusted for weather and occupancy.Set up measurement and verification for future projects.

Quality and unintended consequences

What you seeLikely cause, and what confirms itNext step
Condensation after insulation upgradeNo vapour control or ventilation. Inspection; humidity.Add vapour control and ventilation; treat mould now where it affects health.
Heat pump building cold in winterUndersized heat pump or emitters. Heat loss vs output.Compare the heat loss with the heat pump and emitter output; resize or add capacity.
Overheating after glazing film, insulation or air sealingComfort traded for energy. Temperature logging; ventilation and shading.Add shading or ventilation; review the upgrade design.

Rules, tenants and load growth

What you seeLikely cause, and what confirms itNext step
Rating below the letting minimumRegulatory shortfall. Certificate.Plan the upgrades that reach the minimum by the regulatory date.
Main switchboard near capacity before electrificationElectrical capacity will limit heat pumps and chargers. Maximum demand against supply; for larger buildings, NCC J9D3 time-of-use meters on major services help size this (NCC J9D3).Model the electrified load and plan supply upgrades.

Sub-metering

Wiring, mapping and accuracy

What you seeLikely cause, and what confirms itNext step
Sub-meters add up to much more or less than the main meterRatio, polarity or mapping errors, or missing meters. Reconciliation; spot load checks.Reconcile against the main meter, then check ratios, polarity and mapping with spot load checks.
Negative or reversed readingsCurrent transformer installed backwards. Inspection.Reverse the current transformer and recommission the meter.
Tenant consumption far from expectedWrong circuits measured. Load tracing.Trace the loads and correct the circuit allocation and mapping.
Larger building with only one main electricity meterMetering below the market’s rules. Meters against the asset’s market (Thresholds by market).Add meters at the next switchboard work.

Missing meters and data gaps

What you seeLikely cause, and what confirms itNext step
Data flat for weeksCommunications or battery failure. Gateway status.Restore communications or batteries, and set alarms for data gaps.
Meters installed but nobody reviews the dataMetering without use. Who receives reports and what action follows.Set up monthly review with exception alerts.

Billing and legal rules

What you seeLikely cause, and what confirms itNext step
Billing disputesMapping errors or unapproved meters. Audit.Audit the meters and mapping; correct past bills where errors are found.
Tenants billed from estimates despite meters being fittedMeters unread or untrusted. Reading records; meter approvals.Verify the meters and move billing to actual readings.

Water Conservation

Leaks, urinals and fixtures

What you seeLikely cause, and what confirms itNext step
Night flow with the building emptyLeaks or timed urinals. Night flow test; isolate zones.Isolate zones to find the source; repair leaks and fit sensor urinal controls.
Water use rising with no change in occupancyNew leak. Sub-meters.Use the sub-meters to find the leak, then repair it and set leak alarms.
Blockages after toilet replacementLow flows in old drains. CCTV; drain grades.Survey the drain by CCTV; upgrade it where low flows cannot carry waste.
Toilets or urinals running constantlyFailed fill valves or flush controls. Dye test in cisterns; urinal controls.Repair or replace the valves and fit urinal controls.

Cooling towers, kitchens and process water

What you seeLikely cause, and what confirms itNext step
High cooling tower water usePoor bleed control. Treatment records.Control bleed by conductivity, with good water treatment.
Constant flow from equipmentSingle-pass cooling. Inspection of kitchen and plant.Replace single-pass cooling with air-cooled or closed-loop equipment.

Irrigation and alternative water

What you seeLikely cause, and what confirms itNext step
Summer peaks in water useIrrigation or cooling towers. Sub-meters; seasonal pattern.Use the sub-meters to separate irrigation from the cooling towers; fit smart controllers and rain sensors.
Tanks full but mains use unchangedHarvesting system not supplying end uses. Pump and valve checks.Check the pumps and valves, and reconnect the system to its end uses.