Every sign of failure the Technical Library records under Façades: 87 signs across 9 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.

Architectural & Decorative Features

Cramps and hidden metal

What you seeLikely cause, and what confirms itNext step
Crack following a straight line through a stone unit, rust stain at its end, corner displacedCramp or dowel corrosion. Metal detector locates the cramp on the crack line; opening up shows rust.Remove the corroded cramp, replace it in stainless steel, and repair the stone.

Cornices, projections and earlier repairs

What you seeLikely cause, and what confirms itNext step
Cornice top with vegetation and open joints, staining belowMissing weathering; water at the cramps. Aerial imagery; joints open on top.Clear the vegetation; add lead or copper weatherings, and repoint the top joints in lime.
Fragments found on the pavement below a cornice or parapetAn unsafe façade condition. Hammer survey of the feature from access; in New York City, owners of buildings taller than six storeys must file a critical examination of the façades every five-year cycle, and unsafe conditions call for immediate public protection (FISP Cycle 10 notice).Protect the pavement now, remove anything loose, and pin, rebuild or replace the units before the protection comes down.

Terracotta, stone and render

What you seeLikely cause, and what confirms itNext step
Sheets of stone lifting parallel to the faceContour scaling from salts, or face-bedded stone. Salts in the debris; bedding planes visible parallel to the face.Remove loose material safely; indent new stone, or repair with lime mortar.
Glaze crazed and spalled across terracotta unitsWater in the body of the unit; frost or salt. Moisture in the unit; spalls concentrated on exposed and top surfaces.Stop the water getting in; consolidate the glaze, or replace units from a specialist manufacturer.
Terracotta units cracking along joints with rust stainingAnchor corrosion behind the units. Opening shows corroded anchors or frame.Open up; replace the anchors in stainless steel, and repair or replace the units.
Black crust blistering on limestone or marbleGypsum crust from pollution. Sheltered areas worst; surface loss when crust falls.Clean with a method suited to the stone, never abrasive blasting.
Hollow render moulding cracked around its edgesDelamination from the backing. Tapping; probing behind.Make safe; re-fix with stainless pins, or replace the moulding.

Building Maintenance Units (BMU)

Structure, stability and anchors

What you seeLikely cause, and what confirms itNext step
Inspection overdue or logbook missingEquipment cannot lawfully be used. Last inspection date against the required interval.Take it out of use until inspected and certified, and restore the logbook.
Major inspection never done on a unit more than ten years oldHidden structural condition unknown. Records; Australian guidance calls for a major inspection at that age.Commission a major inspection before relying on the unit.
Corrosion at track fixings and leaks below themWater at roof penetrations. Membrane condition at the fixings; leak log.Refurbish the track and fixings, and renew the roof membrane at the penetrations.
Anchors without certification recordsAnchors cannot be relied on. Certification records and intervals.Take the anchors out of use; replace or recertify them.
Davit sockets or roof supports with no inspection in the last yearSupport structure condition unknown. Inspection records for the supporting structure and the equipment, against the intervals for the asset’s market (Thresholds by market).Inspect the supports and sockets before the next use, and set a yearly regime.

Ropes, hoists, controls and coverage

What you seeLikely cause, and what confirms itNext step
Unit out of service for months, waiting on partsControl obsolescence. Manufacturer support status; service reports.Plan control modernisation on the sound structure.
Hired equipment used for some elevationsCoverage gap. Façade access strategy against the current façade.Review the façade access strategy; add a monorail, davits or anchors to cover the gap.
Roof perimeter guard set well back from the parapetWorkers exposed at the roof edge while rigging. Guard position, setback and davit handling against the asset’s market (Thresholds by market).Have the edge protection and rigging arrangements reviewed against the rules that apply.

Canopies & Awnings

Anchorages and tie rods

What you seeLikely cause, and what confirms itNext step
One slack rod among taut onesAnchorage moved or rod failed. Masonry cracked at that anchorage; rod pulls out or turns freely.Prop it, or close the footpath below; replace the anchorage and rod.
Local dip at one bayFailed rod, anchorage or frame connection at that bay. Inspection of that bay's rod and fixings.Prop that bay; repair the rod, anchorage or frame connection.
Rust bleeding from the wall at rod entry pointsAnchorage corrosion inside the wall. Opening up exposes the plate or hook.Open up the anchorage; replace it with through-bolted plates or chemical anchors into sound masonry.
Street awning more than ten years old with no engineer’s reportStructural adequacy unknown. Age and inspection record against the asset’s market (Thresholds by market).Commission an engineer’s inspection, opening up the tie-rod anchorages.

Ponding, cantilevers and posts

What you seeLikely cause, and what confirms itNext step
Uniform sag along the fasciaConnection rotation at the wall or general overload. All rods equally stretched; cracking along the wall line; added signage or water load.Prop the awning; have an engineer assess the connections and loads.
Staining from the gutter line, deflection worst after rainBlocked box gutter and ponding. Gutter full of debris; outlets undersized or blocked.Clear the gutter; renew it with larger outlets and overflows.
Signage, plant or people now on an awning roofLoads beyond what the awning was built for. Load check against the design actions: NSW structural engineers’ guidance applies 1.5 kPa with a 1.8 kN point load to awnings reachable from windows, roofs or balconies, and 1.0 kPa with 1.8 kN where access is only from the ground; older awnings were designed for as little as 0.25 kPa and 1.4 kN (Practice Note 18).Remove the added load or keep people off; have an engineer check the awning for any load that must stay.

Glass canopies

What you seeLikely cause, and what confirms itNext step
Glass canopy panel cracked with no impactThermal stress or nickel sulphide inclusion. Glass type; fracture origin.Make the area below safe; replace with laminated glass.

Cladding & Wall Systems

Water behind the face

What you seeLikely cause, and what confirms itNext step
Staining and cracking below window corners on render or EIFS; damp at reveals insideWater entry at window perimeter in a face-sealed system. No head or sill flashing; moisture readings high at the sill and bottom plate; decay found on opening up.Probe the framing at the sills; reclad with a drained, ventilated system where the frame has decayed.

Fixings, precast and stone

What you seeLikely cause, and what confirms itNext step
Rust staining from precast joints; cracking at panel cornersCorrosion of concealed fixings. Staining at fixing positions per the panel drawings; cracks radiating from corners; openings expose corroded ferrules or angles.Open up at the fixing positions; add stainless anchors or replace corroded hangers.
Spalling in lines across precast facesReinforcement corrosion from low cover. Covermeter shows low cover along the line; carbonation depth reaches the steel, the front marking a fall in pH from about 12.5 to 8.5 (Institute of Corrosion).Repair the concrete to a recognised repair standard, or overclad where the substrate is sound.
Dished or bowed stone panels, cracks at anchorsThermal bowing of thin marble, or anchor failure. Bowing uniform across panels of the same stone: hysteresis; local cracking at one anchor: anchor corrosion or overstress.Check the anchors; add supplementary stainless anchors, or replace bowed panels.
Layers of stone flaking parallel to the faceFace-bedded stone, or salt crystallisation. Bedding planes parallel to the face; salts in the debris.Replace the affected stone.

Combustible cladding

What you seeLikely cause, and what confirms itNext step
Immaculate composite panels on an apartment block of the 1995 to 2018 eraPossible combustible core; no condition defect. Product identified from records, panel labels or a core sample.Identify the product from records, labels or a sample; replace it if combustible, with interim measures meanwhile.
Combustible cladding on a residential building above the height at which the asset’s market restricts itExternal surface below the class now expected. Cladding classification against the asset’s market (Thresholds by market).Carry out a fire risk appraisal of the external wall to PAS 9980, and plan remediation where it is needed.

Panels, coatings and weatherboards

What you seeLikely cause, and what confirms itNext step
Sandwich panel skins rusting from laps and cut edges, panels bulgingCut-edge corrosion; wet or degraded core. Corrosion starts at edges and fixings; panel soft or delaminated when pressed.Replace affected panels, or the system where the core is wet or degraded.
Peeling paint and decay concentrated at weatherboard ends and the bottom coursesEnd grain moisture and ground-line wetting. Ends unsealed; boards close to paving or soil; sound boards higher up. Clearances to ground, paving and floor framing measured against the asset’s market (Thresholds by market).Replace decayed boards, seal the ends, restore ground clearance, and repaint.

External Coating Systems

Chalking, adhesion, blistering and cracking

What you seeLikely cause, and what confirms itNext step
Powder on the finger, colour fadedNormal UV ageing. Even across the elevation; worst on the sunniest faces.Wash and recoat while the coating is sound.
Peeling to bare substrate at sills, wall bases and under guttersMoisture behind the coating. Source of water at that location; damp readings behind.Fix the water source first, then prepare and recoat.
Peeling between coats in sheetsIntercoat adhesion failure: incompatible or poorly prepared coats. Cross-cut adhesion test fails between layers; glossy layer beneath.Remove the incompatible layers, and recoat with a compatible system.
Water-filled blistersMoisture vapour or water from behind. Damp substrate; impermeable coating on a wall that needs to breathe.Find and fix the moisture source; use a breathable coating.
Fine crazing in a mud-crack pattern on old paintEmbrittled thick alkyd or oil paint. Paint stack thick; age.Remove and recoat in full, under lead controls where lead is present.

Render, concrete and steel

What you seeLikely cause, and what confirms itNext step
Cracks in straight lines at regular spacingSubstrate joints in sheet or panel. Joint locations match.Address the joints in the sheet or panel beneath before recoating.
Hollow, bulging renderRender debonded from masonry. Tapping; render lifts at the edges.Cut out and replace the debonded render, or strip and re-render.
Rust staining through a coating on concreteReinforcement corrosion beneath. Cover survey; carbonation depth at the steel, the front marking a fall in pH from about 12.5 to 8.5, and chloride content where the threshold of 0.2 to 0.4 per cent by mass of cement may be exceeded (Institute of Corrosion).Repair the concrete and treat the reinforcement, then apply an anti-carbonation coating.

Lead paint

What you seeLikely cause, and what confirms itNext step
Old paint being sanded, scraped or burnt offLead dust and fumes. Test the paint first, against the definition of lead paint for the asset’s market (Thresholds by market).Stop the work, contain the area, and resume only with lead-safe methods and clean-up.
Flaking paint and chips in the soil along the base of an older buildingLead paint shedding into the ground. Paint and soil sampling.Stabilise or remove the paint under lead controls, and assess the soil where children play.

Glazing Systems

Water infiltration and seals

What you seeLikely cause, and what confirms itNext step
Leak at the same mullion on every floorSplice or stack joint failure in the curtain wall. Water test at the joint reproduces the leak.Water test the splice or stack joint, then reseal it.
Leak at sill ends and at the slab below window wallsMissing or failed end dams and sill flashing. Water test at sill ends; water found on the slab edge on opening up.Reinstate the end dams and sill flashing.
Leak only in heavy wind-driven rainOverwhelmed drainage or pressure equalisation failure. Weep holes blocked or baffles missing; water rises in the sill under pressure.Clear the weep holes and reinstate the baffles.

Misted insulating glass units

What you seeLikely cause, and what confirms itNext step
Fogging or white bloom between panesIGU edge seal failure. Cannot be wiped from either face; units at the bottom of the elevation or with blocked weeps worst affected.Replace the unit; reglaze the elevation where failure is widespread.

Glass breakage and structural silicone

What you seeLikely cause, and what confirms itNext step
Break in toughened glass with no impact, small fragments, a characteristic butterfly-shaped pair of fragments at the originNickel sulphide inclusion. Origin inside the pane, not at an edge; glass not heat-soaked; other spontaneous breaks in the same batch.Protect the area below; assess the remaining risk, and replace with heat-soaked or laminated glass where warranted.
Single crack starting at an edge at right angles, wandering across the paneThermal stress in annealed or heat-strengthened glass. Edge damaged or partly shaded; blinds or film close to the glass; tinted or coated glass.Replace the pane; check the edges, shading, and any blinds or film close to the glass.
Cracks radiating from a pointImpact. Point of contact visible; often at low level.Replace the pane.
Glass loose or moving on an SSG façadeStructural silicone adhesion loss. Hand pull adhesion test fails at the substrate; bond width less than design.Make the area below safe; add mechanical retention, or reglaze.
Clear glass low in a window or beside a door with no safety glass markGlass that may break dangerously on impact. Glass type in the locations the asset’s market treats as critical (Thresholds by market).Identify the glass from its marks; replace it with safety glass or protect it.

Anchors and steel windows

What you seeLikely cause, and what confirms itNext step
Cracked glass and rust at steel windowsRust jacking at the glazing rebate. Rust visible at the rebate; putty or glazing compound failed.Strip, treat and repaint the frames, and reglaze.

Masonry/Brickwork

Wall ties and sulfate attack

What you seeLikely cause, and what confirms itNext step
Horizontal cracks at regular intervals, about every sixth course, outer leaf onlyWall tie corrosion. Worst on exposed elevations and higher up, where less load resists the lift; ties located by metal detector coincide with the cracks; inner face uncracked.Survey the ties; install stainless remedial ties, removing or cutting back strip ties that are expanding.
Horizontal cracks in most bed joints, white swollen mortar, wall growthSulfate attack. Every course affected, not only tie courses; chimneys, parapets, rendered or wet walls; can affect both leaves; mortar soft when probed.Confirm by mortar analysis, and get an engineer's advice on repair or rebuilding.

Lintels, shelf angles and embedded steel

What you seeLikely cause, and what confirms itNext step
Horizontal crack and outward bow repeated at each floor line of a framed buildingFrame shortening; no soft joint under the shelf angle. Repeats floor by floor; brick spalled at the angle; no sealant line, or crushed sealant, under the angle.Form a soft joint under each shelf angle, and treat or replace the angles.
Stepped crack rising from a lintel end, horizontal crack along the lintel, brick lifted or dropped over the openingLintel corrosion. Rust at the bearing; crack widest at the lintel; opening frame itself square.Prop the brickwork and replace the lintel, with a cavity tray, stop ends and weep holes.
Cracking and displacement along column and floor lines of an early steel-framed buildingRust jacking of embedded steel. Rust staining at the crack; corners and parapets first; brick pushed outward rather than dropped.Open up, treat or replace the steel, and rebuild with flashing and drainage.

Movement and foundation cracking

What you seeLikely cause, and what confirms itNext step
Diagonal crack tapering wider at top or bottom, through openings, continuing below the damp-proof courseFoundation movement. Crack passes through bricks in a continuous line; sticking doors, floor slopes, matching internal cracks; seasonal movement on reactive clay; nearby trees or leaking drains.Address the cause and monitor; see Foundations.
Vertical crack of even width near a corner or at a short return; brickwork oversailing at the baseClay brick expansion or thermal movement. Long run without movement joints; no distortion of openings; width does not change across seasons.Saw-cut and seal a movement joint, and tie across where panels have been freed.
Vertical cracks at openings and mid-panel in blockwork or calcium silicate brickDrying shrinkage. Material type; cracks widest early in life and then stable.Repair once the cracks have stabilised; add movement joints where runs are long.

Damp, frost and salts

What you seeLikely cause, and what confirms itNext step
Powdery brick, eroded mortar and salts in a band at the baseRising damp with salt attack. Tide line up to about a metre; bridged or absent damp-proof course; worse behind garden beds and paving.Remove the bridging, then a new damp-proof course if the old one has failed; replaster in a salt-resistant system.
Spalled faces high on exposed walls, parapets and chimneysFrost damage, or hard cement pointing on soft brick. Cold climate; mortar proud of recessed brick; damage concentrated next to hard pointing.Repoint in a mortar no stronger than the brick, and replace spalled bricks.

Sealants & Joints

Adhesive, cohesive and substrate failure

What you seeLikely cause, and what confirms itNext step
Sealant peeled cleanly from one faceAdhesive failure: preparation, primer or contamination. New sealant needs full removal of old material, cleaning and priming; test adhesion before the programme.Test adhesion at sample joints, then cut out and replace the joint completely.
Split down the middle, bonded both sidesCohesive failure: over-extension or ageing. Check joint width against movement; if the joint is too narrow, a different sealant or joint design is needed.Widen the joint, or change to a sealant suited to its movement.
Sealant intact, skin of substrate pulled offSubstrate failure. Lower-modulus sealant; substrate repair; possibly a bridge seal over the joint.Repair the substrate, then fit a bridge seal or a lower-modulus sealant.
Torn across the back as well as splitThree-sided adhesion. Reinstate backing rod or bond breaker in the new joint.Cut out and replace, with a backing rod or bond breaker.

Ageing, wet substrates and staining

What you seeLikely cause, and what confirms itNext step
Hard, crazed bead with fine cracksAge and UV. Full replacement on cycle.Plan a cut-out-and-replace programme.
Failure concentrated on one or two elevationsExposure. Programme can be staged by elevation.Stage the programme by elevation, starting with the most exposed.
Failure everywhere within a few years of a programmeWorkmanship or product. Warranty claim; test adhesion; review specification.Claim under the warranty; test adhesion and review the specification.
Whole elevation failing within a few years of resealingPoor application conditions or preparation. Failure dates and pattern match the programme; adhesive failure throughout.Pursue the contractor and warranty; adhesion testing supports the claim.
Leak persists after the visible joint was resealedSecond line of defence missing or blocked. Cavity drainage and weep holes blocked; flashings absent.Clear the cavity drainage and weep holes, and add flashings.

Fire-rated joints

What you seeLikely cause, and what confirms itNext step
Ordinary sealant in joints at slab edges or fire wallsFire-rated joints replaced like for like with weathering sealant. No fire-rated product or certificate; joint in a fire-separating line.Replace with a tested fire-rated system matched to the joint.

Hazardous sealants

What you seeLikely cause, and what confirms itNext step
Hard, dark sealant on a building of the 1950s to 1970sPossible PCB sealant. Sampling before removal; PCB sealant can contaminate the concrete or masonry next to it (Thresholds by market).Sample before any removal; if PCBs are found, treat the work as hazardous materials removal, including the adjacent substrate.
Sealant residue and stained masonry beside joints already cut outPCBs left in the substrate. Sampling of the adjacent concrete or masonry.Sample the substrate, and remove or encapsulate contaminated material.

Verandahs, Balconies & Balustrades

Cantilevers and overload

What you seeLikely cause, and what confirms itNext step
Crack along the wall line on the top surface; tip of the slab lower than its rootTop reinforcement corrosion or overload in a cantilever. Half-cell and cover readings at the root; chloride or carbonation at bar depth; rotation measured by level.Close the balcony until an engineer has assessed it; strengthen it, or replace it where section loss at the root is severe.
Spalling on the soffit and front edgeCorrosion of edge and bottom bars. Rust staining along bar lines; low cover.Repair the concrete to a recognised repair standard.

Timber decks, ledgers and heritage verandahs

What you seeLikely cause, and what confirms itNext step
Deck separating from the wall; bounce; stained wall lineLedger fixing failure and decay. Nails or corroded bolts at the ledger; soft timber behind.Close the deck; fit a new ledger with through-bolts and lateral load connectors.
Deck bouncing or sloping outwardLedger, joist or post failure, or overload. Ledger fixings corroded or withdrawn; joists decayed at bearings.Close the deck; replace the failed ledger, joists or posts, or rebuild it.
Cracks in cast iron lace or columnsCorrosion and brittle fracture. Rust at fixings; cracked sections that move.Replace cracked sections with matching castings.

Balustrades and glass

What you seeLikely cause, and what confirms itNext step
Rust and burst concrete at a balustrade post base, post looseWater in hollow post or pocket. Post moves at the root under hand pressure; water inside when drilled.Rebuild the post base with a drained or solid post on a surface-mounted plate above the membrane.
Missing glass panel with fragments belowSpontaneous breakage of monolithic toughened glass. Glass marked toughened, not laminated; no impact.Close the balcony; replace monolithic toughened glass with laminated glass.
Low balustrade, wide gaps, or rails children could climbA barrier that will not prevent a fall. Height, openings and climbable rails measured against the asset’s market (Thresholds by market).Raise, infill or replace the barrier to the current requirement.

Membranes, thresholds and enclosures

What you seeLikely cause, and what confirms itNext step
Leak to the unit below at the door lineMembrane failure at the threshold. Flood test at the threshold; low or reversed upstand.Flood test the threshold separately from the door sill; raise the upstand and renew the membrane.
Drummy and cracked tiles over the whole balconyMembrane failure with saturated bedding. Flood test; moisture in the screed.Re-membrane: remove tiles and screed, correct the falls, renew the membrane and outlets, and re-tile.
Water standing against the door sillFalls towards the building or threshold too low. Level survey; threshold height against the balcony surface.Correct the falls and threshold height when re-membraning.
Leaks below that began after tiling or an enclosureOccupant alteration to the waterproofing. Alteration dates; tiles over membrane; drainage blocked.Establish the alteration, then restore the membrane and drainage.