Every sign of failure the Technical Library records under Fire Services: 69 signs across 8 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.

Automatic Sprinkler Systems

Changes of hazard, obstruction and coverage

What you seeLikely cause, and what confirms itNext step
Warehouse storing more, higher or different goods than designedHazard change beyond design. Design certificate against current storage.Check the design certificate against current storage; reduce the storage or redesign the system.
Rooms without heads after fit-outCoverage gap. Survey against layout.Add coverage to the standard, and have it certified.
Storage stacked up close to the headsSpray pattern blocked from above the goods. Measure from the deflectors to the top of the storage (Thresholds by market).Bring the storage down below the clearance line, and mark the line on racking or walls so it stays clear.

Impairments and water supply

What you seeLikely cause, and what confirms itNext step
Flow test below the design pointWater supply decline or obstruction. Flow test against design curve.Find the obstruction or supply decline; improve the supply with pumps, tanks or a larger connection.
Fire panel shows valve closedImpairment not cleared. Valve inspection.Open and supervise the valve now, and manage impairments with permits and fire watches.
Main drain test pressure lower than at the last testSupply decline, a partly closed valve or an obstruction. Static and residual pressures compared with the previous reading and the limits for the asset’s market (Thresholds by market).Confirm every control valve is fully open, then trace the supply; flow test the water supply where the fall is confirmed.

Corrosion, heads, CPVC and freezing

What you seeLikely cause, and what confirms itNext step
Pinhole leaks in wet pipeworkMicrobiologically influenced corrosion. Pipe section examination; water testing.Examine a pipe section and test the water; replace affected pipe and treat for MIC.
Leaks at low points of a dry systemTrapped water corrosion. Drain and inspect low points.Drain the low points, add auxiliary drains, and consider nitrogen inerting.
Cracked CPVC fittingsChemical incompatibility. Products in contact.Identify and isolate the incompatible products; replace the cracked sections.
Heads corroded, painted or loaded with dust or greaseHeads that may respond late or not at all. Head survey; sample heads removed and tested by a laboratory.Replace affected heads like for like, and sample test heads of the same age and type.

Fire Detection & Alarm Systems

Panels, isolations and coverage

What you seeLikely cause, and what confirms itNext step
Zones isolated for weeksIsolation after works or nuisance alarms. Event log; works records.Clear the isolations now, and manage future ones with a permit and a daily check.
New tenancy cannot be connectedPanel unsupported or at capacity. Vendor advice; panel loading.Confirm vendor support and panel loading; plan replacement with a supported addressable system.
Detectors with no sensitivity readings for yearsDetectors drifting out of their range. Sensitivity readings from an addressable panel, or tests on site; US Department of Defense guidance tests smoke detector sensitivity every five years (UFM 3-601-02).Read or test sensitivity, and clean or replace detectors outside their marked range.

Unwanted alarms and domestic alarms

What you seeLikely cause, and what confirms itNext step
Repeated unwanted alarms from one areaWrong detector type or contamination. Event log; detector type against the space.Fit the right detector for the space, clean or replace contaminated detectors, and move detectors away from diffusers.
Smoke alarms in flats with a date more than ten years oldAlarms past their built-in life. Manufacture or expiry date on the alarm base.Replace them with interconnected photoelectric alarms, hard-wired or with sealed ten-year batteries.

Interfaces, warning and signalling

What you seeLikely cause, and what confirms itNext step
Lifts did not home or doors did not release in a testInterface or cause-and-effect fault. Interface test; matrix review.Update the cause-and-effect matrix and run a full integrated test.
Brigade not called in a testSignalling failure, often a retired line. Monitoring centre test; line type.Test with the monitoring centre; upgrade to supported, preferably dual-path, signalling.
Alarm inaudible in parts of the buildingInsufficient sounders or speakers after fit-outs. Sound level and intelligibility test against the limits for the asset’s market (Thresholds by market).Add sounders or speakers, or a voice system where intelligibility is required.
Alarm faint inside apartments with the entry door shutToo little sound reaching the units. Sound level at the unit entry doors, or inside the units, against the asset’s market (Thresholds by market).Measure at the entry doors, and add sounders in the common areas or inside units where the level falls short.

Fire Pumping Systems

Starting, power and controllers

What you seeLikely cause, and what confirms itNext step
Diesel slow to start or failsBatteries, fuel or heater. Battery test; fuel sample.Test the batteries and sample the fuel; restore batteries, chargers, heater and fuel management.
Pump supply after the main switchDesign defect. Single-line diagram.Reconnect the supply ahead of the main switch with fire-rated cable.
Run log shows short or missed pump runsRuns too short to prove the pump and its driver. Run log against the required run and the limits for the asset’s market (Thresholds by market).Run each pump for the full period, recording start time, suction and discharge pressures, temperatures and fuel level.

Performance, supply and relief

What you seeLikely cause, and what confirms itNext step
Flow test below the rated curveImpeller wear, blocked strainer, or suction restriction. Suction pressure during test; strainer inspection.Check suction pressure and the strainer; overhaul the pump, or replace it where performance cannot be restored.
Cavitation noise during testsLow suction pressure or blocked suction. Suction gauge; tank level.Check suction pressure and tank level, and clear the suction.
No flow tests on recordNo usable test arrangement. Inspection.Install a flow meter or test header so the pump can be tested.
Supply pressure lower than at the last testTown main or tank supply decline. Flow test results compared with the previous and acceptance readings and the asset’s market (Thresholds by market).Trace the decline with the water authority or by tank inspection, and confirm the pump can still meet the design with the supply it now has.
Boosted hydrant outlets below pressure in a testPump or relay pump short of its duty. Pressure at the most disadvantaged outlet in each zone, against the asset’s market (Thresholds by market).Test at the most disadvantaged outlets; overhaul or re-select the pump, or correct the pipework.

Jockey pumps and the pump room

What you seeLikely cause, and what confirms itNext step
Jockey pump starts every few minutesSystem leak or passing valve. Pressure decay test with pumps isolated.Pressure decay test with the pumps isolated; find and repair the leak or passing valve.

Hydrant & Hose Reel Systems

Access, boosters and extensions

What you seeLikely cause, and what confirms itNext step
Booster hidden from the streetAccess obstruction. Site inspection.Clear and protect the access, with signage and lighting, or relocate the booster.
Fire main inlet far from where an appliance can parkAccess shortfall for the fire service. Distance from where an appliance can park to each inlet, against the asset’s market (Thresholds by market).Provide hardstanding within reach, or move the inlet.

Flow, pressure and pressure-reducing valves

What you seeLikely cause, and what confirms itNext step
Flow test below requirement at remote outletsSupply decline, corrosion or closed valves. Pressure readings along the system (Thresholds by market).Take pressure readings along the system; clear blockages, open closed valves and replace corroded pipe.
Street feed hydrant low in the annual testTown main below requirement. Residual pressure at the feed hydrant under flow, against the asset’s market (Thresholds by market).Raise it with the water authority, and add tanks or pumps where the main cannot meet it.

Valves, dry risers, hose reels and freezing

What you seeLikely cause, and what confirms itNext step
Dry riser loses pressure on testLeaking valves or joints. Pressure test and inspection.Pressure test and inspect; repair the valves and joints.
Hose reel leaks when pressurisedAged hose. Inspection.Replace the hose and service the reel.
Hose reels that no longer reach parts of a floor after a fit-outCoverage lost. Hose lay against the current layout (Thresholds by market).Add or move reels to restore coverage.
No standpipe flow test in the last five yearsCapacity unproven. US Department of Defense guidance flow tests standpipes every five years for flow and minimum discharge pressure, and hydrostatically tests dry standpipes (UFM 3-601-02).Flow test at the most remote outlets, and pressure test dry systems.

Passive Fire Protection

Penetrations, walls and cavity barriers

What you seeLikely cause, and what confirms itNext step
Smoke spread between floors in a fire or drillBreached riser penetrations or walls not to slab. Riser and ceiling void survey.Survey every riser and ceiling void; fire stop each breach with a tested system, and complete walls to the slab.
Foam in penetrationsUntested sealing. Product identification.Identify the product; replace untested foam with a tested sealing system.

Fire doors and glazing

What you seeLikely cause, and what confirms itNext step
Doors do not close fullyFailed or disconnected closer, binding, obstruction. Door inspection.Repair or replace the closer, free the binding, and clear the obstruction.
Gaps of several millimetres at door edgesWear, distortion or poor installation. Gap measurement against the door’s evidence and the limits for the asset’s market (Thresholds by market).Adjust or repair the door, or replace it where it cannot meet the standard.
Flat entrance doors of different designsResident replacements. Door survey.Survey them; replace non-compliant doors with certified doorsets.
Smoke doors with hollow-core or thin leavesNot a smoke door. Leaf construction and seals against the asset’s market (Thresholds by market).Replace the leaves with compliant ones, and fit smoke seals.
No record of fire door checks in a block of flatsChecks not being carried out. Check records against the intervals for the asset’s market (Thresholds by market).Start a check regime, and record each door’s gaps, closer and seals.

Structural protection and unverified products

What you seeLikely cause, and what confirms itNext step
Exposed steel with patches of protectionDamage by trades. Structural protection survey.Repair the protection with compatible products, and control trades with permits.

Portable Fire Equipment

Missing, damaged and obstructed units

What you seeLikely cause, and what confirms itNext step
Gauge in the redDischarged or leaking. Weight or pressure check.Replace or recharge the unit.
Service tags out of dateServicing lapsed. Records.Restore the service contract, covering every unit.
Empty bracketsMissing or used unit. Register.Replace the missing unit, and update the register.
Extinguishers on the floor or mounted highNot readily usable. Mounting heights against the asset’s market (Thresholds by market).Mount units on brackets or stands at the right height, beside the exits and hazards they serve.

Wrong types, coverage gaps and PFAS

What you seeLikely cause, and what confirms itNext step
Water extinguisher beside a switchboardWrong type for the hazard. Hazard review.Re-select the type to match the hazard.
Kitchen without blanket or wet chemicalCoverage gap. Hazard review.Add a fire blanket, and a wet chemical extinguisher at commercial cooking.
Extinguishers far apart on a large floorTravel distance too long. Distance to the nearest extinguisher against the asset’s market (Thresholds by market).Add or move units so every point is within distance.

Lithium-ion battery hazards

What you seeLikely cause, and what confirms itNext step
E-bikes and scooters charged in corridors, stairs or plant roomsBattery fire risk on an escape route. Fire risk assessment; where charging actually happens.Move charging off escape routes, to a separated, supervised area with detection.
Swollen, damaged or hot battery packsCell failure that can lead to thermal runaway. Inspection of the pack.Stop charging it, isolate it away from combustibles, and have it removed safely.

Smoke Management Systems

Interfaces and testing

What you seeLikely cause, and what confirms itNext step
AHUs supply air to the fire floor in a testCause-and-effect fault. Integrated test.Repair the interface, update the cause-and-effect matrix, and retest.
No pressure or airflow readings since commissioningPerformance unproven. US Department of Defense guidance operates dedicated smoke control systems semi-annually and others annually, recording airflows and pressure differences for comparison with acceptance results (UFM 3-601-02).Commission a measured test, and keep the readings for comparison next time.

Stair pressure and make-up air

What you seeLikely cause, and what confirms itNext step
Stair doors cannot be opened during a testPressure too high (new seals, failed relief). Door opening force measurement against the limits for the asset’s market (Thresholds by market).Measure the opening force; rebalance the pressurisation, and repair or add relief dampers.
Smoke in stairs during a drillPressure too low or fans not starting. Pressure measurement; interface test.Measure the pressure and test the interfaces; rebalance, or repair the fans.
Atrium smoke fills too low in modelling or testsMake-up air shortfall or enclosure changes. Airflow measurement; layout review.Measure the airflow; restore or add make-up air paths, and review the layout with a fire engineer.

Equipment and alterations

What you seeLikely cause, and what confirms itNext step
Fans run but dampers stay shutSeized dampers or actuator failure. Damper inspection.Replace the seized dampers or actuators, and retest.
Smoke vent obstructed, or replaced with a smaller unitVent area short of the design. Free area measured against the design and the asset’s market (Thresholds by market).Measure the free area, and restore it.
New plant or screens close to a smoke shaft headDischarge compromised. Outlet height and clearances against the asset’s market (Thresholds by market).Survey the shaft head against the design, and move or remove obstructions.

Specialist Suppression Systems

Room integrity and change of use

What you seeLikely cause, and what confirms itNext step
Room integrity test failsPenetrations and gaps added. Door fan test.Seal every penetration with tested products, fit door seals and closers, and retest.
Door fan test predicts a short hold timeRoom too leaky to hold the agent. Predicted hold time against the design and the limits for the asset’s market (Thresholds by market).Seal the leaks with tested products and retest.
Walls, ceilings or doors damaged after a dischargePeak pressure beyond what the enclosure can take. A discharge produces a peak of roughly 240 to 1,200 Pa for a fraction of a second, while suspended ceilings take only about 50 Pa (SFPE).Have pressure relief sized and fitted, and restrain ceiling tiles.

Agents, regulation and occupant safety

What you seeLikely cause, and what confirms itNext step
Halon cylinders presentLegacy system. Labels.Plan decommissioning through approved channels, and replacement with a permitted agent.
Foam concentrate of older typeLikely PFAS-containing foam. Product data; testing.Test the foam; replace PFAS foam with fluorine-free foam, cleaning the system and disposing of the old concentrate.
Carbon dioxide cylinders with no recent weight recordAgent quantity unknown. US Department of Defense guidance verifies high-pressure carbon dioxide by weighing every two years, and checks pre-discharge time delays annually (UFM 3-601-02).Weigh the cylinders and check the time delays; recharge any cylinder found short.

Detection, pre-action and kitchen systems

What you seeLikely cause, and what confirms itNext step
Panel in manual or isolatedLeft after works or a false discharge. Panel status.Return the panel to automatic, and find out why it was left isolated.
Kitchen system label older than six monthsServicing lapsed. US Department of Defense guidance inspects wet chemical systems semi-annually, checking the hazard has not changed and replacing fusible links (UFM 3-601-02).Restore six-monthly servicing, and check the nozzles against the current appliances.