What does it mean when you see this, and what do you do next?
Moyne RossTechnical LibraryUpdated November 14, 2026
Every sign of failure the Technical Library records under Fire Services: 69 signs across 8 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.
Water supply decline or obstruction. Flow test against design curve.
Find the obstruction or supply decline; improve the supply with pumps, tanks or a larger connection.
Fire panel shows valve closed
Impairment not cleared. Valve inspection.
Open and supervise the valve now, and manage impairments with permits and fire watches.
Main drain test pressure lower than at the last test
Supply decline, a partly closed valve or an obstruction. Static and residual pressures compared with the previous reading and the limits for the asset’s market (Thresholds by market).
Confirm every control valve is fully open, then trace the supply; flow test the water supply where the fall is confirmed.
Isolation after works or nuisance alarms. Event log; works records.
Clear the isolations now, and manage future ones with a permit and a daily check.
New tenancy cannot be connected
Panel unsupported or at capacity. Vendor advice; panel loading.
Confirm vendor support and panel loading; plan replacement with a supported addressable system.
Detectors with no sensitivity readings for years
Detectors drifting out of their range. Sensitivity readings from an addressable panel, or tests on site; US Department of Defense guidance tests smoke detector sensitivity every five years (UFM 3-601-02).
Read or test sensitivity, and clean or replace detectors outside their marked range.
Lifts did not home or doors did not release in a test
Interface or cause-and-effect fault. Interface test; matrix review.
Update the cause-and-effect matrix and run a full integrated test.
Brigade not called in a test
Signalling failure, often a retired line. Monitoring centre test; line type.
Test with the monitoring centre; upgrade to supported, preferably dual-path, signalling.
Alarm inaudible in parts of the building
Insufficient sounders or speakers after fit-outs. Sound level and intelligibility test against the limits for the asset’s market (Thresholds by market).
Add sounders or speakers, or a voice system where intelligibility is required.
Alarm faint inside apartments with the entry door shut
Too little sound reaching the units. Sound level at the unit entry doors, or inside the units, against the asset’s market (Thresholds by market).
Measure at the entry doors, and add sounders in the common areas or inside units where the level falls short.
Capacity unproven. US Department of Defense guidance flow tests standpipes every five years for flow and minimum discharge pressure, and hydrostatically tests dry standpipes (UFM 3-601-02).
Flow test at the most remote outlets, and pressure test dry systems.
Repair the interface, update the cause-and-effect matrix, and retest.
No pressure or airflow readings since commissioning
Performance unproven. US Department of Defense guidance operates dedicated smoke control systems semi-annually and others annually, recording airflows and pressure differences for comparison with acceptance results (UFM 3-601-02).
Commission a measured test, and keep the readings for comparison next time.
Seal every penetration with tested products, fit door seals and closers, and retest.
Door fan test predicts a short hold time
Room too leaky to hold the agent. Predicted hold time against the design and the limits for the asset’s market (Thresholds by market).
Seal the leaks with tested products and retest.
Walls, ceilings or doors damaged after a discharge
Peak pressure beyond what the enclosure can take. A discharge produces a peak of roughly 240 to 1,200 Pa for a fraction of a second, while suspended ceilings take only about 50 Pa (SFPE).
Have pressure relief sized and fitted, and restrain ceiling tiles.
Test the foam; replace PFAS foam with fluorine-free foam, cleaning the system and disposing of the old concentrate.
Carbon dioxide cylinders with no recent weight record
Agent quantity unknown. US Department of Defense guidance verifies high-pressure carbon dioxide by weighing every two years, and checks pre-discharge time delays annually (UFM 3-601-02).
Weigh the cylinders and check the time delays; recharge any cylinder found short.
Left after works or a false discharge. Panel status.
Return the panel to automatic, and find out why it was left isolated.
Kitchen system label older than six months
Servicing lapsed. US Department of Defense guidance inspects wet chemical systems semi-annually, checking the hazard has not changed and replacing fusible links (UFM 3-601-02).
Restore six-monthly servicing, and check the nozzles against the current appliances.