Hydraulic Services: signs, causes and next steps
What does it mean when you see this, and what do you do next?
Moyne Ross
Technical Library
Updated November 14, 2026
Every sign of failure the Technical Library records under Hydraulic Services: 56 signs across 7 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.
Scope
A sign usually has more than one possible cause. Each row names the likely one and what would confirm it; none is a diagnosis of a particular building, and none is a price.
What you see Likely cause, and what confirms it Next step Gas smell near the meter Leaking regulator or meter connection. Leak detection.Isolate, and call the network or a licensed gas fitter; repair the regulator or connection. Gas consumption with appliances off Leak in consumer piping. Tightness test.Tightness test; find and repair the leak. Rust and pitting at wall penetrations Corrosion where moisture is trapped. Inspection.Replace the corroded sections, with coatings or materials suited to the environment.
What you see Likely cause, and what confirms it Next step Kitchen gas not cutting off on alarm test Shut-off valve or interface fault. Function test.Repair the shut-off valve or interface, and retest. Uncapped pipe ends Appliances removed without capping. Inspection.Cap them now, and remove redundant pipework. Gas pipework added or altered with no compliance certificate Unverified work. Records of alterations; tightness test and inspection of the new work.Test and certify the work, or have it redone by a licensed gasfitter.
What you see Likely cause, and what confirms it Next step LPG cylinders beside doors, windows, drains or ignition sources Cylinder location against the separation rules. Distances to openings, drains and ignition sources measured against AS/NZS 1596.Relocate the cylinders, or change the openings or ignition sources nearby. LPG tank or cylinders with no inspection or test record Pressure equipment of unknown condition. Supplier records; tank test and inspection dates.Have the supplier inspect and test the installation, and keep the records.
What you see Likely cause, and what confirms it Next step Return loop running cool Circulating pump failure or imbalance. Temperature mapping and pump status, against the asset’s market (Thresholds by market ).Repair the circulating pump, and rebalance the loop. Long waits for hot water at certain outlets Dead legs or loop not reaching that branch. Temperature at outlet over time.Remove dead legs, extend the loop, or heat at the point of use. Positive Legionella result Low storage or loop temperatures, stagnation. Temperature records; outlet use patterns.Disinfect and retest; restore storage and loop temperatures, and flushing.
What you see Likely cause, and what confirms it Next step Very hot water at basins in an aged care home Failed or bypassed TMV. TMV test.Service or replace the TMV now. Hot water too hot at basins in a school, childcare centre or aged care home Scald risk. Delivery temperature at each outlet against the asset’s market (Thresholds by market ).Fit or repair tempering or thermostatic mixing valves and retest every outlet.
What you see Likely cause, and what confirms it Next step Water under a storage tank Tank corroded through or relief valve discharging. Inspection.Replace the tank, or correct the relief valve discharge. Relief valve discharging continuously Thermostat failure or high mains pressure. Temperature and pressure checks.Replace the thermostat, or fit pressure control. Storage heater with no working relief valve, or a valve that has been plugged No protection against over-pressure or flash steam. Relief valve and setting against the asset’s market (Thresholds by market ).Replace the relief valve and drain line, and test it.
What you see Likely cause, and what confirms it Next step Basement flooded after a storm with a power outage Sump pumps without backup power. Power arrangement; incident timeline.Provide backup power for critical sumps, with a monitored high-level alarm. Basement flooded in rain with power on Blocked pumps, failed floats or undersized pit. Pump inspection; capacity check.Clear the pumps, replace floats with level sensors, and check the pit's capacity. Sewage pump tripping repeatedly Ragging from wipes and rags. Pump inspection.Fit vortex or cutter pumps, with screens or signage about wipes.
What you see Likely cause, and what confirms it Next step Booster pumps starting every few seconds Failed pressure vessel or diaphragm. Vessel charge pressure.Replace or recharge the pressure vessel. Upper floors low pressure at peak times Booster capacity or a failed pump. Pressure logging and pump status, against the asset’s market (Thresholds by market ).Repair the failed pump, or upgrade the booster set. Pumps cycling with no inflow Check valve letting water run back. Valve inspection.Replace the check valve.
What you see Likely cause, and what confirms it Next step Rotten-egg smell at a sewage pit or in a plant room Hydrogen sulfide from septic sewage. Gas monitoring before entry, against the exposure limits for the asset’s market (Thresholds by market ).Ventilate the pit, seal the covers, shorten retention time, and treat entry as a confined space. Pit lids corroded, unsealed or not rated for the traffic over them Odour escape and a fall or collapse risk. Lid condition, seals and load rating.Replace with sealed lids of the right load class.
What you see Likely cause, and what confirms it Next step Repeated blockages at the same place Root intrusion, belly or collapse. CCTV survey.CCTV the drain; reline or replace it rather than clearing it again. Subsidence over drain lines Leaking or collapsed drain undermining soil. CCTV.CCTV the drain, repair or replace it, and reinstate the ground. Long, flat drain runs blocking with no root or collapse found Gradient too shallow for the flow. Levels and invert survey against the asset’s market (Thresholds by market ).Relay the run to fall, or add flushing points and access.
What you see Likely cause, and what confirms it Next step Sewer gas odour in a bathroom Dry trap, failed vent or cracked pipe. Smoke test.Refill or replace the trap, repair the vent, or find the cracked pipe. Cast iron stacks leaking along their length Internal corrosion. Inspection; pipe section.Test the wall thickness; reline or replace the stack, riser by riser. Floor wastes and little-used traps smelling in dry weather Traps drying out. Trap seal depth; how often each fixture is used.Fit trap primers or waterless seals, or add the fixtures to a flushing routine.
What you see Likely cause, and what confirms it Next step Leaks from ceilings under bathrooms Wet area membrane failure or pipe leak. Flood test; dye test.Flood test to separate the membrane from the pipes; rectify the wet area or repair the pipe. Sewage in the basement in heavy rain Sewer surcharge without backflow protection. Event timing; relief gully levels.Fit overflow relief gullies at the right level, and backflow valves on low fixtures.
What you see Likely cause, and what confirms it Next step Pool losing water beyond evaporation Shell crack, plumbing leak or failed finish. Bucket test; dye test; pressure testing.Find the leak, and repair the shell, plumbing or finish. Gate that does not latch Hinge or latch failure. Inspection.Close the pool; repair the hinge or latch. Pool fence low, with gaps under it or climbable objects beside it Barrier not stopping a child. Height, gaps and climbable zones measured against the asset’s market (Thresholds by market ).Raise or repair the barrier, and clear the non-climbable zone.
What you see Likely cause, and what confirms it Next step Corroded equipment and electrical panels in the plant room Chlorine fumes from poor storage or ventilation. Inspection.Separate and bund the chemicals, and ventilate the plant room. Cloudy water and complaints of irritation Filtration or chemical dosing problems. Water testing; turnover check.Repair the filtration and dosing, and test the water. Slime and foam in water features Inadequate treatment. Water testing.Set treatment and cleaning regimes, or decommission the feature.
What you see Likely cause, and what confirms it Next step Purple pipe connected to a basin or kitchen tap Cross-connection. Dye or tracer testing.Remove the cross-connection, and label the system. Rainwater or recycled water tank with no backflow protection to the mains Cross-connection risk. Backflow device at the mains connection; device test record.Fit and test a suitable backflow prevention device.
What you see Likely cause, and what confirms it Next step Grease blockages in drains downstream of the arrestor Arrestor undersized, full or with corroded baffles. Size against flow; pump-out dates; internal inspection.Pump out more often, repair the baffles, or upsize the arrestor. Grease blockages upstream of the arrestor Kitchen practices or drain defects. CCTV; kitchen practices.Change kitchen practices, and CCTV the drains. Utility notice for high fats in discharge Overload or bypass. Sampling; connection survey.Remove bypasses, and upsize or add arrestors. No pump-out dockets for months, or dockets with no volumes Arrestor not being emptied as the permit requires. Pump-out records against the trade waste agreement.Set a pump-out contract at the permitted frequency, and keep the dockets.
What you see Likely cause, and what confirms it Next step Strong odour at lids Septic arrestor from infrequent pump-outs, or failed seals. Pump-out records; seal inspection.Pump out more often, and seal the covers. Broken covers Covers not rated for traffic. Cover rating.Fit heavy-duty covers rated for the traffic.
What you see Likely cause, and what confirms it Next step Oil sheen at stormwater outlets from a car park Full or bypassed oil interceptor. Interceptor levels.Empty the interceptor, replace the media and repair the alarm. Oil interceptor alarm silenced or never fitted Full interceptor not detected. Alarm and level probe test; service records.Repair or fit the alarm and empty the interceptor.
What you see Likely cause, and what confirms it Next step Brown water after periods of no use Corroding galvanised steel. Pipe material; internal inspection of a removed section.Plan replacement of the galvanised pipework, riser by riser. Repeated pinhole leaks in copper on the same runs Pitting corrosion from water chemistry. Leak history; water analysis; pipe section examination.Test the water chemistry, and replace the affected runs. Leaks at brass fittings in a plastic system Dezincification. Fitting examination; product type.Replace with dezincification-resistant brass. Night-time water use with the building empty Hidden leak or running cisterns. Meter readings; leak detection.Find and repair the leak, and add smart metering.
What you see Likely cause, and what confirms it Next step Backflow device leaking from the relief port Fouled or failed check valves. Device test.Service or replace the device, and test it. Testable backflow devices with no test record in the last year Protection unverified. Device register and test reports against the water authority’s requirements.Test every device, repair failures, and lodge the reports.
What you see Likely cause, and what confirms it Next step Banging when taps close Water hammer from high pressure or fast-closing valves. Pressure measurement against the asset’s market (Thresholds by market ).Fit pressure-limiting valves and water hammer arrestors. Weak flow at upper floors or remote outlets Pressure below what fixtures need. Pressure logging at the outlets, against the asset’s market (Thresholds by market ).Check valves, filters and boosters, and resize the supply if needed.
Nothing matches that. Try fewer letters.