Every sign of failure the Technical Library records under Hydraulic Services: 56 signs across 7 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.

Gas Services

Leaks, corrosion and damage

What you seeLikely cause, and what confirms itNext step
Gas smell near the meterLeaking regulator or meter connection. Leak detection.Isolate, and call the network or a licensed gas fitter; repair the regulator or connection.
Gas consumption with appliances offLeak in consumer piping. Tightness test.Tightness test; find and repair the leak.
Rust and pitting at wall penetrationsCorrosion where moisture is trapped. Inspection.Replace the corroded sections, with coatings or materials suited to the environment.

Shut-offs, alterations and CSST

What you seeLikely cause, and what confirms itNext step
Kitchen gas not cutting off on alarm testShut-off valve or interface fault. Function test.Repair the shut-off valve or interface, and retest.
Uncapped pipe endsAppliances removed without capping. Inspection.Cap them now, and remove redundant pipework.
Gas pipework added or altered with no compliance certificateUnverified work. Records of alterations; tightness test and inspection of the new work.Test and certify the work, or have it redone by a licensed gasfitter.

LPG

What you seeLikely cause, and what confirms itNext step
LPG cylinders beside doors, windows, drains or ignition sourcesCylinder location against the separation rules. Distances to openings, drains and ignition sources measured against AS/NZS 1596.Relocate the cylinders, or change the openings or ignition sources nearby.
LPG tank or cylinders with no inspection or test recordPressure equipment of unknown condition. Supplier records; tank test and inspection dates.Have the supplier inspect and test the installation, and keep the records.

Hot & Warm Water Plant

Legionella and the loop

What you seeLikely cause, and what confirms itNext step
Return loop running coolCirculating pump failure or imbalance. Temperature mapping and pump status, against the asset’s market (Thresholds by market).Repair the circulating pump, and rebalance the loop.
Long waits for hot water at certain outletsDead legs or loop not reaching that branch. Temperature at outlet over time.Remove dead legs, extend the loop, or heat at the point of use.
Positive Legionella resultLow storage or loop temperatures, stagnation. Temperature records; outlet use patterns.Disinfect and retest; restore storage and loop temperatures, and flushing.

Scalding and TMVs

What you seeLikely cause, and what confirms itNext step
Very hot water at basins in an aged care homeFailed or bypassed TMV. TMV test.Service or replace the TMV now.
Hot water too hot at basins in a school, childcare centre or aged care homeScald risk. Delivery temperature at each outlet against the asset’s market (Thresholds by market).Fit or repair tempering or thermostatic mixing valves and retest every outlet.

Heaters, relief valves and combustion

What you seeLikely cause, and what confirms itNext step
Water under a storage tankTank corroded through or relief valve discharging. Inspection.Replace the tank, or correct the relief valve discharge.
Relief valve discharging continuouslyThermostat failure or high mains pressure. Temperature and pressure checks.Replace the thermostat, or fit pressure control.
Storage heater with no working relief valve, or a valve that has been pluggedNo protection against over-pressure or flash steam. Relief valve and setting against the asset’s market (Thresholds by market).Replace the relief valve and drain line, and test it.

Pumping Systems

Sumps, controls and backup power

What you seeLikely cause, and what confirms itNext step
Basement flooded after a storm with a power outageSump pumps without backup power. Power arrangement; incident timeline.Provide backup power for critical sumps, with a monitored high-level alarm.
Basement flooded in rain with power onBlocked pumps, failed floats or undersized pit. Pump inspection; capacity check.Clear the pumps, replace floats with level sensors, and check the pit's capacity.
Sewage pump tripping repeatedlyRagging from wipes and rags. Pump inspection.Fit vortex or cutter pumps, with screens or signage about wipes.

Booster sets and pressure vessels

What you seeLikely cause, and what confirms itNext step
Booster pumps starting every few secondsFailed pressure vessel or diaphragm. Vessel charge pressure.Replace or recharge the pressure vessel.
Upper floors low pressure at peak timesBooster capacity or a failed pump. Pressure logging and pump status, against the asset’s market (Thresholds by market).Repair the failed pump, or upgrade the booster set.
Pumps cycling with no inflowCheck valve letting water run back. Valve inspection.Replace the check valve.

Sewage pits and gases

What you seeLikely cause, and what confirms itNext step
Rotten-egg smell at a sewage pit or in a plant roomHydrogen sulfide from septic sewage. Gas monitoring before entry, against the exposure limits for the asset’s market (Thresholds by market).Ventilate the pit, seal the covers, shorten retention time, and treat entry as a confined space.
Pit lids corroded, unsealed or not rated for the traffic over themOdour escape and a fall or collapse risk. Lid condition, seals and load rating.Replace with sealed lids of the right load class.

Sanitary & Drainage Systems

Roots, collapse and blockages

What you seeLikely cause, and what confirms itNext step
Repeated blockages at the same placeRoot intrusion, belly or collapse. CCTV survey.CCTV the drain; reline or replace it rather than clearing it again.
Subsidence over drain linesLeaking or collapsed drain undermining soil. CCTV.CCTV the drain, repair or replace it, and reinstate the ground.
Long, flat drain runs blocking with no root or collapse foundGradient too shallow for the flow. Levels and invert survey against the asset’s market (Thresholds by market).Relay the run to fall, or add flushing points and access.

Cast iron stacks and venting

What you seeLikely cause, and what confirms itNext step
Sewer gas odour in a bathroomDry trap, failed vent or cracked pipe. Smoke test.Refill or replace the trap, repair the vent, or find the cracked pipe.
Cast iron stacks leaking along their lengthInternal corrosion. Inspection; pipe section.Test the wall thickness; reline or replace the stack, riser by riser.
Floor wastes and little-used traps smelling in dry weatherTraps drying out. Trap seal depth; how often each fixture is used.Fit trap primers or waterless seals, or add the fixtures to a flushing routine.

Wet areas and sewer surcharge

What you seeLikely cause, and what confirms itNext step
Leaks from ceilings under bathroomsWet area membrane failure or pipe leak. Flood test; dye test.Flood test to separate the membrane from the pipes; rectify the wet area or repair the pipe.
Sewage in the basement in heavy rainSewer surcharge without backflow protection. Event timing; relief gully levels.Fit overflow relief gullies at the right level, and backflow valves on low fixtures.

Specialist Hydraulics

Entrapment, barriers and pool shells

What you seeLikely cause, and what confirms itNext step
Pool losing water beyond evaporationShell crack, plumbing leak or failed finish. Bucket test; dye test; pressure testing.Find the leak, and repair the shell, plumbing or finish.
Gate that does not latchHinge or latch failure. Inspection.Close the pool; repair the hinge or latch.
Pool fence low, with gaps under it or climbable objects beside itBarrier not stopping a child. Height, gaps and climbable zones measured against the asset’s market (Thresholds by market).Raise or repair the barrier, and clear the non-climbable zone.

Chemicals, water quality and features

What you seeLikely cause, and what confirms itNext step
Corroded equipment and electrical panels in the plant roomChlorine fumes from poor storage or ventilation. Inspection.Separate and bund the chemicals, and ventilate the plant room.
Cloudy water and complaints of irritationFiltration or chemical dosing problems. Water testing; turnover check.Repair the filtration and dosing, and test the water.
Slime and foam in water featuresInadequate treatment. Water testing.Set treatment and cleaning regimes, or decommission the feature.

Recycled water and cross-connections

What you seeLikely cause, and what confirms itNext step
Purple pipe connected to a basin or kitchen tapCross-connection. Dye or tracer testing.Remove the cross-connection, and label the system.
Rainwater or recycled water tank with no backflow protection to the mainsCross-connection risk. Backflow device at the mains connection; device test record.Fit and test a suitable backflow prevention device.

Trade Waste Systems

Overload, pump-outs and bypasses

What you seeLikely cause, and what confirms itNext step
Grease blockages in drains downstream of the arrestorArrestor undersized, full or with corroded baffles. Size against flow; pump-out dates; internal inspection.Pump out more often, repair the baffles, or upsize the arrestor.
Grease blockages upstream of the arrestorKitchen practices or drain defects. CCTV; kitchen practices.Change kitchen practices, and CCTV the drains.
Utility notice for high fats in dischargeOverload or bypass. Sampling; connection survey.Remove bypasses, and upsize or add arrestors.
No pump-out dockets for months, or dockets with no volumesArrestor not being emptied as the permit requires. Pump-out records against the trade waste agreement.Set a pump-out contract at the permitted frequency, and keep the dockets.

Corrosion, odour and covers

What you seeLikely cause, and what confirms itNext step
Strong odour at lidsSeptic arrestor from infrequent pump-outs, or failed seals. Pump-out records; seal inspection.Pump out more often, and seal the covers.
Broken coversCovers not rated for traffic. Cover rating.Fit heavy-duty covers rated for the traffic.

Oil interceptors

What you seeLikely cause, and what confirms itNext step
Oil sheen at stormwater outlets from a car parkFull or bypassed oil interceptor. Interceptor levels.Empty the interceptor, replace the media and repair the alarm.
Oil interceptor alarm silenced or never fittedFull interceptor not detected. Alarm and level probe test; service records.Repair or fit the alarm and empty the interceptor.

Water Supply

Corrosion, leaks and valves

What you seeLikely cause, and what confirms itNext step
Brown water after periods of no useCorroding galvanised steel. Pipe material; internal inspection of a removed section.Plan replacement of the galvanised pipework, riser by riser.
Repeated pinhole leaks in copper on the same runsPitting corrosion from water chemistry. Leak history; water analysis; pipe section examination.Test the water chemistry, and replace the affected runs.
Leaks at brass fittings in a plastic systemDezincification. Fitting examination; product type.Replace with dezincification-resistant brass.
Night-time water use with the building emptyHidden leak or running cisterns. Meter readings; leak detection.Find and repair the leak, and add smart metering.

Backflow and tanks

What you seeLikely cause, and what confirms itNext step
Backflow device leaking from the relief portFouled or failed check valves. Device test.Service or replace the device, and test it.
Testable backflow devices with no test record in the last yearProtection unverified. Device register and test reports against the water authority’s requirements.Test every device, repair failures, and lodge the reports.

Lead and pressure

What you seeLikely cause, and what confirms itNext step
Banging when taps closeWater hammer from high pressure or fast-closing valves. Pressure measurement against the asset’s market (Thresholds by market).Fit pressure-limiting valves and water hammer arrestors.
Weak flow at upper floors or remote outletsPressure below what fixtures need. Pressure logging at the outlets, against the asset’s market (Thresholds by market).Check valves, filters and boosters, and resize the supply if needed.