Roofs & Rainwater Goods: signs, causes and next steps
What does it mean when you see this, and what do you do next?
Moyne Ross
Technical Library
Updated November 19, 2026
Every sign of failure the Technical Library records under Roofs & Rainwater Goods: 128 signs across 9 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.
Scope
A sign usually has more than one possible cause. Each row names the likely one and what would confirm it; none is a diagnosis of a particular building, and none is a price.
What you see Likely cause, and what confirms it Next step Stack bending away from the prevailing weather Sulfate attack on mortar. Joints open on the weather side; mortar white and soft.Have an engineer assess the lean; rebuild the upper courses, or the stack from the roof line, if it has gone too far for repointing. Stack loose or cracked at roof level after a storm or earthquake Lateral load on weak masonry. Cracks through bed joints at the roof line; movement by hand.Make safe now: remove loose courses over paths and roofs, then rebuild. Chimney ending below a nearby ridge or taller part of the building Poor draught and fumes re-entering. Height of the terminal against the building around it and the limits for the asset’s market (Thresholds by market ).Extend the flue or fit a suitable terminal, checked against the appliance’s requirements.
What you see Likely cause, and what confirms it Next step Damp on breasts after rain, dry otherwise Water entry at the top or flashings. Flaunching, cap or flashing defects.Repair the flaunching, cap or flashings. Damp on breasts of a disused flue in all weather Open pot and no ventilation. Pot open; fireplace sealed.Cap the pot and ventilate the flue, with a vent at the base of the breast.
What you see Likely cause, and what confirms it Next step Brown staining on the chimney breast Tar or acid condensate through an unsuitable flue. Appliance type; flue unlined.Stop using the appliance on that flue; reline with a liner matched to the fuel. Smoke or fumes in other rooms or adjoining dwellings Liner failure. Smoke test; CCTV.Take the appliance out of use now; smoke test and CCTV the flue, then reline. Staining began after a new boiler or heater was fitted Condensate from an appliance unsuited to the flue. Appliance date; flue unlined or wrong liner.Reline with a liner suited to the new appliance's condensate. Scorched timbers in the roof space next to the stack Past chimney fire or timber built too close. Charring; timber against the flue; cracked liner (Thresholds by market ).Take the appliance out of use until timbers are separated from the flue and the liner is checked. Smoke spilling into the room when the fire is lit Poor draught: obstruction, cold flue, stack too short or downdraught from nearby buildings. Smoke test; obstruction in the flue; stack height relative to the roof and neighbours.Clear any obstruction, then deal with what the smoke test shows, such as a cold flue or a stack too short for its position.
What you see Likely cause, and what confirms it Next step Chimney breast removed in a room below a stack that remains Masonry above left without support. Inspection from the roof space and the room below for brackets or steelwork.Have an engineer confirm the support, and add it where missing. Grey fibrous flue pipe or cowl on an older heater or boiler Possible asbestos cement flue. Asbestos register; sampling by a competent person.Leave it undisturbed until sampled; remove it under asbestos controls when the appliance is replaced.
What you see Likely cause, and what confirms it Next step Fumes from a commercial flue entering the building Discharge too close to air intakes or windows. Flue position against intakes; wind direction when complaints occur.Extend or relocate the flue away from intakes and windows. Grease visible at kitchen duct joints or access panels Cleaning frequency too low or ducts not fully accessible. Deposit depth and cleaning frequency against the asset’s market (Thresholds by market ); cleaning records; access panel spacing.Clean to the required frequency, and add access panels so the whole duct can be cleaned.
What you see Likely cause, and what confirms it Next step Mould on ceilings in lines Thermal bridging at framing. Lines follow joist or rafter spacing.Insulate the bridging framing where the build-up allows, and control vapour. Mould near external walls and corners Missing insulation at the ceiling edge. Insulation stops short of the wall plate.Refit the insulation tight to the wall plate. Hot or cold rooms Gaps or missing insulation. Thermal imaging.Refit and top up where thermal imaging shows gaps. Frost or snow melting early, or in stripes along the framing Heat loss through gaps or bridging. Thermal imaging from inside confirms the pattern.Confirm with thermal imaging from inside, then refit or top up. Droppings, nests and flattened insulation Vermin. Activity in the roof space; damaged wiring nearby.Pest control first, then remove, clean and replace the insulation.
What you see Likely cause, and what confirms it Next step Water drips across a ceiling in cold weather with no rain Condensation. Uniform pattern; underside of sheeting wet; humid space below; no vapour control.Add vapour control and ventilation; more insulation alone will not help. Water stain under one point after rain Leak. Defect in the covering above.Find and fix the leak above; see Roof Coverings. Mould on sarking or roof boards and dark rafters at the eaves Blocked roof-space ventilation. Insulation packed into the eaves; vents covered; humidity high in winter.Clear the eaves, with baffles to keep ventilation paths open. New condensation after insulation was added or upgraded Cold point moved into the roof. Timing follows the upgrade; no vapour control or ventilation provided.Assess the build-up; add vapour control on the warm side and ventilate the roof space. Wet, heavy boards found in a warm flat roof Leak or condensation spreading through the build-up. Cores and moisture survey; see Waterproofing Membranes.Remove the wet insulation and fix the cause; see Waterproofing Membranes.
What you see Likely cause, and what confirms it Next step Ice, frost or delaminated facings inside cold store panels Moist air entering through failed panel joints. Joint seals perished; moisture or ice within the panel.Reseal the joints and replace damaged panels, with vapour sealing on the warm side.
What you see Likely cause, and what confirms it Next step Scorching or discolouration of insulation around a light fitting Insulation in contact with a heat source. Fitting type and clearance; no cover or barrier. Keep the clearance the fitting and the wiring rules require, and allow for the cleared area as lost insulation (Thresholds by market ).Clear insulation from the fitting now; fit a cover or a fitting rated for insulation contact.
What you see Likely cause, and what confirms it Next step Parapet leaning, joints open on one face Differential frost or sulfate expansion. Mortar soft and white on the wet face.Exclude people below if it stands over a public area; have an engineer assess it, then restrain or rebuild. Horizontal crack at roof level, parapet pushed out, corners cracked Roof slab expansion. Concrete roof slab bearing on the wall; no slip joint.Form a slip joint between slab and wall, and repair the cracked masonry. Vertical cracks at regular spacing along a parapet Missing movement joints. Crack spacing regular; no joints in the run; worst at corners.Form movement joints so the cracks do not simply reopen.
What you see Likely cause, and what confirms it Next step Damp at the top of walls inside Coping joints, missing damp-proof course or roof junction. Water test at copings and upstand.Water test the copings and upstand; reset the copings with a damp-proof course or tray. Damp at wall head appearing only in heavy storms Roof drainage overflowing against the parapet. Box gutter or outlet capacity; no overflow through the parapet.Check the box gutter and outlet capacity, and add overflows through the parapet; see Rainwater Systems. Membrane upstand now below the roof surface or ponding line Roof raised by later works. Records of re-roofing or insulation added; upstand height measured.Renew the upstands and flashings, raised to suit the roof. Coping lifted or missing after a storm Fixings corroded or too few. Remaining copings move by hand; fixings rusted.Make safe; reset the copings with new dowels and sound fixings.
What you see Likely cause, and what confirms it Next step Rust staining at cornice or terracotta joints; cracked units Corroding cramps and anchors behind the ornament. Cramps exposed at sample positions; units loose when tested.Make safe now; remove units, replace corroded cramps with stainless steel, and repair or replicate.
What you see Likely cause, and what confirms it Next step Loose louvres after storms Screen fixing or design for wind. Fixings corroded or undersized.Secure or remove loose panels; re-engineer the fixings for current wind loads. Screen panels vibrating or rattling Fixings loosened by plant vibration or overloaded by heavy panels. Bolts loose; panel type heavier than the original design.Retighten or replace the fixings, and check the panels against the original design load.
What you see Likely cause, and what confirms it Next step Parapet top within reach of falling from the roof Parapet too low to serve as guarding. Height above the finished roof measured against edge protection rules and the limits for the asset’s market (Thresholds by market ).Add guardrails on top of or behind the parapet before further roof access.
What you see Likely cause, and what confirms it Next step Leaks inside along the box gutter line, only in heavy storms Overflow: undersized outlet or no overflow. Overflow absent or small; outlet capacity below the catchment's design flow.Add or enlarge overflows, and resize the outlets against current rainfall data. Leaks after re-roofing or adding plant, where there were none before Catchment changed or outlet level raised. Alteration dates match; outlets now above the roof or gutter surface.Recheck the drainage against the changed catchment, and lower or add outlets. Overflow discharging regularly in moderate rain Outlet partly blocked or undersized. Debris in the outlet; capacity check against the catchment.Clear the outlet; if it is clear, it is undersized and needs resizing. Storm leaks on a siphonic roof with clean gutters Siphon breaking at one outlet; design intensity exceeded. Outlet condition and design calculations against current rainfall data.Restore the outlets and re-verify the design as a whole against current rainfall data.
What you see Likely cause, and what confirms it Next step Staining down a wall from an eaves gutter Blocked or corroded gutter overflowing at that point. Debris or perforation above the stain.Clear the gutter, and repair or replace it where perforated. Damp and washouts at the base of a wall Downpipe disconnected from the drain. Pipe ends above ground; drain blocked.Reconnect the downpipe and clear the drain, directing discharge away from footings. Gutter pulling away from the fascia, brackets bent Weight of debris, snow or ice; corroded brackets. Bracket spacing and condition; water held in the gutter.Clear the gutter, and replace corroded brackets at the right spacing. Ponding on a lower roof below a downpipe Downpipe discharging onto the roof without a spreader. Erosion and staining at the discharge point.Fit a spreader, or carry the downpipe to a gutter.
What you see Likely cause, and what confirms it Next step Leaks inside along the box gutter line in any rain Perforated gutter or failed joint. Corrosion or open joint at the leak position.Repair the joint or replace the perforated run. Leaks at an internal stack in a riser Joint failure or outlet clamp loose. Water test at the outlet; joint inspection.Water test the outlet, then remake the joint or tighten the clamp. Rust along the gutter sole, sound elsewhere Water standing from poor fall or blockage. Water present after rain; debris.Correct the falls and clear debris; replace the run where the sole is perforated. Water standing at one end of a box gutter after rain Back fall or sagging sole. Level check along the gutter; water collects away from the outlet.Re-lay the sole to the correct fall, or replace the gutter.
What you see Likely cause, and what confirms it Next step Leak that appears well away from any visible defect Water travelling along the structure or sarking. Trace from inside upslope of the stain; hose test working upward from the lowest point.Find the entry point before replacing anything.
What you see Likely cause, and what confirms it Next step Rust at laps and the bottom metre of sheets, the field sound Normal edge and lap corrosion of coated steel. Corrosion concentrated where water lingers; coating chalked.Programme repair or partial replacement in the near term: treat and coat where the metal is intact; replace the lower run above the gutter where it is not. Holes along the gutter edge or at end laps; daylight from the roof space Corrosion through the sheet where water and debris sit. Holes through the metal on close inspection, with red rust around them.Repair now; replace the failed bays. Even drips on cold, clear mornings, no rain Condensation. Humid space below; no vapour control; uniform pattern; underside corrosion while the top is sound.Correct the cause (vapour control, ventilation) before renewing the covering. A rust stripe below a copper pipe, flue or lead flashing Dissimilar metal run-off. Source above the stripe.Isolate the dissimilar metals and route copper and lead run-off away from coated steel; replace the affected sheets. Staining in a line along a purlin; fixings backed out or washers perished Fixings leaking or backing out. Fixings loose, washers perished, holes elongated on that line.Replace failed fixings with oversized screws and new washers. Sheets buckled between purlins on a long run Thermal movement where expansion joints or oversized holes were not provided. Long sheet runs with no provision for expansion; damage repeats at fixings and laps.Replace the buckled sheets and refix with expansion joints or oversized holes. Torn seams or pans distorted at the clips (standing seam) Concealed clips binding, so the pans cannot move with temperature. Damage repeats at the clip positions along the seam.Free or replace the bound clips and repair the torn seams. Waves in the flat pans, seams closed, no leak Oil canning: stress in the flat sheet. Pans wave but the seams are closed and the fixings sound; no leak.Routine maintenance; a matter of appearance. Rust spots across a new roof within weeks Swarf from cutting and drilling. Small orange spots; no pitting beneath when cleaned.Routine maintenance: remove the swarf before it marks the coating.
What you see Likely cause, and what confirms it Next step Loose ridge cappings, mortar on the ground and in gutters Ridge bedding and pointing failure. Cappings move by hand.Rebed and repoint the ridges and hips. Slipped slates scattered across the roof Nail sickness. Nails rusted through on slates lifted.Refix or replace the slipped slates; where slippage keeps spreading, plan re-slating with stainless steel or copper nails. A line of slipped tiles or slates Batten failure. Batten decayed or broken below.Lift the affected courses, renew the battens and underlay beneath, and reuse the sound slates and tiles. Cracked tiles along the routes people walk to plant and solar Foot traffic to plant and solar arrays; plant mounted directly on the covering. Damage follows the access routes and the equipment positions.Replace the broken tiles; put walkways and plant platforms on separate supports. Concrete tiles weathered to a rough grey surface across whole slopes Concrete tiles erode at the surface and become porous. Erosion uniform across the slopes; tile bodies still whole.Plan replacement by zone, worst first. Uniform, slightly curled grey slates Age: fibre cement slates curl, crack and delaminate. Distortion uniform across the slopes, not scattered.Plan replacement by zone, worst first. In the United Kingdom, test slates laid before 2000 for asbestos first. Health and Safety Executive
What you see Likely cause, and what confirms it Next step Corrugated grey sheets on an older building, or translucent sheets between them Fragile roof. Material identified from age, profile and records; asbestos register.Treat as fragile: no access without staging, covers or guardrails, and manage the asbestos.
What you see Likely cause, and what confirms it Next step Short end laps or open joints on a sheet roof at low pitch Laps too short for the pitch. End laps measured against the limits for the asset’s market (Thresholds by market ).Relay or seal the laps to suit the pitch.
What you see Likely cause, and what confirms it Next step Sarking torn, sagging or missing under a tiled roof after a storm Second line of defence lost. Sarking condition from the roof space against the limits for the asset’s market (Thresholds by market ).Repair or replace the sarking when the covering is lifted.
What you see Likely cause, and what confirms it Next step Tags overdue or missing System cannot be used. Last inspection date against the required interval.Withdraw it from use until inspected; recertify, and book the next inspection before this one lapses. Energy absorber extended or indicator showing System has been shock loaded. Indicator; withdraw from use.Withdraw it from use now and replace the deployed parts. Anchors fixed to sheeting only Anchorage capacity doubtful. Installation records; inspection of fixing.Have the fixing inspected; replace anchors on inadequate substrates. Anchors removed or covered after re-roofing System disturbed. Re-roofing date against recertification records.Reinstate and recertify the anchors before anyone relies on them. Contractors bring their own lanyards and connectors Possible incompatibility with the installed system. Rigging plan silent on required equipment; travellers do not pass brackets.State the compatible equipment on the rigging plan, and check it at induction.
What you see Likely cause, and what confirms it Next step No rigging plan at the access point Users cannot use the system correctly. Absent or out of date against the current roof.Prepare a rigging plan for the roof as it is now, and display it at the access point. Plant or gutters near an edge outside the system's reach Coverage gap. Site plan against maintenance needs.Extend the system to reach every maintained item, or add guardrails along the route. Anchors set back from an edge with a long drop Swing fall or clearance problem. Fall clearance calculation.Calculate the fall clearance; prefer restraint, or move or add anchors. Rigging plan does not match the roof Roof changed since the system was designed. New plant, solar or roof lights not on the plan.Redesign the system for the roof as it is now, and update the plan. Routine plant servicing reliant on fall arrest only System type mismatched to access frequency. Maintenance schedule against system design; no collective protection on the route.Add guardrails or walkways along the routine route.
What you see Likely cause, and what confirms it Next step Access by portable ladder over the gutter No designed access. No fixed ladder, stairs or hatch; no ladder bracket or tie-off.Provide a fixed ladder, stairs or a hatch, or at least a ladder bracket or tie-off point. Roof lights or translucent sheets without mesh, covers or guardrails Fragile surface hazard. Material identified; no protection on the route to plant.Fit mesh, covers or guardrails on the route, and mark the fragile surfaces. Parapet used as edge protection Parapet may be too low after roof works. Parapet height above the finished roof against guarding requirements and the limits for the asset’s market (Thresholds by market ).Measure the parapet above the finished roof; add guardrails where it falls short.
What you see Likely cause, and what confirms it Next step Fall arrest anchors with no rescue plan System incomplete. No rescue procedure, equipment or trained users on record.Write a rescue plan, provide the equipment, and train the users. Fall arrest system with no clearance or rescue calculation Arrest may not stop a fall in time, or a user may be left suspended. (Thresholds by market ).Calculate the clearance below each anchor, and plan and equip a prompt rescue.
What you see Likely cause, and what confirms it Next step Ridge dipped, walls pushed out at the eaves, cracks at wall tops Roof spread. Rafter feet moved on the plate; ties missing or detached; heavier covering.Restore the ties: new collar or ceiling ties, and steel straps across the plate. Ceiling cracks along the wall line on top floors Truss uplift or roof spread. Spread if walls lean out; uplift if seasonal and walls plumb.Tell spread from uplift: if the walls lean out, restore the ties; if the gaps are seasonal, it is truss uplift. Ceiling gaps that open in winter and close in summer Truss uplift. Seasonal; no cracking in external walls; ridge straight.No structural repair is needed: it is a seasonal movement, graded nil. Termite mudding in the roof space or on wall plates Active or past termite attack. Timber pest inspection; damaged timber sounds hollow.Get a timber pest inspection; replace damaged timber and install a management system.
What you see Likely cause, and what confirms it Next step Purlins twisted or buckled near plant Overload or missing bracing. Plant added; bridging missing.Restore the bridging and bracing, and carry the plant on an independent frame. Corrosion along the box gutter line Gutter leaks. Staining continues to the gutter above.Fix the gutter leak above, then treat or replace the corroded steel; see Rainwater Systems. Portal frame bases rusting at ground level Wet ground or raised ground level around the base. Base plates buried or below slab level; section loss measured.Expose the base; clean, treat and recoat it, and keep ground and water away from it. Frame swaying in wind; bracing rods slack or loose Bracing tension lost or bracing removed. Rods slack by hand; turnbuckles or connections loose.Retension or replace the rod bracing.
What you see Likely cause, and what confirms it Next step Roof plane sagging between supports Undersized or overloaded rafters or purlins. Covering weight; member sizes; added loads.Have the members checked against the loads now on the roof, and strengthen them. Ceiling sagging under storage, tanks or services Overloaded ceiling joists. Load placed on the ceiling structure rather than the roof frame.Take the load off the ceiling, and carry tanks and services on the roof structure. Roof plane dished beneath a solar array or plant Added load on members not designed for it. No engineering for the addition; deflection measured.Have the addition engineered, and carry it on an independent frame bearing on the primary structure.
What you see Likely cause, and what confirms it Next step Rust staining and spalls in lines on slab soffits Reinforcement corrosion from membrane failure. Membrane defect above; cover low.Fix the membrane first, then repair the concrete and reinstate cover. Cracks or sag in flat roof panels of a 1950s to 1990s building RAAC planks. Plank identification from below; bearing length; moisture.Treat it as RAAC until identified; prop now where planks are distressed, and restrict access below.
What you see Likely cause, and what confirms it Next step Roof damage concentrated at edges and corners after a storm Tie-down or connection failure. Battens or trusses lifted at their fixings; tie-down below current requirements.Repair, and upgrade the tie-down, most economically when the covering is off. Charred or blackened members in the roof space Past fire. Char depth measured; steel distortion; no assessment on record.Have an engineer assess the members: char depth for timber, distortion for steel.
What you see Likely cause, and what confirms it Next step Yellow, hazy roof sheets UV embrittlement. Age; brittle surface. Treat as fragile: in US workplaces skylights must be guarded, screened or covered, and covers must carry at least twice the load that may be placed on them (OSHA 1910.29 ).Protect them now with mesh, covers or guardrails, and plan replacement with non-fragile rated products. Cracked domes and sheets across a roof after a storm Hail. Storm date; damage on many units; exposed sheets worst.Cover or protect the damaged units now, then replace them.
What you see Likely cause, and what confirms it Next step Leaks around a skylight kerb Kerb flashing detail. Water test.Rebuild the kerb with an upstand to current height and proper flashings. Leaks at the bottom of atrium slopes Gasket or pressure plate failure. Seals shrunk; water test.Replace the gaskets and pressure plates, and clear the drainage channels. Leaks at a translucent sheet lap with the adjacent metal Profile mismatch or lap sealant failure. Sheet profile differs from the metal; sealant missing or perished.Replace the sheet with one matching the metal profile, and reseal the laps. Leaks at the bottom of a dormer cheek or around its window Cheek and sill flashings. Water test at the cheek; decay in the dormer framing.Renew the cheek and sill flashings, and replace decayed timber. Water standing in atrium gutters after rain Blocked or undersized gutters. Debris; outlet capacity against the atrium area.Clear the gutters, and check outlet capacity against the atrium area. Dormer roof sagging or cracking around the opening Inadequate support from the roof structure. Trimming members and support checked from inside.Add support where the roof structure was not adequately trimmed.
What you see Likely cause, and what confirms it Next step Cracked overhead pane with no impact Thermal stress, wire corrosion or nickel sulphide. Glass type and fracture pattern.Protect the area below now; read the fracture pattern, and reglaze with laminated glass.
What you see Likely cause, and what confirms it Next step Drips from frames in cold weather, no rain Condensation. Cold frames; humid space.Ventilate and control humidity in the space below. Space overheating beneath clear roof lights Solar gain. Temperatures follow the sun; roof light area large for the space.Films or external shading now; fewer, better-performing units at replacement.
What you see Likely cause, and what confirms it Next step Smoke vent fails to open on test, or has been fixed shut Actuator, control or seal failure; vent disabled to stop leaks. Test from the fire panel; actuator condition.Repair or replace the actuator, seals and controls, reconnect the vent to the fire system, and test it.
What you see Likely cause, and what confirms it Next step Single leak under a penetration or upstand Detail failure. Water test or electronic leak detection at the detail.Water test or use electronic leak detection at the detail, then renew it. Leaks in a line across the roof Seam failure. Probing seams finds open laps along the line.Probe every seam on the roof, and reweld or re-tape the open laps. Leak under newer plant or a cable penetration Later penetration sealed with mastic. Penetration post-dates the membrane; no proper flashing.Replace the mastic seal with a proper flashing. Leak at a wall head below a parapet Upstand too low, termination failed, or coping and wall above leaking. Water test above the termination first, then the upstand.Test from the top down: the coping and wall first, then the upstand. Punctures and patches along the route to plant Foot traffic and dropped tools. Damage concentrated on the access path; no walkway.Repair the punctures, and lay walkways to the plant.
What you see Likely cause, and what confirms it Next step Leaks moving around, continuing after rain Wet insulation spreading water. Cores show saturated insulation; thermography shows wet areas.Core and moisture-survey the roof; widespread wet insulation means strip and replace. Spongy areas underfoot Wet insulation. Cores and moisture survey.Core and survey; remove the wet insulation before any repair. Leaks on a ballasted or paved roof appearing far from any visible defect Water travelling beneath the build-up. Electronic leak detection locates the breach.Use electronic leak detection to locate the breach under the build-up. Drips from the soffit of a cold roof on clear mornings Condensation within the build-up. Vapour control and ventilation absent; timing follows temperature, not rain.Add vapour control and ventilation; see Insulation. Wet soil and leaks below a planter Root ingress or blocked drainage layer. Roots through the membrane; drainage layer clogged.Clear the drainage layer, and repair the membrane with a root barrier.
What you see Likely cause, and what confirms it Next step Membrane pulled tight at upstands, tearing at the angle EPDM shrinkage. Membrane bridges the angle; field is slack-free.Renew the upstand details, allowing for the shrinkage. Membrane cracks when folded; shrinkage at laps PVC plasticiser loss. Age and product; cracking at stress points.Plan replacement; the membrane is at the end of its life. Blisters over the field Trapped moisture or poor adhesion. Blisters cut show moisture; not structural on their own.Leave dry blisters alone and monitor them; repair any that split. Liquid coating peeling over large areas Application thickness or substrate. Film thickness readings; substrate condition.Check film thickness and the substrate; strip and reapply where the coating has failed. Split running in a straight line across the roof Unaccommodated movement over a deck or structural joint. Split follows a joint below; no movement joint in the membrane.Form a movement joint in the membrane over the joint below.
What you see Likely cause, and what confirms it Next step Ponding lasting days, staining in rings Inadequate falls, blocked outlets or deck deflection. Level survey; outlet condition; deck deflection measured.Clear the outlets, survey the levels, and correct the falls or add outlets.
What you see Likely cause, and what confirms it Next step Old bitumen felt, mastic or roof coating on a building of the 1950s to 1980s Possible asbestos in the membrane, mastic or coating. Asbestos register; sampling by a competent person before cutting or stripping.Sample first; overlay where suitable, or remove under asbestos controls. Grey fibrous sheet or board beneath an old membrane Possible asbestos substrate. Inspection and sampling at an opening.Avoid drilling or cutting until sampled; plan removal or encapsulation with the re-roof.