Every sign of failure the Technical Library records under Roofs & Rainwater Goods: 128 signs across 9 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.

Chimney Stacks & Flues

The stack: lean, weathering and wind

What you seeLikely cause, and what confirms itNext step
Stack bending away from the prevailing weatherSulfate attack on mortar. Joints open on the weather side; mortar white and soft.Have an engineer assess the lean; rebuild the upper courses, or the stack from the roof line, if it has gone too far for repointing.
Stack loose or cracked at roof level after a storm or earthquakeLateral load on weak masonry. Cracks through bed joints at the roof line; movement by hand.Make safe now: remove loose courses over paths and roofs, then rebuild.
Chimney ending below a nearby ridge or taller part of the buildingPoor draught and fumes re-entering. Height of the terminal against the building around it and the limits for the asset’s market (Thresholds by market).Extend the flue or fit a suitable terminal, checked against the appliance’s requirements.

Flashings, water and staining

What you seeLikely cause, and what confirms itNext step
Damp on breasts after rain, dry otherwiseWater entry at the top or flashings. Flaunching, cap or flashing defects.Repair the flaunching, cap or flashings.
Damp on breasts of a disused flue in all weatherOpen pot and no ventilation. Pot open; fireplace sealed.Cap the pot and ventilate the flue, with a vent at the base of the breast.

Flues, liners, appliances and fire

What you seeLikely cause, and what confirms itNext step
Brown staining on the chimney breastTar or acid condensate through an unsuitable flue. Appliance type; flue unlined.Stop using the appliance on that flue; reline with a liner matched to the fuel.
Smoke or fumes in other rooms or adjoining dwellingsLiner failure. Smoke test; CCTV.Take the appliance out of use now; smoke test and CCTV the flue, then reline.
Staining began after a new boiler or heater was fittedCondensate from an appliance unsuited to the flue. Appliance date; flue unlined or wrong liner.Reline with a liner suited to the new appliance's condensate.
Scorched timbers in the roof space next to the stackPast chimney fire or timber built too close. Charring; timber against the flue; cracked liner (Thresholds by market).Take the appliance out of use until timbers are separated from the flue and the liner is checked.
Smoke spilling into the room when the fire is litPoor draught: obstruction, cold flue, stack too short or downdraught from nearby buildings. Smoke test; obstruction in the flue; stack height relative to the roof and neighbours.Clear any obstruction, then deal with what the smoke test shows, such as a cold flue or a stack too short for its position.

Removed breasts, shared stacks and asbestos flues

What you seeLikely cause, and what confirms itNext step
Chimney breast removed in a room below a stack that remainsMasonry above left without support. Inspection from the roof space and the room below for brackets or steelwork.Have an engineer confirm the support, and add it where missing.
Grey fibrous flue pipe or cowl on an older heater or boilerPossible asbestos cement flue. Asbestos register; sampling by a competent person.Leave it undisturbed until sampled; remove it under asbestos controls when the appliance is replaced.

Kitchen exhaust and tall stacks

What you seeLikely cause, and what confirms itNext step
Fumes from a commercial flue entering the buildingDischarge too close to air intakes or windows. Flue position against intakes; wind direction when complaints occur.Extend or relocate the flue away from intakes and windows.
Grease visible at kitchen duct joints or access panelsCleaning frequency too low or ducts not fully accessible. Deposit depth and cleaning frequency against the asset’s market (Thresholds by market); cleaning records; access panel spacing.Clean to the required frequency, and add access panels so the whole duct can be cleaned.

Insulation

Gaps, bridging and vermin

What you seeLikely cause, and what confirms itNext step
Mould on ceilings in linesThermal bridging at framing. Lines follow joist or rafter spacing.Insulate the bridging framing where the build-up allows, and control vapour.
Mould near external walls and cornersMissing insulation at the ceiling edge. Insulation stops short of the wall plate.Refit the insulation tight to the wall plate.
Hot or cold roomsGaps or missing insulation. Thermal imaging.Refit and top up where thermal imaging shows gaps.
Frost or snow melting early, or in stripes along the framingHeat loss through gaps or bridging. Thermal imaging from inside confirms the pattern.Confirm with thermal imaging from inside, then refit or top up.
Droppings, nests and flattened insulationVermin. Activity in the roof space; damaged wiring nearby.Pest control first, then remove, clean and replace the insulation.

Condensation, wetting and ventilation

What you seeLikely cause, and what confirms itNext step
Water drips across a ceiling in cold weather with no rainCondensation. Uniform pattern; underside of sheeting wet; humid space below; no vapour control.Add vapour control and ventilation; more insulation alone will not help.
Water stain under one point after rainLeak. Defect in the covering above.Find and fix the leak above; see Roof Coverings.
Mould on sarking or roof boards and dark rafters at the eavesBlocked roof-space ventilation. Insulation packed into the eaves; vents covered; humidity high in winter.Clear the eaves, with baffles to keep ventilation paths open.
New condensation after insulation was added or upgradedCold point moved into the roof. Timing follows the upgrade; no vapour control or ventilation provided.Assess the build-up; add vapour control on the warm side and ventilate the roof space.
Wet, heavy boards found in a warm flat roofLeak or condensation spreading through the build-up. Cores and moisture survey; see Waterproofing Membranes.Remove the wet insulation and fix the cause; see Waterproofing Membranes.

Inverted roofs and sandwich panels

What you seeLikely cause, and what confirms itNext step
Ice, frost or delaminated facings inside cold store panelsMoist air entering through failed panel joints. Joint seals perished; moisture or ice within the panel.Reseal the joints and replace damaged panels, with vapour sealing on the warm side.

Fire, electrical hazards and spray foam

What you seeLikely cause, and what confirms itNext step
Scorching or discolouration of insulation around a light fittingInsulation in contact with a heat source. Fitting type and clearance; no cover or barrier. Keep the clearance the fitting and the wiring rules require, and allow for the cleared area as lost insulation (Thresholds by market).Clear insulation from the fitting now; fit a cover or a fitting rated for insulation contact.

Plant Screens & Parapets

Lean, slab expansion, ties and movement

What you seeLikely cause, and what confirms itNext step
Parapet leaning, joints open on one faceDifferential frost or sulfate expansion. Mortar soft and white on the wet face.Exclude people below if it stands over a public area; have an engineer assess it, then restrain or rebuild.
Horizontal crack at roof level, parapet pushed out, corners crackedRoof slab expansion. Concrete roof slab bearing on the wall; no slip joint.Form a slip joint between slab and wall, and repair the cracked masonry.
Vertical cracks at regular spacing along a parapetMissing movement joints. Crack spacing regular; no joints in the run; worst at corners.Form movement joints so the cracks do not simply reopen.

Copings and the roof junction

What you seeLikely cause, and what confirms itNext step
Damp at the top of walls insideCoping joints, missing damp-proof course or roof junction. Water test at copings and upstand.Water test the copings and upstand; reset the copings with a damp-proof course or tray.
Damp at wall head appearing only in heavy stormsRoof drainage overflowing against the parapet. Box gutter or outlet capacity; no overflow through the parapet.Check the box gutter and outlet capacity, and add overflows through the parapet; see Rainwater Systems.
Membrane upstand now below the roof surface or ponding lineRoof raised by later works. Records of re-roofing or insulation added; upstand height measured.Renew the upstands and flashings, raised to suit the roof.
Coping lifted or missing after a stormFixings corroded or too few. Remaining copings move by hand; fixings rusted.Make safe; reset the copings with new dowels and sound fixings.

Ornament and concrete parapets

What you seeLikely cause, and what confirms itNext step
Rust staining at cornice or terracotta joints; cracked unitsCorroding cramps and anchors behind the ornament. Cramps exposed at sample positions; units loose when tested.Make safe now; remove units, replace corroded cramps with stainless steel, and repair or replicate.

Plant screens

What you seeLikely cause, and what confirms itNext step
Loose louvres after stormsScreen fixing or design for wind. Fixings corroded or undersized.Secure or remove loose panels; re-engineer the fixings for current wind loads.
Screen panels vibrating or rattlingFixings loosened by plant vibration or overloaded by heavy panels. Bolts loose; panel type heavier than the original design.Retighten or replace the fixings, and check the panels against the original design load.

Parapets as roof edge protection

What you seeLikely cause, and what confirms itNext step
Parapet top within reach of falling from the roofParapet too low to serve as guarding. Height above the finished roof measured against edge protection rules and the limits for the asset’s market (Thresholds by market).Add guardrails on top of or behind the parapet before further roof access.

Rainwater Systems

Capacity, overflows and changed catchments

What you seeLikely cause, and what confirms itNext step
Leaks inside along the box gutter line, only in heavy stormsOverflow: undersized outlet or no overflow. Overflow absent or small; outlet capacity below the catchment's design flow.Add or enlarge overflows, and resize the outlets against current rainfall data.
Leaks after re-roofing or adding plant, where there were none beforeCatchment changed or outlet level raised. Alteration dates match; outlets now above the roof or gutter surface.Recheck the drainage against the changed catchment, and lower or add outlets.
Overflow discharging regularly in moderate rainOutlet partly blocked or undersized. Debris in the outlet; capacity check against the catchment.Clear the outlet; if it is clear, it is undersized and needs resizing.
Storm leaks on a siphonic roof with clean guttersSiphon breaking at one outlet; design intensity exceeded. Outlet condition and design calculations against current rainfall data.Restore the outlets and re-verify the design as a whole against current rainfall data.

Blockage, ponding and ice

What you seeLikely cause, and what confirms itNext step
Staining down a wall from an eaves gutterBlocked or corroded gutter overflowing at that point. Debris or perforation above the stain.Clear the gutter, and repair or replace it where perforated.
Damp and washouts at the base of a wallDownpipe disconnected from the drain. Pipe ends above ground; drain blocked.Reconnect the downpipe and clear the drain, directing discharge away from footings.
Gutter pulling away from the fascia, brackets bentWeight of debris, snow or ice; corroded brackets. Bracket spacing and condition; water held in the gutter.Clear the gutter, and replace corroded brackets at the right spacing.
Ponding on a lower roof below a downpipeDownpipe discharging onto the roof without a spreader. Erosion and staining at the discharge point.Fit a spreader, or carry the downpipe to a gutter.

Corrosion, joints and movement

What you seeLikely cause, and what confirms itNext step
Leaks inside along the box gutter line in any rainPerforated gutter or failed joint. Corrosion or open joint at the leak position.Repair the joint or replace the perforated run.
Leaks at an internal stack in a riserJoint failure or outlet clamp loose. Water test at the outlet; joint inspection.Water test the outlet, then remake the joint or tighten the clamp.
Rust along the gutter sole, sound elsewhereWater standing from poor fall or blockage. Water present after rain; debris.Correct the falls and clear debris; replace the run where the sole is perforated.
Water standing at one end of a box gutter after rainBack fall or sagging sole. Level check along the gutter; water collects away from the outlet.Re-lay the sole to the correct fall, or replace the gutter.

Roof Coverings

Where roofs actually leak

What you seeLikely cause, and what confirms itNext step
Leak that appears well away from any visible defectWater travelling along the structure or sarking. Trace from inside upslope of the stain; hose test working upward from the lowest point.Find the entry point before replacing anything.

Metal sheet: laps, fixings and condensation

What you seeLikely cause, and what confirms itNext step
Rust at laps and the bottom metre of sheets, the field soundNormal edge and lap corrosion of coated steel. Corrosion concentrated where water lingers; coating chalked.Programme repair or partial replacement in the near term: treat and coat where the metal is intact; replace the lower run above the gutter where it is not.
Holes along the gutter edge or at end laps; daylight from the roof spaceCorrosion through the sheet where water and debris sit. Holes through the metal on close inspection, with red rust around them.Repair now; replace the failed bays.
Even drips on cold, clear mornings, no rainCondensation. Humid space below; no vapour control; uniform pattern; underside corrosion while the top is sound.Correct the cause (vapour control, ventilation) before renewing the covering.
A rust stripe below a copper pipe, flue or lead flashingDissimilar metal run-off. Source above the stripe.Isolate the dissimilar metals and route copper and lead run-off away from coated steel; replace the affected sheets.
Staining in a line along a purlin; fixings backed out or washers perishedFixings leaking or backing out. Fixings loose, washers perished, holes elongated on that line.Replace failed fixings with oversized screws and new washers.
Sheets buckled between purlins on a long runThermal movement where expansion joints or oversized holes were not provided. Long sheet runs with no provision for expansion; damage repeats at fixings and laps.Replace the buckled sheets and refix with expansion joints or oversized holes.
Torn seams or pans distorted at the clips (standing seam)Concealed clips binding, so the pans cannot move with temperature. Damage repeats at the clip positions along the seam.Free or replace the bound clips and repair the torn seams.
Waves in the flat pans, seams closed, no leakOil canning: stress in the flat sheet. Pans wave but the seams are closed and the fixings sound; no leak.Routine maintenance; a matter of appearance.
Rust spots across a new roof within weeksSwarf from cutting and drilling. Small orange spots; no pitting beneath when cleaned.Routine maintenance: remove the swarf before it marks the coating.

Tiles and slates

What you seeLikely cause, and what confirms itNext step
Loose ridge cappings, mortar on the ground and in guttersRidge bedding and pointing failure. Cappings move by hand.Rebed and repoint the ridges and hips.
Slipped slates scattered across the roofNail sickness. Nails rusted through on slates lifted.Refix or replace the slipped slates; where slippage keeps spreading, plan re-slating with stainless steel or copper nails.
A line of slipped tiles or slatesBatten failure. Batten decayed or broken below.Lift the affected courses, renew the battens and underlay beneath, and reuse the sound slates and tiles.
Cracked tiles along the routes people walk to plant and solarFoot traffic to plant and solar arrays; plant mounted directly on the covering. Damage follows the access routes and the equipment positions.Replace the broken tiles; put walkways and plant platforms on separate supports.
Concrete tiles weathered to a rough grey surface across whole slopesConcrete tiles erode at the surface and become porous. Erosion uniform across the slopes; tile bodies still whole.Plan replacement by zone, worst first.
Uniform, slightly curled grey slatesAge: fibre cement slates curl, crack and delaminate. Distortion uniform across the slopes, not scattered.Plan replacement by zone, worst first. In the United Kingdom, test slates laid before 2000 for asbestos first. Health and Safety Executive

Asbestos cement and fragile roofs

What you seeLikely cause, and what confirms itNext step
Corrugated grey sheets on an older building, or translucent sheets between themFragile roof. Material identified from age, profile and records; asbestos register.Treat as fragile: no access without staging, covers or guardrails, and manage the asbestos.

Shingles, lead, copper and zinc

What you seeLikely cause, and what confirms itNext step
Short end laps or open joints on a sheet roof at low pitchLaps too short for the pitch. End laps measured against the limits for the asset’s market (Thresholds by market).Relay or seal the laps to suit the pitch.

After hail or a storm

What you seeLikely cause, and what confirms itNext step
Sarking torn, sagging or missing under a tiled roof after a stormSecond line of defence lost. Sarking condition from the roof space against the limits for the asset’s market (Thresholds by market).Repair or replace the sarking when the covering is lifted.

Roof Safety Systems

Certification and the hardware

What you seeLikely cause, and what confirms itNext step
Tags overdue or missingSystem cannot be used. Last inspection date against the required interval.Withdraw it from use until inspected; recertify, and book the next inspection before this one lapses.
Energy absorber extended or indicator showingSystem has been shock loaded. Indicator; withdraw from use.Withdraw it from use now and replace the deployed parts.
Anchors fixed to sheeting onlyAnchorage capacity doubtful. Installation records; inspection of fixing.Have the fixing inspected; replace anchors on inadequate substrates.
Anchors removed or covered after re-roofingSystem disturbed. Re-roofing date against recertification records.Reinstate and recertify the anchors before anyone relies on them.
Contractors bring their own lanyards and connectorsPossible incompatibility with the installed system. Rigging plan silent on required equipment; travellers do not pass brackets.State the compatible equipment on the rigging plan, and check it at induction.

Coverage, clearance and the wrong system

What you seeLikely cause, and what confirms itNext step
No rigging plan at the access pointUsers cannot use the system correctly. Absent or out of date against the current roof.Prepare a rigging plan for the roof as it is now, and display it at the access point.
Plant or gutters near an edge outside the system's reachCoverage gap. Site plan against maintenance needs.Extend the system to reach every maintained item, or add guardrails along the route.
Anchors set back from an edge with a long dropSwing fall or clearance problem. Fall clearance calculation.Calculate the fall clearance; prefer restraint, or move or add anchors.
Rigging plan does not match the roofRoof changed since the system was designed. New plant, solar or roof lights not on the plan.Redesign the system for the roof as it is now, and update the plan.
Routine plant servicing reliant on fall arrest onlySystem type mismatched to access frequency. Maintenance schedule against system design; no collective protection on the route.Add guardrails or walkways along the routine route.

Access, fragile surfaces and guardrails

What you seeLikely cause, and what confirms itNext step
Access by portable ladder over the gutterNo designed access. No fixed ladder, stairs or hatch; no ladder bracket or tie-off.Provide a fixed ladder, stairs or a hatch, or at least a ladder bracket or tie-off point.
Roof lights or translucent sheets without mesh, covers or guardrailsFragile surface hazard. Material identified; no protection on the route to plant.Fit mesh, covers or guardrails on the route, and mark the fragile surfaces.
Parapet used as edge protectionParapet may be too low after roof works. Parapet height above the finished roof against guarding requirements and the limits for the asset’s market (Thresholds by market).Measure the parapet above the finished roof; add guardrails where it falls short.

Rescue

What you seeLikely cause, and what confirms itNext step
Fall arrest anchors with no rescue planSystem incomplete. No rescue procedure, equipment or trained users on record.Write a rescue plan, provide the equipment, and train the users.
Fall arrest system with no clearance or rescue calculationArrest may not stop a fall in time, or a user may be left suspended. (Thresholds by market).Calculate the clearance below each anchor, and plan and equip a prompt rescue.

Roof Structure

Spread, trusses and decay

What you seeLikely cause, and what confirms itNext step
Ridge dipped, walls pushed out at the eaves, cracks at wall topsRoof spread. Rafter feet moved on the plate; ties missing or detached; heavier covering.Restore the ties: new collar or ceiling ties, and steel straps across the plate.
Ceiling cracks along the wall line on top floorsTruss uplift or roof spread. Spread if walls lean out; uplift if seasonal and walls plumb.Tell spread from uplift: if the walls lean out, restore the ties; if the gaps are seasonal, it is truss uplift.
Ceiling gaps that open in winter and close in summerTruss uplift. Seasonal; no cracking in external walls; ridge straight.No structural repair is needed: it is a seasonal movement, graded nil.
Termite mudding in the roof space or on wall platesActive or past termite attack. Timber pest inspection; damaged timber sounds hollow.Get a timber pest inspection; replace damaged timber and install a management system.

Steel: corrosion, bracing and connections

What you seeLikely cause, and what confirms itNext step
Purlins twisted or buckled near plantOverload or missing bracing. Plant added; bridging missing.Restore the bridging and bracing, and carry the plant on an independent frame.
Corrosion along the box gutter lineGutter leaks. Staining continues to the gutter above.Fix the gutter leak above, then treat or replace the corroded steel; see Rainwater Systems.
Portal frame bases rusting at ground levelWet ground or raised ground level around the base. Base plates buried or below slab level; section loss measured.Expose the base; clean, treat and recoat it, and keep ground and water away from it.
Frame swaying in wind; bracing rods slack or looseBracing tension lost or bracing removed. Rods slack by hand; turnbuckles or connections loose.Retension or replace the rod bracing.

Overload, snow and ponding

What you seeLikely cause, and what confirms itNext step
Roof plane sagging between supportsUndersized or overloaded rafters or purlins. Covering weight; member sizes; added loads.Have the members checked against the loads now on the roof, and strengthen them.
Ceiling sagging under storage, tanks or servicesOverloaded ceiling joists. Load placed on the ceiling structure rather than the roof frame.Take the load off the ceiling, and carry tanks and services on the roof structure.
Roof plane dished beneath a solar array or plantAdded load on members not designed for it. No engineering for the addition; deflection measured.Have the addition engineered, and carry it on an independent frame bearing on the primary structure.

Concrete slabs and RAAC

What you seeLikely cause, and what confirms itNext step
Rust staining and spalls in lines on slab soffitsReinforcement corrosion from membrane failure. Membrane defect above; cover low.Fix the membrane first, then repair the concrete and reinstate cover.
Cracks or sag in flat roof panels of a 1950s to 1990s buildingRAAC planks. Plank identification from below; bearing length; moisture.Treat it as RAAC until identified; prop now where planks are distressed, and restrict access below.

Wind tie-down and fire damage

What you seeLikely cause, and what confirms itNext step
Roof damage concentrated at edges and corners after a stormTie-down or connection failure. Battens or trusses lifted at their fixings; tie-down below current requirements.Repair, and upgrade the tie-down, most economically when the covering is off.
Charred or blackened members in the roof spacePast fire. Char depth measured; steel distortion; no assessment on record.Have an engineer assess the members: char depth for timber, distortion for steel.

Skylights, Dormers & Glazed Atria

Fragility, embrittlement and hail

What you seeLikely cause, and what confirms itNext step
Yellow, hazy roof sheetsUV embrittlement. Age; brittle surface. Treat as fragile: in US workplaces skylights must be guarded, screened or covered, and covers must carry at least twice the load that may be placed on them (OSHA 1910.29).Protect them now with mesh, covers or guardrails, and plan replacement with non-fragile rated products.
Cracked domes and sheets across a roof after a stormHail. Storm date; damage on many units; exposed sheets worst.Cover or protect the damaged units now, then replace them.

Leaks at kerbs, seals and dormers

What you seeLikely cause, and what confirms itNext step
Leaks around a skylight kerbKerb flashing detail. Water test.Rebuild the kerb with an upstand to current height and proper flashings.
Leaks at the bottom of atrium slopesGasket or pressure plate failure. Seals shrunk; water test.Replace the gaskets and pressure plates, and clear the drainage channels.
Leaks at a translucent sheet lap with the adjacent metalProfile mismatch or lap sealant failure. Sheet profile differs from the metal; sealant missing or perished.Replace the sheet with one matching the metal profile, and reseal the laps.
Leaks at the bottom of a dormer cheek or around its windowCheek and sill flashings. Water test at the cheek; decay in the dormer framing.Renew the cheek and sill flashings, and replace decayed timber.
Water standing in atrium gutters after rainBlocked or undersized gutters. Debris; outlet capacity against the atrium area.Clear the gutters, and check outlet capacity against the atrium area.
Dormer roof sagging or cracking around the openingInadequate support from the roof structure. Trimming members and support checked from inside.Add support where the roof structure was not adequately trimmed.

Overhead glass and atrium structure

What you seeLikely cause, and what confirms itNext step
Cracked overhead pane with no impactThermal stress, wire corrosion or nickel sulphide. Glass type and fracture pattern.Protect the area below now; read the fracture pattern, and reglaze with laminated glass.

Condensation, heat and glare

What you seeLikely cause, and what confirms itNext step
Drips from frames in cold weather, no rainCondensation. Cold frames; humid space.Ventilate and control humidity in the space below.
Space overheating beneath clear roof lightsSolar gain. Temperatures follow the sun; roof light area large for the space.Films or external shading now; fewer, better-performing units at replacement.

Smoke vents

What you seeLikely cause, and what confirms itNext step
Smoke vent fails to open on test, or has been fixed shutActuator, control or seal failure; vent disabled to stop leaks. Test from the fire panel; actuator condition.Repair or replace the actuator, seals and controls, reconnect the vent to the fire system, and test it.

Waterproofing Membranes

Details, seams and penetrations

What you seeLikely cause, and what confirms itNext step
Single leak under a penetration or upstandDetail failure. Water test or electronic leak detection at the detail.Water test or use electronic leak detection at the detail, then renew it.
Leaks in a line across the roofSeam failure. Probing seams finds open laps along the line.Probe every seam on the roof, and reweld or re-tape the open laps.
Leak under newer plant or a cable penetrationLater penetration sealed with mastic. Penetration post-dates the membrane; no proper flashing.Replace the mastic seal with a proper flashing.
Leak at a wall head below a parapetUpstand too low, termination failed, or coping and wall above leaking. Water test above the termination first, then the upstand.Test from the top down: the coping and wall first, then the upstand.
Punctures and patches along the route to plantFoot traffic and dropped tools. Damage concentrated on the access path; no walkway.Repair the punctures, and lay walkways to the plant.

Wet insulation, inverted and green roofs

What you seeLikely cause, and what confirms itNext step
Leaks moving around, continuing after rainWet insulation spreading water. Cores show saturated insulation; thermography shows wet areas.Core and moisture-survey the roof; widespread wet insulation means strip and replace.
Spongy areas underfootWet insulation. Cores and moisture survey.Core and survey; remove the wet insulation before any repair.
Leaks on a ballasted or paved roof appearing far from any visible defectWater travelling beneath the build-up. Electronic leak detection locates the breach.Use electronic leak detection to locate the breach under the build-up.
Drips from the soffit of a cold roof on clear morningsCondensation within the build-up. Vapour control and ventilation absent; timing follows temperature, not rain.Add vapour control and ventilation; see Insulation.
Wet soil and leaks below a planterRoot ingress or blocked drainage layer. Roots through the membrane; drainage layer clogged.Clear the drainage layer, and repair the membrane with a root barrier.

Ageing, blisters, coatings and movement

What you seeLikely cause, and what confirms itNext step
Membrane pulled tight at upstands, tearing at the angleEPDM shrinkage. Membrane bridges the angle; field is slack-free.Renew the upstand details, allowing for the shrinkage.
Membrane cracks when folded; shrinkage at lapsPVC plasticiser loss. Age and product; cracking at stress points.Plan replacement; the membrane is at the end of its life.
Blisters over the fieldTrapped moisture or poor adhesion. Blisters cut show moisture; not structural on their own.Leave dry blisters alone and monitor them; repair any that split.
Liquid coating peeling over large areasApplication thickness or substrate. Film thickness readings; substrate condition.Check film thickness and the substrate; strip and reapply where the coating has failed.
Split running in a straight line across the roofUnaccommodated movement over a deck or structural joint. Split follows a joint below; no movement joint in the membrane.Form a movement joint in the membrane over the joint below.

Ponding and wind

What you seeLikely cause, and what confirms itNext step
Ponding lasting days, staining in ringsInadequate falls, blocked outlets or deck deflection. Level survey; outlet condition; deck deflection measured.Clear the outlets, survey the levels, and correct the falls or add outlets.

Older membranes and asbestos

What you seeLikely cause, and what confirms itNext step
Old bitumen felt, mastic or roof coating on a building of the 1950s to 1980sPossible asbestos in the membrane, mastic or coating. Asbestos register; sampling by a competent person before cutting or stripping.Sample first; overlay where suitable, or remove under asbestos controls.
Grey fibrous sheet or board beneath an old membranePossible asbestos substrate. Inspection and sampling at an opening.Avoid drilling or cutting until sampled; plan removal or encapsulation with the re-roof.