What does it mean when you see this, and what do you do next?
Moyne RossTechnical LibraryUpdated November 14, 2026
Every sign of failure the Technical Library records under Superstructure: 32 signs across 4 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.
Inadequate bearing or padstone. Opening up at the bearing.
Open up the bearing; add a padstone or spreader beam.
Dropped brickwork over an opening
Failed lintel or spreading arch. Inspection of lintel or abutment.
Prop the opening; replace the lintel or repair the arch.
Vertical cracks in a heavily loaded pier
Overload or crushing. Load review.
Review the loads with an engineer; relieve or strengthen the pier.
Masonry building being extended upward or converted to flats
A change of consequence class. In England, flats and offices of more than 4 and up to 15 storeys fall in Class 2b, which needs horizontal and vertical ties or a check that the loss of any one wall does not cause disproportionate collapse (Approved Document A, Table 11).
Have the robustness assessed before the change, and add ties or strengthening where the new class requires it.
Accumulated service penetrations. Survey against drawings; engineering review.
Survey against the drawings; get an engineering review, with strengthening around openings where needed.
Warehouse bay without the bracing shown on drawings
Bracing removed for doors or racking. Drawing comparison.
Install temporary bracing now; reinstate or relocate it to an engineer's design.
Building now taller or more public than its original class
Robustness short of the new consequence class. In England offices and flats over 15 storeys fall in Class 3 and need a systematic risk assessment, while those over 4 storeys sit in Class 2b (Approved Document A, Table 11).
Have the lateral system and robustness assessed before the change.
Shear distress from overload, settlement or past earthquake. Engineering assessment.
Get an engineering assessment, then repair or strengthen.
Noticeable sway in wind
Reduced stiffness or design limits. Monitoring; assessment.
Monitor the sway, and have it assessed.
Rust staining or spalling on concrete core walls
Reinforcement corrosion. Carbonation depth and chloride at bar depth: the carbonation front marks a fall in pH from about 12.5 to 8.5, shown by phenolphthalein on a fresh break, and the chloride threshold is generally taken as 0.2 to 0.4 per cent by mass of cement (Institute of Corrosion).
Map the corrosion, repair the concrete, and protect it against further carbonation or chloride.
Cracking and spalling along bars across a facade or soffit
Carbonation-induced corrosion. Carbonation depth at the steel; low cover. The carbonation front marks a fall in pH from about 12.5 to 8.5, shown by phenolphthalein on a fresh break (Institute of Corrosion).
Patch repair, then anti-carbonation coatings or realkalisation.
Localised spalling in a car park, especially near joints and drains
Chloride-induced corrosion. Chloride content at bar depth, against a threshold generally taken as 0.2 to 0.4 per cent by mass of cement (Institute of Corrosion); half-cell potentials.
Repair with cathodic protection, and fix the deck drainage and membranes.
Call an engineer urgently; prop if advised, restrict loads, and add punching shear reinforcement.
Diagonal cracks near beam supports
Shear distress. Engineering assessment.
Get an engineering assessment; strengthen with plates, wraps or added members.
Vertical cracks at mid-span soffits
Flexural cracking from load or loss of capacity. Load review against the design loads and the asset’s market (Thresholds by market); reinforcement check.
Review the loads and check the reinforcement; restrict loads or strengthen.
Beams or slabs visibly sagging, with cracked partitions
Deflection beyond serviceability. Level survey against the design limits and the asset’s market (Thresholds by market).
Survey the deflection, compare it with the design, and have an engineer advise on loads or strengthening.
Creep deflection or overload. Level survey and load review, against the asset’s market (Thresholds by market).
Survey the levels and review the loads; restrict loads or strengthen.
Cracks under heavy storage areas
Overload. Loads against design.
Move heavy items over beams and columns, limit storage, and post load notices.
Lively floor under footfall
Low stiffness and mass. Vibration measurement.
Measure the vibration; add stiffness or mass.
Partitions cracking along their head on an upper floor
Slab deflection after the partitions were built. Deflection since the partitions went in, against span/500, or 20 mm for brittle finishes (The Structural Engineer).
Fit deflection heads to the partitions, and have the slab assessed if movement continues.
Heavy plant, compactus or stock on an existing floor
Loads beyond the design imposed load. Load review against the design loads, the floor’s capacity and the asset’s market (Thresholds by market).
Move heavy items over beams and columns, spread the load, or strengthen the floor, and post load notices.