Every sign of failure the Technical Library records under Electrical Services: 73 signs across 9 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.

Communications, Security & Specialist Systems

Copper retirement and fire interfaces

What you seeLikely cause, and what confirms itNext step
Lift phone silent on testCopper line retired or disconnected. Line type; carrier notice.Take the lift out of service; migrate the phone to 4G/5G or IP with battery backup.
Alarm monitoring signals not receivedDialler on a retired line. Monitoring centre test.Migrate the dialler off copper, with battery backup and monitoring.
Doors stay locked in a fire alarm testBroken fire interface. Interface test.Fix the fire interface, and retest.
Fire alarm, lift phone or monitoring dialler still on a copper serviceService due to be switched off by the carrier. Line audit of every safety-critical connection; carrier notices.Move each service to a supported path, and test it end to end with the monitoring centre.

Obsolescence and cyber exposure

What you seeLikely cause, and what confirms itNext step
Only one company can add a cardProprietary access control. Vendor; licensing.Replace with an open-standard system, with the owner holding licences and databases.
Cameras visible from the internetInsecure configuration. Security assessment.Segregate the network, change credentials and update firmware.

Coverage and cabling

What you seeLikely cause, and what confirms itNext step
Network faults take days to traceUndocumented cabling and patching. Documentation.Document the cabling and patching, and remove redundant cable.
No mobile or radio signal in basements, stairs or plant roomsCoverage gap for occupants and emergency services. Signal survey; fire brigade radio requirements.Fit an in-building coverage system where people work or the brigade needs radio.

Emergency Lighting

Batteries, chargers and central systems

What you seeLikely cause, and what confirms itNext step
Fittings pass a short test but go dark within the durationBattery capacity lost. Full-duration discharge test against the duration for the asset’s market (Thresholds by market).Replace the batteries, all of an age together.
Charge indicators offCharger, supply or indicator failure. Inspection and test.Check the supply, charger and indicator; repair or replace the fitting.

Wiring, coverage and exit signs

What you seeLikely cause, and what confirms itNext step
Fitting works on test switch but stays dark when local lights failWired to the wrong circuit. Circuit check against local lighting.Rewire the fitting to the local lighting circuit.
Batteries flat each morningFed from a switched supply. Circuit check.Rewire it to an unswitched supply.
Dark sections of escape routes after a fit-outCoverage gap. Layout review against current partitions.Add fittings designed to the standard, and verify by measurement.
Corridors or large rooms with no emergency lighting at allCoverage below the market’s rules. Rooms and paths of travel without fittings, against the asset’s market (Thresholds by market).Add fittings to cover the gaps, designed to AS/NZS 2293.1.

Testing and monitoring

What you seeLikely cause, and what confirms itNext step
Monitoring shows no faults for yearsMonitoring not working or not testing. Manual test of a sample.Test the monitoring itself, and make someone responsible for its reports.
Self-test fittings showing fault lights that nobody readsFaults detected but not acted on. Walk-round of indicators; monitoring reports and who receives them.Assign someone to read and act on the reports, and log repairs.

Emergency Power

Starting, wet stacking and fuel

What you seeLikely cause, and what confirms itNext step
Black smoke and oil at exhaust jointsWet stacking. Test logs showing no-load running.Run a load bank test, and exercise the generator under meaningful load.
Generator failed to start in a test or outageBatteries, charger, fuel or heater. Battery test; charger output; fuel filters.Replace the batteries; check the charger, fuel and heater, and fit monitoring.
Filters blocking during runsFuel contamination. Fuel sample.Test, polish and treat the fuel, and remove water.
Generator run each week but never on loadWet stacking and an untested set. Test records against the routine runs the asset’s market expects (Thresholds by market), and a periodic load test to show whether it can carry the building.Run a load bank test, and add load to routine runs.

Transfer switches, UPS and capacity

What you seeLikely cause, and what confirms itNext step
UPS dropped load on mains failureFailed batteries. Battery test.Replace the batteries, with monitoring.
Generator stalls when fire systems startCapacity or load sequencing. Load study.Remove non-essential loads and sequence large motors, or increase capacity.
UPS batteries past their design lifeBattery failure on the next outage. Battery dates; impedance or discharge test.Replace the battery strings, and test under load.

Rooms, exhaust and permits

What you seeLikely cause, and what confirms itNext step
Fumes inside the building during testsExhaust re-entry. Discharge location.Extend the exhaust away from intakes.

Lighting

Lamp obsolescence and LED quality

What you seeLikely cause, and what confirms itNext step
LED fittings failing in clusters on one circuitDriver failure from heat or surges. Driver type, location and circuit history.Replace the drivers, and add surge protection on external circuits.
Fluorescent lamps hard or costly to sourceMercury lamp withdrawal. Supplier advice.Convert to LED with new fittings.
Flicker or colour shift in LED fittingsDriver or product quality. Product data; replacement history.Replace the driver, or the product with a better-quality one.

Light levels, glare and spill

What you seeLikely cause, and what confirms itNext step
Dark stairs or car park zonesFailed or removed fittings, or depreciation. Lux survey against the asset’s market (Thresholds by market).Replace or reinstate fittings, and bring levels to standard.
Offices or workshops dim at desks and benchesLight levels below what the work needs. Lux survey at the task against the asset’s market (Thresholds by market).Replace or add fittings, or relamp to recover the design level.

Columns, fixings and PCBs

What you seeLikely cause, and what confirms itNext step
Rust and section loss at a column base or doorGround-line corrosion. Ultrasonic wall thickness test.Treat it as unsafe; test it, then replace the column or sleeve the base.
Oily residue in old fittingsLeaking PCB capacitor. Sampling; date of manufacture.Remove the PCB capacitor, and dispose of it as hazardous waste.
External lighting spilling into windows or neighbouring propertyLight spill or glare. Complaint locations; aiming and shielding of fittings.Re-aim or shield the fittings, or replace with better-controlled optics.

Lighting Control System

Commissioning, overrides and sensors

What you seeLikely cause, and what confirms itNext step
High night-time electricity useLighting not switching off. Interval meter data; night visit.Reset the schedules and remove the overrides.
Lights switching off on occupantsShort time delays or poor sensor placement. Settings; sensor locations against layout.Lengthen the time delays, and move sensors to suit the layout.
Perimeter lights at full output in daylightDaylight dimming disabled or never set up. Settings; light level measurement.Set up and enable daylight dimming.
One switch or sensor controlling a whole open floorControl zones too large. Area served by each control against the asset’s market (Thresholds by market).Divide the floor into smaller control zones at the next upgrade.
Perimeter lights switched with the core of a large officeDaylight zone not separately controlled. Perimeter circuits against the asset’s market (Thresholds by market).Separate the perimeter circuits and add daylight sensors.
Time switch holding lights on in rooms that are rarely usedOverride where occupancy does not justify it. Occupancy against the conditions the asset’s market sets for time switches (Thresholds by market).Return the room to occupancy control.

Obsolescence, integration and security

What you seeLikely cause, and what confirms itNext step
No-one can change programmingProprietary lock-in or lost tools and passwords. Vendor; documentation.Recover the tools and passwords; specify an open-protocol system at replacement.

Egress and emergency lighting

What you seeLikely cause, and what confirms itNext step
Emergency lighting tests not runningIntegration failure. Test logs.Repair the integration, and run the tests.

Lightning Protection

Continuity, coverage and earthing

What you seeLikely cause, and what confirms itNext step
Conductor ends hanging free near new plantRoof works without reinstatement. Continuity test.Reinstate and refix the conductors, and bond the new plant.
Missing down conductors at low levelTheft. Inspection.Replace them, with less attractive materials or concealed routes.
High earth resistance readingsCorroded electrodes or dry soil. Test against previous readings.Add or replace earth electrodes.
ESE terminal with few down conductorsDesign relying on unrecognised coverage claims. Design review against the standard.Redesign to a recognised standard where the risk requires.

Side flashing, bonding and surge protection

What you seeLikely cause, and what confirms itNext step
Equipment damage after stormsSurge protection absent or exhausted. Device status; coordination.Replace exhausted surge devices, and coordinate them across boards and data entries.
New rooftop plant or solar not bonded to the systemSide-flash risk. Inspection of bonds and separation distances.Bond or separate the new plant, and add surge protection to its supply.

Natural components

What you seeLikely cause, and what confirms itNext step
Steel frame or metal roof counted as part of the system, with no continuity recordNatural component unproven. Continuity test across joints and to earth; design records.Test and record continuity, and bond across any breaks.
Reinforcement relied on as down conductors in a refurbished buildingContinuity possibly broken by alterations. Design records; continuity test from roof to earth.Test each path, and add dedicated down conductors where continuity is lost.

Main Electrical Supply

Connections, insulation and transformers

What you seeLikely cause, and what confirms itNext step
Hot spot at a termination on thermographyLoose or overloaded connection. Temperature rise against adjacent phases; torque check after isolation.Re-terminate and torque the connection, then re-survey to confirm.
Hot neutralHarmonics or unbalanced load. Harmonic measurement.Measure harmonics and balance; filter or rebalance the load.
Rising gases in transformer oilInternal overheating or arcing. Dissolved gas analysis pattern.Retest, and plan oil treatment or transformer replacement.
Partial discharge readings on HV gearInsulation deterioration. Repeat testing; trend.Monitor it, and plan replacement of the switchgear.

Protective devices and arc flash

What you seeLikely cause, and what confirms itNext step
Main breaker trips for faults on final circuitsLoss of discrimination. Protection study.Review the protection settings to restore discrimination.
Breaker fails to trip on testSeized mechanism or failed trip unit. Primary or secondary injection test.Replace or retrofit the breaker; it cannot be relied on.

Capacity and switchroom conditions

What you seeLikely cause, and what confirms itNext step
Hot spot across a whole circuitOverload. Load measurement against rating.Measure the load; redistribute it, or upgrade the circuit.
Network refuses additional loadSupply capacity reached. Maximum demand; supply agreement.Apply to the network early, and manage demand meanwhile.
Switchroom used for storage, or boards blocked by furnitureNo safe working space. Clearances in front of the equipment against the asset’s market (Thresholds by market).Clear the room and mark the working space.

Power Distribution

Insulation, connections and RCDs

What you seeLikely cause, and what confirms itNext step
Crumbling insulation at light fittings and switchesPerished rubber-insulated cable. Inspection; era of the building or rewiring.Rewire the affected circuits.
Warm or scorched outlets and switchesLoose terminal, overload, or aluminium wiring. Thermography; inspection of terminals.Isolate the circuit; repair the terminal, reduce the load, or remediate the aluminium wiring.
RCD trips intermittentlyEarth leakage from appliances or damp, or an ageing RCD. Insulation resistance test; RCD test.Test the circuit and appliances, and find the leakage.
No RCD test records, or test buttons never pressedShock protection unverified. Records and test, against the intervals for the asset’s market (Thresholds by market).Test every RCD, replace those that fail, and set a test schedule.

Busducts, alterations and harmonics

What you seeLikely cause, and what confirms itNext step
Breakers trip under normal loadCircuit overloaded by added equipment. Load measurement.Add circuits or redistribute the load.
Neutral hotter than phasesHarmonics. Harmonic measurement.Upgrade the neutral, or add harmonic filtering.
Unlabelled breakers and added boardsUndocumented alterations. Inspection against drawings.Trace and label the circuits, and update the drawings.

Fire stopping in risers

What you seeLikely cause, and what confirms itNext step
Smoke spread between floors in a fire drill or fireUnsealed riser penetrations. Riser inspection.Fire stop every riser penetration with tested systems.

Solar Photovoltaic (PV) Systems

DC fire risk, batteries and firefighting

What you seeLikely cause, and what confirms itNext step
Burn marks at isolators or connectorsDC arcing. Inspection.Have a qualified person isolate the array; replace with matched, correctly installed parts.
Rooftop DC isolators cracked, discoloured or full of waterIsolator failure and fire risk. Inspection of enclosures and terminals.Replace the isolators with suitable rated units, protected from weather.
Battery installed in a habitable room, escape path or unventilated spaceBattery location against the standard. Location, clearances and enclosure against AS/NZS 5139.Relocate or enclose the battery as the standard requires.

Inverters, modules and soiling

What you seeLikely cause, and what confirms itNext step
No generation; inverter fault lightInverter failure. Error codes; monitoring.Replace the inverter, and add monitoring with alerts.
Output below expectedShading, soiling, degradation or string fault. String measurements; thermal imaging.Compare the strings; clean, trim shading, or repair the weak string.
Hot cells on thermal imageCell cracks or shading. Thermography; electroluminescence.Replace the defective modules.
Monitoring offline or showing no dataFaults going unnoticed. Monitoring connection and history.Restore monitoring, and set alerts for zero or low output.

Roof, frames and compliance

What you seeLikely cause, and what confirms itNext step
Roof leaks under the arrayMounting penetrations. Water test.Reseal the penetrations, or remove and reinstate the array at re-roofing.