Electrical Services: signs, causes and next steps
What does it mean when you see this, and what do you do next?
Moyne Ross
Technical Library
Updated November 14, 2026
Every sign of failure the Technical Library records under Electrical Services: 73 signs across 9 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.
Scope
A sign usually has more than one possible cause. Each row names the likely one and what would confirm it; none is a diagnosis of a particular building, and none is a price.
What you see Likely cause, and what confirms it Next step Lift phone silent on test Copper line retired or disconnected. Line type; carrier notice.Take the lift out of service; migrate the phone to 4G/5G or IP with battery backup. Alarm monitoring signals not received Dialler on a retired line. Monitoring centre test.Migrate the dialler off copper, with battery backup and monitoring. Doors stay locked in a fire alarm test Broken fire interface. Interface test.Fix the fire interface, and retest. Fire alarm, lift phone or monitoring dialler still on a copper service Service due to be switched off by the carrier. Line audit of every safety-critical connection; carrier notices.Move each service to a supported path, and test it end to end with the monitoring centre.
What you see Likely cause, and what confirms it Next step Only one company can add a card Proprietary access control. Vendor; licensing.Replace with an open-standard system, with the owner holding licences and databases. Cameras visible from the internet Insecure configuration. Security assessment.Segregate the network, change credentials and update firmware.
What you see Likely cause, and what confirms it Next step Network faults take days to trace Undocumented cabling and patching. Documentation.Document the cabling and patching, and remove redundant cable. No mobile or radio signal in basements, stairs or plant rooms Coverage gap for occupants and emergency services. Signal survey; fire brigade radio requirements.Fit an in-building coverage system where people work or the brigade needs radio.
What you see Likely cause, and what confirms it Next step Fittings pass a short test but go dark within the duration Battery capacity lost. Full-duration discharge test against the duration for the asset’s market (Thresholds by market ).Replace the batteries, all of an age together. Charge indicators off Charger, supply or indicator failure. Inspection and test.Check the supply, charger and indicator; repair or replace the fitting.
What you see Likely cause, and what confirms it Next step Fitting works on test switch but stays dark when local lights fail Wired to the wrong circuit. Circuit check against local lighting.Rewire the fitting to the local lighting circuit. Batteries flat each morning Fed from a switched supply. Circuit check.Rewire it to an unswitched supply. Dark sections of escape routes after a fit-out Coverage gap. Layout review against current partitions.Add fittings designed to the standard, and verify by measurement. Corridors or large rooms with no emergency lighting at all Coverage below the market’s rules. Rooms and paths of travel without fittings, against the asset’s market (Thresholds by market ).Add fittings to cover the gaps, designed to AS/NZS 2293.1.
What you see Likely cause, and what confirms it Next step Monitoring shows no faults for years Monitoring not working or not testing. Manual test of a sample.Test the monitoring itself, and make someone responsible for its reports. Self-test fittings showing fault lights that nobody reads Faults detected but not acted on. Walk-round of indicators; monitoring reports and who receives them.Assign someone to read and act on the reports, and log repairs.
What you see Likely cause, and what confirms it Next step Black smoke and oil at exhaust joints Wet stacking. Test logs showing no-load running.Run a load bank test, and exercise the generator under meaningful load. Generator failed to start in a test or outage Batteries, charger, fuel or heater. Battery test; charger output; fuel filters.Replace the batteries; check the charger, fuel and heater, and fit monitoring. Filters blocking during runs Fuel contamination. Fuel sample.Test, polish and treat the fuel, and remove water. Generator run each week but never on load Wet stacking and an untested set. Test records against the routine runs the asset’s market expects (Thresholds by market ), and a periodic load test to show whether it can carry the building.Run a load bank test, and add load to routine runs.
What you see Likely cause, and what confirms it Next step UPS dropped load on mains failure Failed batteries. Battery test.Replace the batteries, with monitoring. Generator stalls when fire systems start Capacity or load sequencing. Load study.Remove non-essential loads and sequence large motors, or increase capacity. UPS batteries past their design life Battery failure on the next outage. Battery dates; impedance or discharge test.Replace the battery strings, and test under load.
What you see Likely cause, and what confirms it Next step Fumes inside the building during tests Exhaust re-entry. Discharge location.Extend the exhaust away from intakes.
What you see Likely cause, and what confirms it Next step LED fittings failing in clusters on one circuit Driver failure from heat or surges. Driver type, location and circuit history.Replace the drivers, and add surge protection on external circuits. Fluorescent lamps hard or costly to source Mercury lamp withdrawal. Supplier advice.Convert to LED with new fittings. Flicker or colour shift in LED fittings Driver or product quality. Product data; replacement history.Replace the driver, or the product with a better-quality one.
What you see Likely cause, and what confirms it Next step Dark stairs or car park zones Failed or removed fittings, or depreciation. Lux survey against the asset’s market (Thresholds by market ).Replace or reinstate fittings, and bring levels to standard. Offices or workshops dim at desks and benches Light levels below what the work needs. Lux survey at the task against the asset’s market (Thresholds by market ).Replace or add fittings, or relamp to recover the design level.
What you see Likely cause, and what confirms it Next step Rust and section loss at a column base or door Ground-line corrosion. Ultrasonic wall thickness test.Treat it as unsafe; test it, then replace the column or sleeve the base. Oily residue in old fittings Leaking PCB capacitor. Sampling; date of manufacture.Remove the PCB capacitor, and dispose of it as hazardous waste. External lighting spilling into windows or neighbouring property Light spill or glare. Complaint locations; aiming and shielding of fittings.Re-aim or shield the fittings, or replace with better-controlled optics.
What you see Likely cause, and what confirms it Next step High night-time electricity use Lighting not switching off. Interval meter data; night visit.Reset the schedules and remove the overrides. Lights switching off on occupants Short time delays or poor sensor placement. Settings; sensor locations against layout.Lengthen the time delays, and move sensors to suit the layout. Perimeter lights at full output in daylight Daylight dimming disabled or never set up. Settings; light level measurement.Set up and enable daylight dimming. One switch or sensor controlling a whole open floor Control zones too large. Area served by each control against the asset’s market (Thresholds by market ).Divide the floor into smaller control zones at the next upgrade. Perimeter lights switched with the core of a large office Daylight zone not separately controlled. Perimeter circuits against the asset’s market (Thresholds by market ).Separate the perimeter circuits and add daylight sensors. Time switch holding lights on in rooms that are rarely used Override where occupancy does not justify it. Occupancy against the conditions the asset’s market sets for time switches (Thresholds by market ).Return the room to occupancy control.
What you see Likely cause, and what confirms it Next step No-one can change programming Proprietary lock-in or lost tools and passwords. Vendor; documentation.Recover the tools and passwords; specify an open-protocol system at replacement.
What you see Likely cause, and what confirms it Next step Emergency lighting tests not running Integration failure. Test logs.Repair the integration, and run the tests.
What you see Likely cause, and what confirms it Next step Conductor ends hanging free near new plant Roof works without reinstatement. Continuity test.Reinstate and refix the conductors, and bond the new plant. Missing down conductors at low level Theft. Inspection.Replace them, with less attractive materials or concealed routes. High earth resistance readings Corroded electrodes or dry soil. Test against previous readings.Add or replace earth electrodes. ESE terminal with few down conductors Design relying on unrecognised coverage claims. Design review against the standard.Redesign to a recognised standard where the risk requires.
What you see Likely cause, and what confirms it Next step Equipment damage after storms Surge protection absent or exhausted. Device status; coordination.Replace exhausted surge devices, and coordinate them across boards and data entries. New rooftop plant or solar not bonded to the system Side-flash risk. Inspection of bonds and separation distances.Bond or separate the new plant, and add surge protection to its supply.
What you see Likely cause, and what confirms it Next step Steel frame or metal roof counted as part of the system, with no continuity record Natural component unproven. Continuity test across joints and to earth; design records.Test and record continuity, and bond across any breaks. Reinforcement relied on as down conductors in a refurbished building Continuity possibly broken by alterations. Design records; continuity test from roof to earth.Test each path, and add dedicated down conductors where continuity is lost.
What you see Likely cause, and what confirms it Next step Hot spot at a termination on thermography Loose or overloaded connection. Temperature rise against adjacent phases; torque check after isolation.Re-terminate and torque the connection, then re-survey to confirm. Hot neutral Harmonics or unbalanced load. Harmonic measurement.Measure harmonics and balance; filter or rebalance the load. Rising gases in transformer oil Internal overheating or arcing. Dissolved gas analysis pattern.Retest, and plan oil treatment or transformer replacement. Partial discharge readings on HV gear Insulation deterioration. Repeat testing; trend.Monitor it, and plan replacement of the switchgear.
What you see Likely cause, and what confirms it Next step Main breaker trips for faults on final circuits Loss of discrimination. Protection study.Review the protection settings to restore discrimination. Breaker fails to trip on test Seized mechanism or failed trip unit. Primary or secondary injection test.Replace or retrofit the breaker; it cannot be relied on.
What you see Likely cause, and what confirms it Next step Hot spot across a whole circuit Overload. Load measurement against rating.Measure the load; redistribute it, or upgrade the circuit. Network refuses additional load Supply capacity reached. Maximum demand; supply agreement.Apply to the network early, and manage demand meanwhile. Switchroom used for storage, or boards blocked by furniture No safe working space. Clearances in front of the equipment against the asset’s market (Thresholds by market ).Clear the room and mark the working space.
What you see Likely cause, and what confirms it Next step Crumbling insulation at light fittings and switches Perished rubber-insulated cable. Inspection; era of the building or rewiring.Rewire the affected circuits. Warm or scorched outlets and switches Loose terminal, overload, or aluminium wiring. Thermography; inspection of terminals.Isolate the circuit; repair the terminal, reduce the load, or remediate the aluminium wiring. RCD trips intermittently Earth leakage from appliances or damp, or an ageing RCD. Insulation resistance test; RCD test.Test the circuit and appliances, and find the leakage. No RCD test records, or test buttons never pressed Shock protection unverified. Records and test, against the intervals for the asset’s market (Thresholds by market ).Test every RCD, replace those that fail, and set a test schedule.
What you see Likely cause, and what confirms it Next step Breakers trip under normal load Circuit overloaded by added equipment. Load measurement.Add circuits or redistribute the load. Neutral hotter than phases Harmonics. Harmonic measurement.Upgrade the neutral, or add harmonic filtering. Unlabelled breakers and added boards Undocumented alterations. Inspection against drawings.Trace and label the circuits, and update the drawings.
What you see Likely cause, and what confirms it Next step Smoke spread between floors in a fire drill or fire Unsealed riser penetrations. Riser inspection.Fire stop every riser penetration with tested systems.
What you see Likely cause, and what confirms it Next step Burn marks at isolators or connectors DC arcing. Inspection.Have a qualified person isolate the array; replace with matched, correctly installed parts. Rooftop DC isolators cracked, discoloured or full of water Isolator failure and fire risk. Inspection of enclosures and terminals.Replace the isolators with suitable rated units, protected from weather. Battery installed in a habitable room, escape path or unventilated space Battery location against the standard. Location, clearances and enclosure against AS/NZS 5139.Relocate or enclose the battery as the standard requires.
What you see Likely cause, and what confirms it Next step No generation; inverter fault light Inverter failure. Error codes; monitoring.Replace the inverter, and add monitoring with alerts. Output below expected Shading, soiling, degradation or string fault. String measurements; thermal imaging.Compare the strings; clean, trim shading, or repair the weak string. Hot cells on thermal image Cell cracks or shading. Thermography; electroluminescence.Replace the defective modules. Monitoring offline or showing no data Faults going unnoticed. Monitoring connection and history.Restore monitoring, and set alerts for zero or low output.
What you see Likely cause, and what confirms it Next step Roof leaks under the array Mounting penetrations. Water test.Reseal the penetrations, or remove and reinstate the array at re-roofing.