Emergency lighting fails at the battery: fittings that light on a quick test go dark before the rated duration. Fit-outs cause the other failures: fittings rewired to the wrong circuit so they stay dark when local lights fail, new corridors without coverage, exit signs pointing to doors that no longer lead out. Self-test systems help only if someone reads their reports. It is a life-safety system, and its test records establish its position.
What it is and how it is built
Emergency lighting lights the way out when normal lighting fails. It has three jobs: escape route lighting along corridors, stairs and to final exits; open-area (anti-panic) lighting in large rooms so people can reach a route; and high-risk task lighting where a process must be shut down safely. Exit signs, lit at all times or photoluminescent, show the direction to exits. It is a life-safety system with prescribed design, testing and record-keeping in all three jurisdictions.
| Type | Where it is found | Character |
|---|---|---|
| Self-contained luminaires and exit signs | Most buildings | Battery, charger and lamp in each fitting; every fitting must be tested |
| Central battery systems | Larger buildings, hospitals, theatres, some towers | Batteries and inverter in one room; sub-circuit monitoring; wiring must survive fire |
| Monitored or addressable systems | Larger buildings from the 2000s | Fittings test themselves on schedule and report faults to a panel or software |
| Maintained fittings | Exit signs; theatres, cinemas, public spaces | Lit at all times, and stay lit in a failure |
| Non-maintained fittings | Most escape lighting | Off normally, on when the local supply fails |
| Photoluminescent signs and markings | Stairs and exit signs where permitted | Glow after charging by normal light; no wiring |
Fittings must be placed at every exit door, every change of direction and intersection, on every stair flight, near fire alarm call points and fire-fighting equipment, and outside final exits, with enough light along the route. Fittings must also sense the failure of the local lighting circuit they serve: a fitting wired to a different circuit will not come on when the lights around it fail.
Era tells you the likely state. Fluorescent self-contained fittings with nickel-cadmium batteries dominate installations of the 1980s to 2000s and are at end of life; LED fittings with nickel-metal hydride or lithium iron phosphate batteries are the current generation, often with self-test.
Service life and what shortens it
| Component | Typical life | What moves it |
|---|---|---|
| Nickel-cadmium and nickel-metal hydride batteries | 4 to 6 years | Heat in ceiling spaces; charging |
| Lithium iron phosphate batteries | 8 to 10 years | Heat; battery management |
| LED emergency luminaires and exit signs | 15 to 20 years | Driver and charger; heat |
| Fluorescent emergency fittings | 10 to 15 years | Lamp availability ending |
| Central battery systems | 15 to 20 years; batteries 5 to 10 | Battery room temperature |
| Monitoring panels and software | 10 to 15 years | Vendor support |
| Photoluminescent signs | 20 to 25 years | Fading; charging light levels |
What shortens life:
- Heat: fittings in hot ceiling spaces, near plant or in roof spaces lose battery life fastest.
- Missed testing: batteries never discharged lose capacity unnoticed.
- Fit-outs that disconnect fittings, rewire them to the wrong circuits, or hide them behind new partitions.
- Damage in car parks, plant rooms and stairs.
How it fails
Battery capacity loss
Batteries are the commonest failure. They lose capacity with age and heat until the fitting cannot run for its rated duration: typically 90 minutes in Australia and the United States, and often three hours in Britain where premises may be re-occupied straight after a failure. A fitting that lights on a quick switch test can fail a full-duration test, which is why the duration test is required.
Charger and lamp failure
Chargers fail and leave batteries flat; fluorescent tubes and early LED modules fail; indicators fail so faults are not seen.
Wiring faults from alterations
Non-maintained fittings must be fed from the same unswitched circuit as the normal lighting in that area so that they detect its failure. Fit-outs often rewire them to another circuit or to a switched supply; the fitting then stays dark when the local lights fail, or drains its battery every time the lights are switched off.
Coverage gaps
New partitions create corridors, dead ends and changes of direction the original layout did not cover; exit signs end up pointing to doors that no longer lead out, or are hidden behind signage and joinery.
Central battery failures
Central battery systems fail as one: a battery, inverter or changeover fault darkens a whole area. Sub-circuit monitoring must detect local lighting failures, and wiring to fittings must be fire-resisting so it survives long enough to be useful.
Silent monitoring failures
Self-test and addressable systems only help if someone reads their reports. Communication faults, unsupported software and disabled schedules leave a building believing it is tested when it is not.
Photoluminescent limitations
Photoluminescent signs need enough normal light to charge; in dim stairs and plant areas they may not glow brightly enough when needed.
What to look for
On site
- Charge indicators off on fittings; exit signs unlit or dim.
- Fittings damaged, missing, painted over or hidden by fit-out.
- Escape routes, stairs, changes of direction and final exits without fittings.
- Exit signs pointing the wrong way, or to doors now locked or removed.
- Test labels and dates on fittings; key switches for testing.
- Central battery room: temperature, battery condition, alarms.
In the records
- Test logbook with each fitting, its result and date.
- Annual fire safety statement or essential safety measures report.
- Monitoring system reports and fault lists.
- Battery replacement records.
- Emergency lighting layout drawings against the current fit-out.
Telling causes apart
| What you see | Most likely cause | What confirms it |
|---|---|---|
| Fittings pass a short test but go dark within the duration | Battery capacity lost | Full-duration discharge test |
| Charge indicators off | Charger, supply or indicator failure | Inspection and test |
| Fitting works on test switch but stays dark when local lights fail | Wired to the wrong circuit | Circuit check against local lighting |
| Batteries flat each morning | Fed from a switched supply | Circuit check |
| Dark sections of escape routes after a fit-out | Coverage gap | Layout review against current partitions |
| Monitoring shows no faults for years | Monitoring not working or not testing | Manual test of a sample |
How serious it is
Findings are graded by what they demand: safety (can hurt someone now), failure (failed and damaging the building), condition (distress present and progressing), lifecycle (renewal due on age and exposure), deadline (a regulator or ordinance sets the date), check (investigate before sizing works) and nil (cosmetic or stable).
| Finding | Situation | What it means for timing |
|---|---|---|
| Escape routes, stairs or exits without working emergency lighting or exit signs; fittings that will not operate on local failure | safety | Rectify now |
| Periodic testing due | deadline | Six-monthly duration test in Australia; monthly functional and annual duration tests in Britain and the United States |
| Batteries failing duration tests across the installation | condition | Replace batteries or fittings in the near term |
| Fluorescent fittings and old batteries at end of life | lifecycle | Replace with LED, ideally with self-test |
| No test records; layout not checked after fit-outs | check | Test every fitting and review coverage |
| Isolated faults found and fixed at testing | nil | Routine maintenance |
Investigation and testing
An electrical contractor licensed for fire safety systems carries out testing; a lighting designer or fire engineer reviews coverage where layouts have changed.
- Full-duration test of every fitting by simulating failure of the normal supply, recording each result.
- Circuit check that each non-maintained fitting is fed from the local lighting circuit it protects.
- Coverage survey against the current layout: every exit, change of direction, stair flight, call point and final exit; light levels along routes where doubtful.
- Exit sign review: visibility, direction, legibility, correct pictograms.
- Central battery inspection: batteries, charger, inverter, changeover, sub-circuit monitoring, room ventilation and temperature, fire-resisting wiring.
- Monitoring check: manual test of a sample against what the system reports.
- Records review: logbooks, annual statements, battery dates.
The report should list every fitting with its result, coverage gaps, wiring faults, and the works needed to certify the system.
Remedies and what they involve
- Battery replacement programme: replace all batteries of an age together rather than fitting by fitting.
- Fitting replacement with LED fittings and long-life batteries, which cuts energy and maintenance.
- Self-test or addressable monitoring, so testing is automatic and faults are reported, with someone responsible for reading the reports.
- Rewiring of fittings fed from the wrong circuits.
- Coverage additions after fit-outs, designed to the standard.
- Exit sign updates to current pictograms and positions.
- Central battery refurbishment: batteries, chargers, monitoring, or replacement with distributed fittings.
- Records: a logbook or digital record for every fitting, with test dates, results and actions.
- Escape route lighting design verified by measurement after major fit-outs.
Cost shape
Testing is a recurring contract at the prescribed interval. Battery replacement is priced per fitting and recurs on battery life. Fitting replacement is priced per fitting, with ceiling access in occupied areas. Monitoring systems are priced per fitting plus a panel. Coverage additions are per fitting with design. Central battery refurbishment is a lump sum.
Testing and safety rectification are code compliance; battery replacement is repairs and maintenance on a cycle; fitting replacement is lifecycle.
Standards and jurisdiction
- Australia. The National Construction Code requires emergency lighting and exit signs (Part E4); AS/NZS 2293.1 covers design, AS/NZS 2293.3 luminaires and exit signs, and AS/NZS 2293.2 inspection and maintenance, including a six-monthly discharge test for at least the rated duration. Emergency lighting is an essential safety measure under state building regulations, certified annually.
- United Kingdom. BS 5266-1 sets the code of practice, with BS EN 1838 for lighting levels and BS EN 50172 for systems: monthly functional tests and an annual full-duration test, with a logbook. The Regulatory Reform (Fire Safety) Order 2005 places the duty on the responsible person.
- United States. NFPA 101 Section 7.9 requires emergency lighting with monthly 30-second tests and an annual 90-minute test, or approved self-testing equipment; Section 7.10 covers exit marking; UL 924 lists equipment; the International Building and Fire Codes adopt equivalent requirements.
What to ask the owner or agent for
- Emergency lighting test logbook with every fitting and result.
- Annual fire safety statement or essential safety measures report.
- Monitoring system reports and fault history.
- Battery replacement records and dates.
- Emergency lighting and exit sign layout drawings.
- Fit-out records since the last layout review.
- Monitoring system access and reports.
Sources
- National Construction Code, Australian Building Codes Board. Accessed 7 November 2026.
- Standards catalogue, Standards Australia. Accessed 7 November 2026.
- British Standards, BSI. Accessed 7 November 2026.
- NFPA 101 Life Safety Code, National Fire Protection Association. Accessed 7 November 2026.
- Fire safety in the workplace, UK Government. Accessed 7 November 2026.
Related references: the Capital Register and the MR Index.