Every sign of failure the Technical Library records under Internal Areas: 286 signs across 27 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.
Scope
A sign usually has more than one possible cause. Each row names the likely one and what would confirm it; none is a diagnosis of a particular building, and none is a price.
What you see Likely cause, and what confirms it Next step Ceiling stain below appears after showers and dries between Membrane, screen or shower floor failure. Flood test of the shower floor; spray test of the screen.Flood test the floor and spray test the screen separately; strip and re-waterproof if the membrane has failed. Swollen skirting or door frame outside the bathroom Water escaping at the threshold or waterstop. Moisture readings; flood test.Fit or reseal the waterstop at the threshold, and replace the swollen joinery once it has dried. Drummy tiles around the waste Water under tiles from membrane or waste flange failure. Lift a tile; inspect the flange.Lift a tile; replace the waste flange and repair the membrane, or strip and re-waterproof. Water on the floor outside a hobless shower after use Inadequate falls, or no waterstop at the entry. Water crosses the line of the screen; a level shows the floor falling away from the waste.Re-form the falls, and fit a waterstop or a linear drain across the entry. Tiles cracked in a straight line across a timber-framed floor Floor movement cracking the tiles and the membrane beneath. The crack follows a joist or sheet joint, and the floor gives underfoot.Stiffen the floor first; a new membrane on a floor that still moves fails again.
What you see Likely cause, and what confirms it Next step Stain below that is wet all the time Pressurised pipe or fitting leak. Pressure test; water meter with outlets closed.Pressure test, find the leaking pipe or fitting, and repair it. Stain below the WC Pan seal or cistern connection leak. Dye test in the cistern and pan.Replace the pan seal or cistern connection. Damp in the wall beside the shower mixer, whether or not the shower is used A leaking mixer body or connection. Moisture is constant and highest around the mixer; a pressure test confirms it.Open the wall or tiles, and repair or replace the mixer.
What you see Likely cause, and what confirms it Next step Mould on the ceiling Inadequate exhaust or fan not ducted outside. Fan airflow; duct route (Thresholds by market ).Fit a ducted fan discharging outside, with a run-on timer or humidity control. Mould on the roof timbers above the bathroom Exhaust discharging into the roof space. The duct ends in the roof space, not at an outlet outside.Duct the fan to outside, and treat or replace the mouldy materials.
What you see Likely cause, and what confirms it Next step Very hot water at the basin or shower Scald risk. Outlet temperature measured against the limits for the asset’s market (Thresholds by market ).Fit or repair the tempering or thermostatic mixing valve and retest. Lukewarm water at a little-used shower, or a long wait for hot water Legionella risk from low temperatures or stagnation. Temperature at the outlet over time against the limits for the asset’s market (Thresholds by market ).Flush little-used outlets weekly, remove dead legs, and restore temperatures. Slips on a wet bathroom floor Floor finish unsuitable when wet. Wet slip resistance test against the class for the use.Treat the surface or replace it with a suitably slip-resistant finish.
What you see Likely cause, and what confirms it Next step Suppression nozzles over empty bench Appliances moved since design. Layout against design.Redesign the suppression to the current layout, and interlock it to gas and power. Thick grease at duct access panels, or no access panels at all Cleaning too infrequent for the cooking, or parts of the duct unreachable. Grease depth measured at access points; certificates cover the hood but not the duct run.Clean the full duct at a frequency set by the cooking, and add access panels. Gas still flowing in a suppression or interlock test An interlock bypassed or failed. Gas does not shut off on discharge, or when the exhaust stops.Restore and test the interlock before cooking continues.
What you see Likely cause, and what confirms it Next step Smoke escaping canopies at busy times Exhaust capacity or make-up air shortfall. Airflow measurements.Measure capture and make-up air; rebalance, or upgrade the hood and fan for the cooking now done. Doors slamming, flues backdraughting Negative pressure. Pressure and CO measurement (Thresholds by market ).Stop using the affected gas appliances until make-up air is restored, and measure carbon monoxide.
What you see Likely cause, and what confirms it Next step Stains below the kitchen Floor membrane or waste failure. Flood test.Flood test; renew the membrane and wastes, with falls to drains. Food safety non-compliances for linings Damaged or unsuitable finishes. Inspection report.Replace with impervious, cleanable linings, and seal the penetrations. Water ponding away from the floor wastes A floor without falls to drains. A level shows the ponding; tiles crack where water sits.Re-form the floor to fall to drains, with a slip-resistant finish. Hot water at hand basins slow to arrive or barely warm Hot water not reaching temperature. Temperatures at the outlets against the limits for the asset’s market (Thresholds by market ).Rebalance or repair the hot water circulation, and fit tempering at hand basins where required.
What you see Likely cause, and what confirms it Next step No working release on the inside of a cool room door An internal release missing, broken or iced up. Test the release from inside, with the door held.Repair or fit the release, with an alarm and lighting, before the room is used again.
What you see Likely cause, and what confirms it Next step Floor hard to lease despite good condition Market grade drift or functional limits. Grade assessment; leasing feedback.Assess the grade against the market, and plan base-building refurbishment at lease expiry. Tenants asking for amenities the floor cannot offer Amenities and end-of-trip below current expectations. Ratios and facilities compared with competing buildings.Upgrade amenities and end-of-trip at the next base-building refurbishment.
What you see Likely cause, and what confirms it Next step Complaints at the perimeter in afternoons, blinds always down Façade heat gain and glare. Orientation; glazing type; perimeter temperatures.Add solar control, with blinds, films or glazing upgrades, and check the perimeter zoning. Complaints in meeting rooms and enclosed offices Zoning that no longer matches partitions. Terminal unit zoning against layout.Rezone and rebalance the air conditioning to the current layout. Stuffiness and complaints after lunch Low outside air or high density. CO₂ readings; outside air measurement (Thresholds by market ).Measure outside air and carbon dioxide; upgrade the outside air where it falls short. Dark patches between desks, or glare on screens Lighting laid out for an earlier layout, or old fittings. Light levels at desks measured against the current layout and the limits for the asset’s market (Thresholds by market ).Upgrade to LED designed for even desk light and low glare, with controls. Staff complaining of cold first thing in winter Start-up too late or heating short. Temperature logging from start of occupancy against the limits for the asset’s market (Thresholds by market ).Bring start times forward or rebalance heating.
What you see Likely cause, and what confirms it Next step Ceiling void crowded with abandoned cabling and capped ducts Fit-out residue from previous tenancies. Ceiling inspection.Remove abandoned cabling and services, and replace damaged tiles. Rooms without sprinkler or detector coverage Fit-out compliance drift. Survey against the layout.Add or relocate sprinklers, detectors, emergency lights and exit signs to suit the layout. A partition or joinery unit cutting across a sprinkler head's spray Fit-out added after the sprinkler layout. The clearance between the head and the obstruction, measured.Relocate the head, or add one to cover the new room.
What you see Likely cause, and what confirms it Next step Stained tiles in a line Leak from services or the floor above. Trace the line to a pipe, riser or wet area.Trace the line to its source and repair it, then replace the tiles. Ceiling grid bent near risers and service access points Services workers leaning on the grid. Damage concentrated around access points.Straighten or replace the grid, and provide proper access to the services above.
What you see Likely cause, and what confirms it Next step Corridors cluttered on residential floors Storage shortage or poor management. Building rules; storage provision.Provide storage, clear the corridor, and enforce the rules. A corridor that now ends at a new partition A dead end created by a fit-out. Travel distance to an exit measured against the fire strategy (Thresholds by market ).Have the egress reviewed, and remove or rearrange the partition.
What you see Likely cause, and what confirms it Next step Doors wedged open on every floor Doors used for convenience; no hold-open devices. Inspection; use patterns.Fit hold-open devices linked to the alarm where doors need to stand open, and stop the wedging. Smoke spread in a minor fire or alarm test Failed doors, seals or vents. Door survey; smoke vent test.Survey every door, repair closers and seals, and test the smoke vents. Flat entrance doors of mixed designs Owner-replaced doors that may not be fire-rated. No evidence of a rating, with gaps and missing closers. Gaps are measured against the door’s evidence and the limits for the asset’s market (Thresholds by market ).Survey them, and replace non-compliant doors with self-closing, fire-rated doorsets. A smoke vent still shut during an alarm test A failed actuator, or a blocked vent. The vent does not open when the alarm is triggered (Thresholds by market ).Repair the actuator, clear the vent, and retest.
What you see Likely cause, and what confirms it Next step Walls damaged at a consistent height Trolleys or bins. Wall protection review.Fit corner guards, rails or impact-resistant finishes at that height. Odours along corridors Inadequate ventilation or unbalanced pressure. Airflow check.Rebalance the corridor ventilation, and renew the door seals. Exit signs hidden, or pointing the wrong way Signs not updated after a layout change. From some points no sign leads to an exit.Renew and reposition the signs to suit the layout.
What you see Likely cause, and what confirms it Next step Flat doors without closers Resident alterations. Door survey; by-law enforcement.Survey every door, enforce the by-laws, and replace non-compliant doors, settling the cost allocation first. Storage throughout corridors Insufficient storage and weak enforcement. Storage provision; enforcement records.Provide storage and charging rooms, and enforce the rules. E-bikes or scooters charging in a corridor, stair or bike room No designated charging room. Chargers plugged into common area outlets, with batteries left overnight.Stop charging in escape routes, and provide a charging room with detection. Flat entrance doors with wide or uneven gaps at the edges Fire doors no longer sealing. Gap measurement against the door’s evidence and the asset’s market (Thresholds by market ); check records against the inspection intervals the market sets.Adjust or replace the doors, renew seals, and set up the checks the market requires.
What you see Likely cause, and what confirms it Next step Intercom stopped working Network shutdown or obsolete equipment. Network type; vendor.Upgrade to a supported system on current networks, with open fob formats. An entry door that does not close and latch behind people A failed closer or latch, or a door propped for deliveries. The door stays ajar when released.Restore the closer and latch, and add parcel lockers to reduce propping.
What you see Likely cause, and what confirms it Next step Common areas dated despite sound fabric Deferred refurbishment. Capital works plan; fund balance.Fund and schedule the refurbishment through the capital works plan. A capital works fund far short of the works the plan shows due A plan not based on condition, or levies set too low. Plan items compared with a condition survey and the fund balance.Update the plan from a condition survey, and set levies to fund it. Defects in a newer building with the warranty period running Construction defects not yet pursued. Defect reports, and the date the warranty period ends.Commission an expert report, and pursue the claim within the period.
What you see Likely cause, and what confirms it Next step Light visible through slab penetrations Fire stopping missing. Inspection from both sides.Reinstate the fire stopping with a tested system, and record it with photographs. A riser door without a closer or a rating label A fire door that no longer protects the riser. The door stays open when released, or has been replaced. Gaps are measured against the door’s evidence and the limits for the asset’s market (Thresholds by market ).Repair it, or replace it as a self-closing fire door.
What you see Likely cause, and what confirms it Next step Trays bowed or collapsed Overloading with cables. Inspection.Remove abandoned cables, and add trays and supports. New tenant cannot connect Space or capacity exhausted. Capacity survey.Survey capacity; remove abandoned cables first, then add risers, busducts or backbone if still needed. Carrier equipment no one has a record of Equipment installed without approval or records. No agreement or drawing matches the equipment.Identify the owner, regularise or remove it, and record it in the riser register.
What you see Likely cause, and what confirms it Next step Equipment faults on hot days Riser overheating. Temperature logging.Log temperatures, and add ventilation or cooling. Corrosion on boards Water ingress. Leak tracing.Trace the leak; add drip trays and upstands, or relocate the pipes.
What you see Likely cause, and what confirms it Next step A riser cupboard used for cleaning gear or storage Unmanaged access. Mops, chemicals or boxes stand against the boards.Clear it, lock it, and manage the keys. Breakers labelled for tenants who left years ago Labels not updated after fit-outs. Circuits traced do not match the schedule.Trace and relabel every circuit, and keep a riser register updated after every job. Cables, trays or stored items in the space in front of a board Working space lost. The clear space in front of each board measured against the asset’s market (Thresholds by market ).Clear the working space, reroute trays that intrude, and keep it marked and free of storage.
What you see Likely cause, and what confirms it Next step Soot above a gas heater Incomplete combustion or spillage. Service; CO test.Stop using it; have a licensed gas fitter service it and test for carbon monoxide. Headaches when the heater runs Carbon monoxide. CO test (Thresholds by market ).Stop using the heater, ventilate the room, and have the heater tested before it runs again. An open fire or open-flued heater near a strong exhaust fan Negative pressure pulling combustion products down the flue. A spillage test with the fans running together.Interlock or balance the fans, or replace with a room-sealed appliance. An unflued gas heater in a bedroom Combustion products and moisture released into a sleeping room. The heater's type and location.Remove it from the bedroom, and give the owners guidance on unflued heaters.
What you see Likely cause, and what confirms it Next step Scorched timber near a wood heater Inadequate clearance. Measurement.Correct the clearance with a heat shield, a larger hearth, or relocation. A new timber mantel or shelving close to the firebox A renovation without a clearance check. The distance measured against the appliance's clearances.Remove or shield the combustible material. Hearth small, cracked or level with a timber floor Hearth too small for the opening. Hearth extent measured against the asset’s market (Thresholds by market ).Extend or replace the hearth in non-combustible material.
What you see Likely cause, and what confirms it Next step Smoke into the room Poor draw or blocked flue. Flue inspection.Inspect and sweep the flue, fit a bird guard, and check for negative pressure. A gas log fire in an old masonry fireplace with no visible liner A conversion relying on an unsuited flue. A flue inspection for cracks, the liner and the termination.Fit a correct liner and termination, or decommission the fire. Chimney ending below the ridge or a nearby taller part of the building Poor draught and smoke re-entry. Terminal height measured against the building around it and the asset’s market (Thresholds by market ).Extend the flue or fit a suitable terminal.
What you see Likely cause, and what confirms it Next step Vinyl or resin lifting across a slab Moisture vapour from the slab. In-situ relative humidity test.Test the slab's relative humidity; dry it, or lay a surface membrane before new flooring. Timber cupping Moisture from below or a leak. Moisture readings.Find and stop the moisture or leak, then let the boards settle before refinishing or replacing them. Cracks in vinyl or tiles running in a straight line A crack or joint in the substrate reflecting through. The line matches a slab joint or screed crack.Repair the substrate before replacing the finish. Dark staining or adhesive bleeding at vinyl seams Moisture attacking the adhesive. Discoloured seams, with high in-situ humidity readings.Test the slab, and lay a surface membrane before relaying.
What you see Likely cause, and what confirms it Next step Tiles ridging along a line No movement joints. Joint inspection.Cut movement joints, and relay the lifted tiles.
What you see Likely cause, and what confirms it Next step Slips on entry tiles Low wet slip resistance. Slip test.Apply a slip treatment or replace the finish, and add entry matting. Small square vinyl tiles in an older building Possible asbestos in the tiles or adhesive. The asbestos register, and testing before any work.Test first; have a licensed contractor remove them, or encapsulate them under new flooring. Lips at thresholds, transitions or lifted boards Trip hazard. Level change measured against the limits for the asset’s market (Thresholds by market ).Fit a transition strip or ramp, or relay the floor.
What you see Likely cause, and what confirms it Next step Noise complaints after a renovation Hard floor without acoustic underlay. Floor construction; acoustic test (Thresholds by market ).Require a tested acoustic underlay under hard floors, as the by-laws allow. Coatings stripped, or stone polished slippery, after cleaning The wrong cleaning chemicals. The damage follows a change of products or contractor.Change the cleaning specification, and restore the finish.
What you see Likely cause, and what confirms it Next step Lifts did not home in a real alarm Interface broken after lift or fire panel change. Integrated test.Repair the interface, then run a full integrated test of every connected function. Doors stayed locked in a drill Access control interface failure. Interface test.Repair the access control interface so the doors release on alarm, and re-test. Bypass switches on, or fire panel outputs to air handlers disabled Interfaces bypassed during maintenance and never restored. The fire panel log shows disabled outputs, or bypass keys left on.Restore the outputs, and re-test the functions they drive. Contractors each saying an interface belongs to someone else No one owns the links between systems. Maintenance contracts that each stop at their own system.Appoint a single point of responsibility for the interfaces and their testing. Stair doors hard to open, or alarms faint, after a change to another system One system’s change upsetting another. Stair door forces and alarm sound levels measured after any change to air handling, doors or fit-out, against the asset’s market (Thresholds by market ).Retest the affected interfaces together, and record the result in the cause-and-effect matrix.
What you see Likely cause, and what confirms it Next step BMS shows plant offline Gateway or protocol failure. Network diagnostics.Diagnose the gateway and protocol; plan migration to open protocols if support has ended. No one can say what the building does in a fire Matrix lost or out of date. Records review.Rebuild the cause-and-effect matrix from the fire strategy and the current systems, then test against it. A gateway from a vendor that no longer supports it Integration locked to an unsupported platform. The vendor's support status and the protocol used.Plan replacement with open protocols, so systems can be changed independently.
What you see Likely cause, and what confirms it Next step Unknown devices on the building network Unmanaged network. Network audit.Audit the network, segment building systems, and control remote access. Building controllers reachable from the internet with default passwords An exposed building network. A scan of the building network, and its remote access arrangements.Change default passwords, patch, segment the network and control remote access.
What you see Likely cause, and what confirms it Next step Exit door locked when the alarm sounds Electronic lock not released. Interface test.Repair the interface, and make the lock fail safe on alarm and on power loss. A kick-down stop, hook or wedge on a fire door A fire door held open by its users. The door stays open when released.Remove it, and fit a hold-open device that releases on alarm where the door must stay open. Decorative or unlabelled hardware on a fire door Hardware replaced by a tenant or resident. Hinges, closer or lock without the certification the door needs.Replace it with certified hardware, and set hardware standards for occupants. Master keys that cannot be accounted for Unmanaged keying. Key records show losses, or there are none.Renew the keying system with key control.
What you see Likely cause, and what confirms it Next step Doors not closing fully Closer adjustment or failure, or binding. Test from fully open.Adjust or replace the closer, and free any binding, so the door closes and latches from fully open. Door rubs at the head on the lock side Hinge wear or frame distortion. Inspection.Repair or replace the hinges, and correct the frame. Noise through meeting room doors Missing or damaged seals. Inspection.Replace the seals, and stop them being painted over. Fire doors with uneven or wide gaps at the edges Leaf dropped, warped or badly hung. Gap measurement against the door’s evidence and the limits for the asset’s market (Thresholds by market ).Adjust or rehang the leaf, renew the seals, and replace doors that cannot meet the limits.
What you see Likely cause, and what confirms it Next step Door hard to open Closer set too strong or stack effect. Opening force measurement against the limits for the asset’s market (Thresholds by market ).Reduce the closer force or treat the stack effect; fit an automatic operator where needed. Glazed doors with no markings Missing manifestation. Clear glass with nothing at eye level.Add manifestation so the glass can be seen.
What you see Likely cause, and what confirms it Next step Falls on one flight Uneven risers, worn nosings or poor light. Riser and going measurement against the limits for the asset’s market (Thresholds by market ), and nosing condition.Measure the risers; replace worn nosings with slip-resistant, contrasting nosings, and improve the lighting. Water on treads Roof or services leak into the stair. Leak tracing.Trace and repair the leak, and keep the treads dry. A handrail on one side only, or stopping at landings Handrails short of what the stair needs. Gaps in the rail through landings, or one side bare. Height, extent and continuity checked against the asset’s market (Thresholds by market ).Fit handrails on both sides where required, continuous through landings. A low balustrade, or open risers on a stair Barrier or treads that will not stop a fall. Barrier height, and the openings between treads and balusters, checked against the asset’s market (Thresholds by market ).Raise or extend the barrier, and close the open risers.
What you see Likely cause, and what confirms it Next step Doors propped on several floors Stair used for circulation between floors. Use patterns.Fit hold-open devices linked to the alarm where doors must stand open, and repair the closers and latches. People unable to leave the stair on a floor Locked re-entry without release. Security interface test.Bring the locking into line with release-on-alarm and re-entry rules, and sign it. Stair doors that do not latch, or show daylight at the edges Fire doors no longer sealing the stair. Gap measurement against the door’s test evidence and the limits for the asset’s market (Thresholds by market ).Adjust the hinges and closer, renew the seals, and replace doors that cannot meet the limits.
What you see Likely cause, and what confirms it Next step Smoke in the stair during a drill Doors propped or pressurisation failed. Door survey; smoke test.Survey and repair the doors, and test the pressurisation. Ordinary glass or an unrated access panel in the stair enclosure Separation lost to a later change. No rating marks on the glass or panel.Replace them with rated glazing or panels, and fire stop the penetrations. Cigarette butts and chairs on a landing The stair being used as a break area. Litter and furniture on one landing, with the door near it propped.Clear it, enforce the rules, and give people somewhere else to go.
What you see Likely cause, and what confirms it Next step A final exit door chained, or opening onto a locked yard An escape route that fails at the last step. The door cannot be opened without a key, or the yard is closed.Keep final exits openable without keys, and the route beyond them clear.
What you see Likely cause, and what confirms it Next step Old ceiling sagging in the middle of the room Lath and plaster keys failing. Inspection from above.Keep people out from under it; refix or replace the ceiling. Plasterboard ceiling bowing between battens Fixing or adhesive failure, or water. Inspection from the roof space.Refix with additional fasteners, or replace water-damaged boards after fixing the leak. Mould on bathroom ceiling Condensation from poor exhaust. Fan and humidity check.Improve the exhaust, treat the mould, then repaint. A ceiling fan or heavy fitting fixed to plasterboard alone A fitting pulling the ceiling down over time. No framing behind the fixing.Refix it to the framing.
What you see Likely cause, and what confirms it Next step Hairline cracks at joints and cornices Normal shrinkage and movement. Pattern; stability.Repair the cracks, with flexible joints where movement will recur. Tapering cracks above doors and windows Structural or foundation movement. See foundations page.Treat it as possible structural movement; see Foundations .
What you see Likely cause, and what confirms it Next step A textured ceiling in an older building about to be drilled for new lights Possible asbestos about to be disturbed. The asbestos register, and testing before work.Test first; leave intact material undisturbed, or have licensed contractors remove it. Old painted walls or ceilings about to be sanded or stripped Lead in older paint. Paint testing before work, against the definition of lead paint for the asset’s market (Thresholds by market ).Test first; use lead-safe methods and clean-up, and keep occupants away during the work.
What you see Likely cause, and what confirms it Next step Stained suspended tiles in a line Leak from services or the floor above. Trace the line.Trace the line to its source and repair it, then replace the tiles. Tiles left out, or mismatched, after services works A ceiling system with gaps in it. Openings in a ceiling that forms part of a fire, smoke or acoustic system.Replace the tiles, and restore the ceiling system. Services cut through a fire-rated ceiling Rating lost to penetrations. Openings above the ceiling without fire stopping.Fire stop the penetrations with tested systems.
What you see Likely cause, and what confirms it Next step Swollen cabinet base under the sink Slow leak at waste or tap connections. Inspection with the cabinet emptied.Repair the connection, replace the swollen base and kickboard, and fit isolation valves. Water on the floor in front of the dishwasher Hose or door seal leak. Run a cycle and inspect.Replace the hose or door seal, and check the floor beneath. Braided hoses with rust spots, kinks or no date tag Hoses near the end of their life. Corrosion at the crimped ends, and an installation date unknown or more than five to ten years ago.Replace them with quality hoses and accessible isolation valves. Floor beside the refrigerator lifting or stained A leak at the refrigerator's water connection. Moisture readings are highest behind the refrigerator, and the supply line weeps when it is pulled out.Repair or replace the connection, and fit an isolation valve. Hot water too hot at the kitchen tap Temperature control failed or absent. Outlet temperature against the limits for the asset’s market (Thresholds by market ).Fit or repair tempering at the heater or outlet.
What you see Likely cause, and what confirms it Next step Condensation and mould after cooking Rangehood recirculating or ducted into the ceiling. Duct route inspection (Thresholds by market ).Duct the rangehood to outside, sized for the cooktop. Grease film on cupboards and the ceiling near the cooktop Extraction too weak, or filters clogged. Saturated filters and little airflow at the hood.Clean or replace the filters; duct or upgrade the hood.
What you see Likely cause, and what confirms it Next step Scorch marks behind the cooktop Clearance to combustible materials too small. Measurement against gas rules.Have a licensed gas fitter correct the clearance, or replace the splashback with non-combustible material. Circuit trips when cooking Overloaded circuit. Load assessment.Add dedicated circuits for the cooktop, oven and dishwasher, with RCD protection. Smoke alarm missing or disabled near the kitchen An alarm removed after nuisance alarms from cooking. An empty alarm base, or the battery taken out.Refit alarms positioned to avoid nuisance alarms, and add a fire blanket near the cooktop.
What you see Likely cause, and what confirms it Next step Benchtop edges chipped, swollen or delaminating near the sink Water reaching the core of a laminate or timber top. Edges and joints at the sink and cooktop.Reseal or replace the affected sections. Engineered stone benchtop to be cut or modified Silica dust hazard. Product type; current rules on engineered stone.Do not cut or modify it on site; replace with a permitted material if changes are needed.
What you see Likely cause, and what confirms it Next step Car walls repeatedly damaged Goods and moves in passenger lifts. Protection practices.Use protective pads for moves, or direct goods to a goods lift; refurbish with impact-resistant finishes. Complaints from vision-impaired users Missing tactile and audio features. Accessibility audit.Fit braille and tactile buttons, and audible and visual indicators. A hot, dark car A failed car fan or lights. Fan and lights checked with the contractor (Thresholds by market ).Repair or replace the car fan and lighting. A trip edge at a landing entrance Worn sills or poor levelling. The step measured at each landing against the limits for the asset’s market (Thresholds by market ).Repair the sills, and have the contractor adjust the levelling; see Passenger & Goods Lifts . Car too small for a wheelchair user to enter and use Car below current access sizes. Car dimensions against the limits for the asset’s market (Thresholds by market ).Record the gap for the next modernisation.
What you see Likely cause, and what confirms it Next step Breakdowns cluster on hot days Machine room overheating. Temperature logging.Log machine room temperatures; add cooling or ventilation, with temperature alarms, before replacing components. A machine room used for storage, or left unlocked Poor housekeeping and access control. Stored items beside the equipment, and no lock.Clear it, lock it, and light the access route. Drips onto controllers in a rooftop machine room Roof leaks. Staining above the controllers, and leaks after rain.Repair the roof, and waterproof the machine room.
What you see Likely cause, and what confirms it Next step Corrosion of pit equipment Water in the pit. Pit inspection; sump.Drain and waterproof the pit, with a sump pump and alarm where groundwater is present.
What you see Likely cause, and what confirms it Next step Near misses between forklifts and people No segregation or traffic plan. Observation; incident records.Segregate walkways with barriers, mark crossings, and write and enforce a traffic management plan. Dock doors open with no trailer and no barrier An open edge that people and forklifts can fall from. Doors left open between deliveries, and levellers left raised.Keep doors closed or barriers in place when no trailer is docked, and store levellers level.
What you see Likely cause, and what confirms it Next step Door damaged repeatedly at the same height Vehicle or forklift impact. Door location against traffic paths.Protect the door with bollards and guide protection, or move it out of the traffic path. Canopy and services damaged at the dock entry Vehicles taller than the dock was designed for. Clearance against vehicle fleet.Check clearances against the vehicles now delivering; add height warnings, or raise the canopy and services. A roller shutter that drops quickly or stops part-way A failing counterbalance spring or cable. The door is heavy to lift by hand, or the spring shows wear or breakage.Take the door out of use, and replace the springs and cables.
What you see Likely cause, and what confirms it Next step Dock floods in storms Blocked grates or failed pumps. Inspection; pump tests.Clean the grates and pits, and maintain the pumps with alarms. Odour and vermin in the dock Waste room management. Inspection; contract review.Right-size the waste room, add a compactor and washdown, and vermin-proof it. Bins stacked against walls under combustible linings A waste room set up to become a fire origin. Linings not fire-rated, and bins against the walls.Enclose the waste room in fire-rated construction, and keep bins off the walls. A diesel smell in corridors next to the dock Vehicles idling in an enclosed dock. Fumes strongest at delivery times, with carbon monoxide readings to match.Ventilate the dock with fans interlocked to carbon monoxide detection, and enforce no-idling. Drivers or staff with headaches after vehicles idle in an enclosed dock Exhaust building up. Carbon monoxide readings at workstations while vehicles run, against the exposure limits for the asset’s market (Thresholds by market ).Stop engines idling, improve extract, and add monitoring if the readings are high.
What you see Likely cause, and what confirms it Next step Planters, furniture or displays against upper-level balustrades Edges made climbable by what stands against them. Items within reach of the top rail on an upper level.Move the items away, and set rules and fixings that keep them away. A cracked overhead pane with no sign of impact Possible spontaneous breakage of toughened glass. The glass marking and fracture origin, and the glass schedule.Protect the area below now, and replace with laminated glass. An upper-level balustrade that seems low, or with gaps a child could pass through Barrier that may not prevent a fall. Height and openings measured against the asset’s market (Thresholds by market ).Raise or infill the barrier, and keep climbable furniture away from it.
What you see Likely cause, and what confirms it Next step Smoke test fails to clear the atrium Exhaust or make-up air shortfall, or changed geometry. Integrated test; layout review.Repair fans and dampers, restore make-up air, or have the fire engineer redesign for the changed geometry. A new floor infill, bridge or enclosure inside the atrium An alteration that may invalidate the smoke design. The geometry compared with the fire engineering report.Have the fire engineer review it before approval, and retest the system.
What you see Likely cause, and what confirms it Next step Drips onto the floor in cold weather without rain Condensation on cold glass or frames. Weather correlation; humidity.Control the condensation with warm air over the glazing, thermally broken frames, or humidity control. Drips in rain Glazing seal or gutter failure. Water test.Water test, and renew the seals and gutters. Upper levels hot, ground floor draughty Stratification and stack effect. Temperature profile.Add high-level exhaust or destratification fans, solar control, and draught lobbies at entries. Announcements hard to understand Echo from a large volume with hard finishes. Reverberation measured, or obvious to the ear.Add absorptive panels, baffles or finishes.
What you see Likely cause, and what confirms it Next step Many failed high-level lights No practical maintenance access. Access strategy.Provide gantries, monorails or winches, or move equipment within reach. Dim circulation routes at night or in winter Failed fittings or lighting designed for the space when new. Lux survey of the routes against the asset’s market (Thresholds by market ).Replace failed fittings and add lighting where the survey falls short.
What you see Likely cause, and what confirms it Next step Slips concentrated inside the entry on wet days Matting too short or worn; slippery finish. Wet slip resistance test; matting length.Lengthen and recess the matting; test the floor wet, and treat or replace the finish in the wet zone. Floor dull in a path from the door Grit tracked past inadequate matting. Matting review.Extend the matting so grit is removed before the hard floor, and hone the stone. A floor slippery even when dry after cleaning Cleaning products leaving residue, or a sealer that polishes the surface. Slip resistance improves once the residue is stripped.Change the cleaning products, strip the sealer, and retest. A lip at the threshold or matwell Trip at the change of level. Level change measured against the asset’s market (Thresholds by market ).Reset the mat flush, or bevel or ramp the threshold.
What you see Likely cause, and what confirms it Next step Door strikes reported Sensors or safety settings out of adjustment. Door safety check against the standard.Reset sensors, safety beams and closing speeds to the standard, and record the check. Turnstiles stay locked in an alarm test Fire interface fault. Interface test.Repair the fire interface, and test release on alarm and on power loss. A revolving door with no swing or sliding door beside it No accessible alternative to the revolving door. People using wheelchairs, prams or walking aids cannot pass.Add an adjacent accessible door. An accessible gate at the turnstiles that is locked, or none at all Security added without an accessible route. The only wide gate needs staff to open it.Provide a wide accessible gate that opens without staff and releases on alarm. Entrance door heavy to open, or narrow for a wheelchair Door force or width short of access needs. Opening force and clear width measured against the asset’s market (Thresholds by market ).Adjust or replace the closer, fit a powered operator, or widen the opening.
What you see Likely cause, and what confirms it Next step Draughts and doors hard to open in winter Stack effect or no draught lobby. Pressure and airflow observation.Add a draught lobby or air curtain, and review stack effect with the mechanical engineer. Heaters under the reception desk Draughts reaching the desk. Staff report cold in winter, and the desk faces the doors.Treat the cause with a draught lobby or air curtain, rather than heaters.
What you see Likely cause, and what confirms it Next step Visitors unable to find lifts or tenants Wayfinding and sightlines. Observation; directory currency.Update the directories, and open sightlines to the lifts.
What you see Likely cause, and what confirms it Next step Broken ceiling tiles under plant People standing on the ceiling to reach equipment. Access review.Provide catwalks or access panels below the equipment, so no one stands on the ceiling. Workers using portable ladders to roofs No fixed access. Observation.Install fixed access with fall protection, or a guarded hatch. Footprints on insulation, and no walkway boards People walking on joists hidden by insulation. Damage to the ceiling below, and insulation crushed in a line.Lay walkway boards to every item needing maintenance, with lighting. Fixed ladder or platform to plant with uneven rungs or no guardrail Access unsafe for regular use. Rung spacing and width, and guardrail height, measured against the asset’s market (Thresholds by market ).Repair or replace the ladder and add guardrails, or provide a stair where access is frequent.
What you see Likely cause, and what confirms it Next step Unsigned pits and tanks Confined spaces not identified. Register review.Identify, sign and lock every confined space, and set entry procedures and rescue plans. A sump or tank with a lid anyone can lift A confined space with no control on entry. No sign, no lock, and no entry in the register.Sign and lock it, and add it to the register with an entry procedure. Workers entering a pit or tank without a gas test Confined space entered without controls. Gas monitoring before and during entry, against the exposure limits for the asset’s market (Thresholds by market ).Stop entry until there is a permit, testing and rescue arrangements.
What you see Likely cause, and what confirms it Next step Foil insulation lying on old wiring in a roof space A risk of electrocution. Foil in contact with cables, or rubber-insulated wiring nearby.Have an electrician isolate and assess before anyone works in the space, and separate or remove the foil. A roof space too hot to work in by midday Heat stress in an insulated, poorly ventilated roof. Temperatures measured during the working window.Schedule roof space work for the cooler part of the day.
What you see Likely cause, and what confirms it Next step Filters and dampers neglected above ceilings No practical access. Maintenance records.Provide practical access, or relocate the plant at replacement.
What you see Likely cause, and what confirms it Next step Conversations audible between meeting rooms Gap above ceiling or services penetration. Ceiling void inspection.Seal the gap above the ceiling and around services, or add ceiling barriers. Rated wall with open penetrations Services works without fire stopping. Inspection.Fire stop every penetration with tested systems. Back-to-back power outlets in a wall between apartments or meeting rooms A sound and fire path through the wall. Outlets aligned on both faces of the same cavity.Offset the outlets, or seal behind them. Neighbours heard through a wall between apartments Separating wall short of its sound insulation. Field sound test against the asset’s market (Thresholds by market ); flanking paths and penetrations checked.Seal penetrations and flanking paths, or add an independent lining.
What you see Likely cause, and what confirms it Next step A corridor or riser wall altered or removed during a fit-out A base-building fire or acoustic wall lost without review. The fire strategy plans compared with the walls on site.Reinstate the wall, and require fire and acoustic review before base-building walls are altered.
What you see Likely cause, and what confirms it Next step Cracking at the partition head Slab deflection without a deflection head. Head detail inspection.Fit or free a deflection head. Full-height glass with nothing at eye level Glazing people walk into. No manifestation; check whether the glass is safety glass.Add manifestation, and replace any glass that is not safety glass. Swelling and staining at the base of plasterboard near wet areas Water reaching standard plasterboard. Moisture readings at the base of the wall.Fix the water source, and replace with moisture-resistant board. People walking into glass screens or doors Glazing not marked. Manifestation heights and contrast against the asset’s market (Thresholds by market ).Add manifestation at the required heights, contrasting with the background.
What you see Likely cause, and what confirms it Next step Operable wall dragging or dropping Track or carrier wear. Service inspection.Service the tracks and carriers, or replace failing panels; stop using the wall if a panel drops.
What you see Likely cause, and what confirms it Next step Refrigerant alarms or low charge Leaks in a poorly ventilated room. Leak detection records (Thresholds by market ).Find and repair the leak, and check the room's detection and emergency ventilation. A gas or carbon monoxide detector with a lapsed calibration label Detection not calibrated. Calibration records have lapsed, and the detector does not alarm on test gas.Calibrate or replace the detectors, and test the alarm to the building management system.
What you see Likely cause, and what confirms it Next step Trips and failures of electrical equipment in summer Overheated switch room. Temperature logging.Log temperatures; restore the ventilation, or add cooling to the switch room. Equipment corroded at low level Flooding or chronic damp. Flood history.Reroute water pipes away from electrical equipment, and add upstands, sumps and alarms. Boxes, furniture and redundant equipment in front of a switchboard A plant room used as a storeroom. The working clearance at the switchboard is obstructed; clearances measured against the asset’s market (Thresholds by market ).Clear the room, remove redundant equipment, and set housekeeping rules. No bund under a fuel tank or chemical store Spill containment never provided. Staining on the floor, with no upstand or drain.Install a bund and drainage for the store.
What you see Likely cause, and what confirms it Next step No route for a chiller replacement Plant boxed in after installation. Dimensions against openings.Plan a route now: knock-out panels, removable louvres, roof hatches, lifting beams or floor strengthening. Noise complaints from occupied floors Failed isolators or acoustic breaches. Vibration measurements.Replace failed isolators, and add acoustic linings or enclosures. One exit from a large plant room No second exit. Travel distance to the single door from the far corner.Provide a second exit where the room's size requires it. Fixed ladder to a plant platform with uneven or narrow rungs Unsafe access. Rung spacing and width against the limits for the asset’s market (Thresholds by market ).Repair or replace the ladder, or provide a stair where access is frequent.
What you see Likely cause, and what confirms it Next step Stain on the ceiling below a toilet block Membrane failure or pipe leak. Flood test; dye test; duct inspection.Flood test the floor and dye test the fixtures; repair the membrane, joint or duct pipework found. Odour in a lightly used room Dry floor waste trap. Trap inspection.Fit trap primers or water-based seals to dry wastes. Odour near urinals Scale and blockage or failed waterless cartridges. Inspection.Descale or clear the urinals, or replace failed waterless cartridges on a schedule. Cubicle partitions swelling at the base Moisture and cleaning water. Material type.Replace with moisture-resistant partitions. Toilets in one block blocking again and again A defect in the stack or branch, rather than misuse. Blockages recur in the same block; a CCTV survey of the branch shows the defect.CCTV the branch and stack, and repair the defect.
What you see Likely cause, and what confirms it Next step Queues at peak Fixtures below the occupancy now on the floor. Count against code ratios.Count fixtures against the code ratios for the current occupancy; add fixtures or convert space. Bike racks, lockers and showers full at peak End-of-trip demand beyond what was provided. Counts at peak and usage data.Expand the end-of-trip facilities to match demand.
What you see Likely cause, and what confirms it Next step An end-of-trip shower unused for weeks A dead leg where Legionella can grow. Temperature checks and flushing records show water standing.Flush it on a recorded schedule, and disinfect if testing warrants. An accessible toilet used for storage, or locked A management failure, not a fabric one. Cleaning gear or boxes inside, or no one can find the key.Clear it, keep it available, and make the access arrangement known. Hand basin water too hot to keep hands under Tempering failed or absent. Outlet temperature against the asset’s market (Thresholds by market ).Fit or repair tempering or thermostatic mixing valves and retest every outlet. Hot water slow to arrive or lukewarm at little-used outlets Legionella risk from low temperature or stagnation. Temperatures at the outlets over time, and the flushing record, against the asset’s market (Thresholds by market ).Restore temperatures, flush little-used outlets, and remove dead legs.
What you see Likely cause, and what confirms it Next step A unit entry door that does not close by itself, or a replacement door of a different design A failed closer, or an owner-fitted door that is not fire-rated. The door stays open when released, and there is no evidence of its fire rating.Repair the closer, or replace the door with a self-closing, sealed, fire-rated door. Smoke alarms that sound only in the room where they are tested Alarms that are not interconnected. Testing one alarm does not set off the others.Interconnect them, or replace them with interconnected photoelectric alarms where required.
What you see Likely cause, and what confirms it Next step Mould on ceilings in bathrooms and bedrooms Condensation from inadequate exhaust and heating. Fan airflow; humidity logging; occupant habits.Increase the exhaust and get it running, with humidity or run-on controls; address heating and indoor drying. Stain below a bathroom after showers Membrane or shower screen leak. Flood and dye tests.Flood and dye test; re-waterproof, or replace the screen and seals. Stain below a bathroom constantly Pipe leak. Pressure test; inspection.Pressure test, and repair the pipe. Water at window sills in storms Seal or sill failure. Water test.Water test; replace the seals and repair the sill. Mould behind wardrobes on outside walls Cold surfaces and still air behind furniture. Thermal imaging shows the cold spot, and the mould stops where air moves.Improve ventilation and heating, move furniture off the wall, and treat the mould.
What you see Likely cause, and what confirms it Next step Impact noise complaints after a renovation Hard floor without acoustic underlay. Floor construction; acoustic test.Test the floor; require a tested acoustic underlay, or remediate where the complaint is upheld. Plumbing noise heard in the unit next door Pipes fixed to party walls without isolation. The noise follows flushing or taps next door.Fit acoustic clips or lagging where the pipes can be reached.
What you see Likely cause, and what confirms it Next step Bathroom or kitchen with no working extract fan Ventilation below what the market expects. Fan airflow measured against the asset’s market (Thresholds by market ).Repair or fit a fan ducted outside. Hot water too hot at the basin or bath Temperature control failed or absent. Outlet temperature against the asset’s market (Thresholds by market ).Fit or repair tempering and retest. A unit short of the operator’s brand or the jurisdiction’s minimum standard Specification below the standard the unit is let or sold against. Checklist of the brand standard or the local minimum standard, room by room.Prioritise items that affect safety and habitability, then brand items at refurbishment.
What you see Likely cause, and what confirms it Next step Food tenants unable to take vacant shops No exhaust riser, grease waste or capacity. Services survey against fit-out guide.Survey services against the fit-out guide, and add exhaust risers, grease waste and power where the market needs them.
What you see Likely cause, and what confirms it Next step Fire alarm faults after each new tenancy Fit-outs altering detection without proper reprogramming. Fire services records.Reprogram and test after each fit-out, and enforce sign-off through fit-out approval. Unsealed penetrations through a demising wall Fit-out services run through the separation without fire stopping. Open holes or foam around services between tenancies.Fire stop with tested systems, and check every fit-out before sign-off. Sprinkler heads boxed in by a tenant's ceiling or signage Coverage lost to a fit-out. Heads above a new ceiling, or blocked by bulkheads.Relocate or add heads to cover the tenancy as it is fitted out. Stock or signage close below sprinkler heads Spray pattern obstructed. Clearance from the deflectors to the top of stock measured against the asset’s market (Thresholds by market ).Lower the storage or relocate the signage, and brief the tenant.
What you see Likely cause, and what confirms it Next step Odour complaints in a mall Exhaust inadequate or discharging near intakes. Exhaust survey.Upgrade the exhaust, and move its discharge away from intakes. Blocked drains downstream of food court Grease treatment inadequate. See trade waste page.Upgrade the grease treatment; see Trade Waste Systems . Stains on the slab below a salon, gym or food tenancy Leaking equipment, floor wastes or wet floors. Stains below the tenancy's wet zones.Repair the source, and require waterproofing and floor wastes in the fit-out guide. Grease deposits in food court extract ducts Cleaning not keeping up with use. Deposit depth against the asset’s market (Thresholds by market ); cleaning records.Clean the full duct run and set the frequency to the use. A food court drain run that blocks repeatedly on a flat section Gradient too shallow for the flow and grease load. Levels and invert survey against the asset’s market (Thresholds by market ).Relay the run to fall, add access, and enforce arrestor maintenance.
What you see Likely cause, and what confirms it Next step Shells handed back in poor order Weak make-good clauses or enforcement. Lease review; condition reports.Tighten the make-good clauses, record condition at entry and exit, and claim where needed. Long vacancy in good condition shells Configuration, trade area or rent. Leasing evidence.Test configuration, trade area and rent; merge or split tenancies if demand supports it. Disputes over outgoings between landlord and tenants Shared or estimated metering. Tenancies that are not separately metered.Separately meter power, water and gas to every tenancy.
What you see Likely cause, and what confirms it Next step Corridors used as stores Insufficient storage for tenants or operations. Storage provision review.Provide storage elsewhere, mark no-storage zones, and enforce through the leases. Exit doors locked Security concerns overriding egress. Security review.Fit security locks that release on alarm and on power failure. Problems concentrated in one section of corridor A particular tenant or operation. Mapping who uses that section, and when.Enforce the lease with that tenant, rather than changing the building. A long route to an exit, or a dead end, after racking or partitions were added Travel distance extended by the layout. Distance to the nearest exit or point of choice measured against the asset’s market (Thresholds by market ).Remove the obstruction or restore the route, and check against the fire strategy.
What you see Likely cause, and what confirms it Next step Doors damaged at trolley height No protection or poor door selection. Inspection.Fit protection plates and buffer rails at trolley height, or more robust doors. A sprinkler pipe or duct dented at low height Struck by trolleys or pallet jacks. Damage at trolley height along the route.Repair or replace the service, and fit guards at low height. Stains on the corridor ceiling or floor A leak from overhead pipes, drains or ducts. Moisture readings, and the run of the service above.Repair the leak, and add drip protection where services cross. Dim sections of corridor Failed fittings or lighting not suited to the use. Lux survey against the asset’s market (Thresholds by market ).Replace failed fittings and add lighting where the survey falls short.
What you see Likely cause, and what confirms it Next step Pests in tenancies near the corridor Waste spills and gaps in corridor walls. Pest reports.Seal the gaps in the corridor walls, and improve waste management and cleaning. Valves and isolation points hidden behind stock or racking Stored goods blocking access to services. Isolations cannot be reached by ladder from the corridor.Clear and mark access zones beneath valves, dampers and trays. Goods stacked close to sprinkler heads in the corridor Spray pattern obstructed. Clearance below the deflectors measured against the asset’s market (Thresholds by market ).Clear the stacking and mark the limit on the wall.
What you see Likely cause, and what confirms it Next step Fume cupboards alarming low flow Exhaust fan, damper or balancing problem. Face velocity and duct tests.Take the cupboard out of use; test face velocity and the duct, then rebalance or replace the fan. Chemical odours in corridors Exhaust re-entrainment or containment failure. Smoke tests; stack location.Smoke test the containment; raise or relocate the stack away from intakes. Brown water from safety shower Stagnation from infrequent testing. Test log.Activate it weekly, flush until clear, and keep a test log. Chemicals stored on benches and floors No ventilated, segregated storage. Containers outside cabinets, and incompatible chemicals together.Provide ventilated, segregated cabinets and stores. Fume cupboard face velocity never tested, or tested years ago Containment unverified. Face velocity and containment test against the asset’s market (Thresholds by market ).Test every cupboard, repair or replace failures, and set an annual test.
What you see Likely cause, and what confirms it Next step Isolation room pressure alarms Door seals, supply and exhaust balance. Pressure monitoring.Restore the door seals and the supply and exhaust balance, and keep monitoring. A medical gas outlet without a clear label, or an alarm panel in fault A medical gas system out of control. Labels missing or wrong, and alarms untested.Have a medical gas specialist test and certify it, under permit. Open seams in clinical sheet flooring Infection-control finishes that have failed. Joints lifting at seams and coving.Replace with seamless flooring and coved skirtings.
What you see Likely cause, and what confirms it Next step Classroom complaints of noise and fatigue Reverberation, ventilation noise or low outdoor air. Acoustic and CO₂ measurement.Measure reverberation and carbon dioxide; add acoustic treatment, quieter ventilation and more outdoor air.
What you see Likely cause, and what confirms it Next step An office floor now used as a laboratory, or a repurposed ward A change of use the services never followed. Exhaust, gases, drainage or safety equipment unchanged from the old use.Review the services against the new use, and upgrade them.
What you see Likely cause, and what confirms it Next step Mould and rot around an indoor pool Inadequate dehumidification and vapour control. Humidity logging; fabric inspection.Log humidity; add dehumidification, ventilation and vapour control, and repair the damaged fabric. A steam or chemical smell elsewhere in the house A pool hall or steam room not separated from the rest of the building. Odour and humidity readings in adjoining rooms.Separate it with sealed doors and its own ventilation. Corroded fixings, light fittings and ventilation around an indoor pool Pool chemicals and their by-products attacking metalwork. Corrosion concentrated in the pool hall.Replace corroded items with suitable materials, and improve the ventilation.
What you see Likely cause, and what confirms it Next step Floor deflection under a spa or aquarium Load beyond design. Engineering check.Have an engineer check the load; strengthen the floor or reduce the load. Tripping circuits Electrical faults in wet areas. Electrical test.Test the circuits; add RCD protection, and separate equipment from water. A sauna heater close to timber linings A fire hazard. The clearance between heater and linings.Correct the clearance to the heater's requirements. A pool or spa without a barrier, or with a gate that stays open Child drowning risk. Barrier height, gaps, climbable zones and gate closing measured against the asset’s market (Thresholds by market ).Repair or install the barrier, and fix the gate to close and latch from any position.
What you see Likely cause, and what confirms it Next step Feature cannot be repaired Supplier gone. Supplier search.Search for a supplier; replace the platform with an open alternative, or decommission the feature. Services capped and left behind where a feature was removed A decommissioning never finished. Capped pipes and cables, and damaged fabric, where the feature stood.Make the services safe, and repair the fabric.
What you see Likely cause, and what confirms it Next step Floor cracks under a compactus room Overload beyond design. Load calculation against design.Have an engineer check the loads; move the storage over beams or to a lower floor, limit its density, or strengthen the floor. New compactus on an upper floor with no engineering on record Heavy storage added without a load check. No approval or calculation on file.Have the floor checked against the load before the shelving is filled. Archive boxes or compactus on a floor designed for offices Load beyond the floor’s design. The design imposed load compared with the storage load, against the asset’s market (Thresholds by market ).Have an engineer confirm the capacity before loading further.
What you see Likely cause, and what confirms it Next step Sprinklers blocked by stacked goods Housekeeping and inadequate storage space. Clearance measurement.Clear and mark maximum stacking heights; upgrade the sprinklers if the stored hazard has outgrown them. E-bikes charging in basement storage cages Battery charging in stores. Cables run from outlets into cages, with batteries left on charge.Ban charging in cages and stores, and provide a charging room with detection. Store doors propped open, or stores with no detection Fire separation and early warning defeated. Doors wedged for access, and no detectors in the store.Close the doors or fit hold-open devices linked to the alarm, and add detection. Boxes stacked up close to the sprinkler heads Spray pattern blocked from above the goods. Clearance below the deflectors measured against the asset’s market (Thresholds by market ).Lower the stacks and mark the limit on the racking.
What you see Likely cause, and what confirms it Next step Corroded fittings near a chemical store Fumes from incompatible or unventilated storage. Inventory; ventilation check.Separate incompatible chemicals into bunded, ventilated cabinets or rooms. No register of what is stored where Dangerous goods not recorded. No manifest, and quantities unknown.Inventory the store, and keep a register and manifest.
What you see Likely cause, and what confirms it Next step Mould on archive boxes Damp basement or poor ventilation. Humidity logging.Dehumidify, stabilise the temperature, and remove damp-damaged material. Water-stained boxes Leaks from overhead pipes. Pipe route survey.Reroute the pipes or add drip trays and leak detection, and raise storage off the floor.