Stairs fail in daily use through falls: worn and slippery nosings, edges that cannot be seen, uneven risers, missing handrails, dark landings. As escape routes they fail when doors are propped or closers broken, when storage fills the enclosure, when security locks doors without release or re-entry, when emergency lighting fails, and when final exits are blocked. Propped doors, storage, failed emergency lighting and locked exits are life-safety failures.

What the space does and what it contains

Internal stairwells are the vertical escape routes and everyday stairs of a building: fire-isolated stairs enclosed in fire-rated construction, open stairs between floors, and feature stairs in lobbies and atria. Functionally a stair must be safe to use every day (even risers, slip-resistant nosings, handrails, good light), and, if it is an escape stair, must stay clear, protected from fire and smoke, lit when the power fails, and lead people out to safety. Fire-isolated stairs are the most important life-safety space in a multi-storey building and the one most often misused for storage, smoking and shortcuts.

What a stairwell contains
Element groupTypical provisionWhat matters for the space
Treads, risers and nosingsConcrete, steel or timber stairs with nosingsEven geometry; slip resistance; visible edges
Handrails and balustradesHandrails on one or both sides; balustrades at open sidesHeight, continuity, grip, openings
Enclosure and doorsFire-rated walls and self-closing fire doorsFire and smoke separation
Smoke controlStair pressurisation or vents in taller buildingsKeeping smoke out
Lighting and emergency lightingLighting on every flight and landingVisibility when power fails
SignageExit signs, floor level identification, re-entry signsOrientation in an emergency
DischargeExit to open space or a protected routeClear path to safety

How long it stays fit for purpose

How long a stair stays fit for purpose
Component or qualityTypical lifeWhat moves it
Stair structureLife of the buildingCorrosion of steel stairs; alterations
Nosings10 to 25 yearsTraffic; product
Floor finishes on treads and landings10 to 20 yearsTraffic; cleaning
Fire door hardware10 to 15 yearsUse; abuse
Paint and wall finishes7 to 15 yearsDamage; appearance
Stair lighting15 to 20 years for LEDTechnology

What shortens fitness for purpose:

  • Use as storage, smoking areas or shortcuts, with doors propped open.
  • Worn nosings that become slippery and hard to see.
  • Security measures that lock stair doors without proper release.
  • Penetrations by services through stair walls.

Stair condition is less a matter of age than of how the stair is used.

How the space fails

Falls

Falls on stairs are among the most common serious injuries in buildings. Worn or slippery nosings, edges that cannot be seen, uneven risers, missing handrails, poor lighting and wet treads from leaks all contribute. Older stairs often have handrails on one side only and nosings without contrast.

Fire doors propped or failing

Stair doors are propped for convenience, ventilation or deliveries, and closers and latches fail. A propped stair door lets smoke into the escape route for every floor above and defeats stair pressurisation.

Storage and obstruction

Furniture, boxes, bicycles and rubbish stored in stairs, especially under the lowest flight, narrow the route and add fire load inside the protected enclosure.

Locking and re-entry

Security often locks stair doors from the stair side to stop people moving between floors. Rules in each jurisdiction allow this only under conditions such as release on fire alarm or re-entry floors, so that people in a smoke-filled stair can leave it. Locks fitted without those conditions can trap people.

Loss of fire separation

Service penetrations, unrated access panels and glazing replaced with ordinary glass compromise the stair enclosure.

Smoke control failure

Pressurisation that has failed or is unbalanced either lets smoke in or makes doors too hard to open; see the smoke management page.

Blocked discharge

Stairs that discharge into car parks, loading docks or locked yards, or whose final exit doors are blocked or chained, fail at the last step.

What to look for

On site, flight by flight

  • Doors propped, wedged or held by hooks; closers and latches not working.
  • Storage, bikes or rubbish in stairs and under flights.
  • Worn, polished or loose nosings; no contrast strips.
  • Handrails missing, loose or on one side only.
  • Dark landings; emergency lights failed.
  • Floor level signs missing.
  • Locked stair doors with no indication of release.
  • Final exits blocked or locked.

In the records

  • Fire door inspection records.
  • Annual fire safety certification.
  • Fall incidents on stairs.
  • Smoke control test records.
  • Security locking arrangements and fire alarm interfaces.
  • Cigarette butts and furniture on landings, a sign the stair is used as a break area.

Telling causes apart

Reading the signs
What you seeMost likely causeWhat confirms it
Falls on one flightUneven risers, worn nosings or poor lightRiser measurement; nosing condition
Doors propped on several floorsStair used for circulation between floorsUse patterns
Smoke in the stair during a drillDoors propped or pressurisation failedDoor survey; smoke test
People unable to leave the stair on a floorLocked re-entry without releaseSecurity interface test
Water on treadsRoof or services leak into the stairLeak tracing

How serious it is

Findings are graded by what they demand: safety (can hurt someone now), failure (failed and damaging the building), condition (distress present and progressing), lifecycle (renewal due on age and exposure), deadline (a regulator or ordinance sets the date), check (investigate before sizing works) and nil (cosmetic or stable).

Grading stairwell findings
FindingSituationWhat it means for timing
Propped or failed stair doors; storage in stairs; failed emergency lighting; locked final exits; unsafe lockingsafetyRectify now
Stair unusable through damage or leaksfailureRepair now
Fire door and emergency lighting checks duedeadlineAt the prescribed interval
Worn nosings; missing handrails; dark landingsconditionRepair in the near term
Finishes at end of lifelifecycleRefurbish
No review of locking and re-entrycheckAssess
NormalnilRoutine

Most stair findings are cheap to fix, so there is rarely a reason to defer them.

Investigation and testing

A building surveyor with a fire safety consultant; a security consultant where stairs are locked.

  • Flight-by-flight inspection of every stair: doors, closers and latches, storage, treads and nosings, handrails, lighting, signage, enclosure penetrations and discharge.
  • Riser and going measurement where falls occur or stairs look irregular.
  • Slip resistance testing of nosings and landings.
  • Locking and re-entry test: security doors released by the fire alarm and on power failure.
  • Smoke control and emergency lighting tests.
  • Use review: why doors are propped and stairs used for storage.

The report should list life-safety items by stair and floor, and stair improvements.

Stairs are best inspected at different times of day, because propped doors and storage often appear outside business hours.

Night and weekend checks are often revealing.

Remedies and refurbishment

  • Door repair: closers, latches and seals restored so every stair door closes and latches from fully open; hold-open devices linked to the fire alarm where stairs are genuinely used for circulation between floors.
  • Clear storage from every stair and enforce building rules, with regular checks recorded.
  • Nosings: slip-resistant nosings with contrasting edges on every tread and landing edge, so each step can be seen and gripped.
  • Handrails on both sides where required, continuous through landings, at the right height and graspable.
  • Lighting: even lighting on every flight with emergency lighting tested to the standard, and occupancy-dimmed lighting that never leaves a flight dark.
  • Locking: bring security locking into line with release-on-alarm and re-entry rules, with signage on the stair side.
  • Fire stopping of service penetrations and replacement of any unrated panels or glazing in the enclosure.
  • Final exits kept clear and openable without keys, with signage outside to stop obstruction.

Cost shape

Stair works are priced per flight or per stair. Nosings and handrails are priced by length; door works per door; lighting per fitting; locking changes per door with fire alarm interface. Most items are code compliance and low in cost relative to their safety value; the main cost driver is doing the work without closing escape routes, which usually means one stair at a time and out-of-hours work.

Keeping stairs clear costs only management time.

Standards and jurisdiction

  • Australia. The National Construction Code sets stair geometry, handrails, fire-isolated stairs and door requirements, with fire doors maintained under AS 1851; slip resistance follows AS 4586; strata and building rules prohibit storage in stairs.
  • United Kingdom. Approved Document B governs escape stairs and Approved Document K stair geometry and guarding; the Fire Safety (England) Regulations 2022 require checks of fire doors in residential buildings; the responsible person must keep escape routes clear.
  • United States. NFPA 101 and the International Building Code govern exit stairs, including re-entry rules for locked stair doors; NFPA 80 covers stair door inspection; OSHA requires exit routes kept clear.

Insurers and fire services in all three countries treat obstructed or compromised escape stairs as serious breaches and can require immediate action or issue orders.

What to ask the owner or agent for

  • Fire door inspection records for every stair door.
  • Annual fire safety certification and any qualifications on stairs.
  • Stair fall incident records.
  • Security locking and fire alarm interface test records.
  • Smoke control and emergency lighting test records.
  • Building rules on stair use and storage, with records of enforcement.

Sources

Related references: the Capital Register and the MR Index.