Mechanical Services: signs, causes and next steps
What does it mean when you see this, and what do you do next?
Moyne Ross
Technical Library
Updated November 14, 2026
Every sign of failure the Technical Library records under Mechanical Services: 79 signs across 9 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.
Scope
A sign usually has more than one possible cause. Each row names the likely one and what would confirm it; none is a diagnosis of a particular building, and none is a price.
What you see Likely cause, and what confirms it Next step Musty smell at start-up Microbial growth in drain pans, coils or wet insulation. Standing water and slime in the pan; wet insulation; swab results.Commission a hygiene inspection; clean the pans and coils, and replace wet insulation. Water on the floor or ceiling below Blocked drain or dry trap. Drain flow; trap depth against fan pressure.Clear the drain, and fix the trap depth and falls.
What you see Likely cause, and what confirms it Next step High carbon dioxide in occupied spaces Outside air damper closed or minimum set too low. Damper position; outside air flow measured against the design and the asset’s market (Thresholds by market ).Measure the outside air; repair the dampers and reset the minimum, with carbon dioxide control. Heat recovery wheel or plate with frost, leaks or a seized bypass Heat recovery not working, or exhaust air carried back into supply. Temperatures across the recovery device; damper and bypass operation.Repair the bypass and seals, and confirm exhaust is not transferring to supply.
What you see Likely cause, and what confirms it Next step Cannot reach supply temperature; low chilled water delta T Fouled cooling coil or failed valve. Coil pressure drop; air and water temperatures across the coil.Clean the coil or repair the valve; replace a corroded coil. Vibration and noise Bearing wear, belt problems or imbalance. Vibration analysis.Replace bearings and belts, or upgrade to a direct-drive fan. Rising fan energy Overloaded filters or fouled coils. Filter pressure drop.Change the filters and clean the coils. Water carried into ductwork Coil face velocity too high or eliminators missing. Airflow measurement.Measure the airflow; reduce face velocity or reinstate the eliminators.
What you see Likely cause, and what confirms it Next step Plant running at night Schedules overridden or lost. Schedule review; trends.Restore the schedules and release the overrides. Many points in manual Workarounds for faults. Point list.Fix the faults behind the overrides, then release them. Hundreds of suppressed alarms Alarm fatigue. Alarm list.Rationalise the alarms so the real ones are seen. Energy high despite modern plant Poor sequences or drifted sensors. Trends; calibration.Recommission: calibrate sensors and rewrite sequences to current loads. Carbon dioxide trends that never move Failed or uncalibrated sensor. Spot reading against the trend: outdoor air is around 400 ppm, and occupied spaces read higher.Calibrate or replace the sensor, and check the ventilation it controls.
What you see Likely cause, and what confirms it Next step Only one contractor can work on it Proprietary system. Protocol and licensing.Secure the licences, programs and passwords; specify open protocols at the next upgrade.
What you see Likely cause, and what confirms it Next step BMS reachable from the internet Insecure remote access. Security assessment.Remove direct internet exposure; secure remote access and change default credentials.
What you see Likely cause, and what confirms it Next step Air handling units keep running during a fire alarm test Fire interface broken. Integrated test from the fire panel with the BMS logging each output.Repair the interface, update the cause-and-effect matrix, and retest jointly with the fire contractor. Meters and other systems missing from the BMS since an upgrade Integration lost when one side changed. Points list against the field devices; protocol and gateway versions.Reinstate the integration, and document it so the next change does not break it.
What you see Likely cause, and what confirms it Next step Evaporator approach rising Low refrigerant charge or fouled evaporator. Refrigerant log; leak test; evaporator inspection.Leak test and repair; inspect the evaporator. Refrigerant added at each service Leak. Refrigerant log; leak test locates it; leak rate against the asset’s market (Thresholds by market ).Find and repair the leak, rather than topping up. High purge run time on an R123 or R11 machine Air leak on the low-pressure side. Purge records; leak test under pressure.Pressure leak test the low-pressure side, and repair it.
What you see Likely cause, and what confirms it Next step Condenser approach rising over months Fouled or scaled condenser tubes. Tube inspection; water treatment records; approach falls after cleaning.Clean the tubes, and correct the water treatment. Surging noise at light load Oversized centrifugal at low load. Load profile; surge events in logs.Review the load profile; a variable speed drive or a smaller machine suits light loads. Acidic oil or refrigerant Moisture or motor winding failure. Oil and refrigerant analysis.Analyse the oil and refrigerant; overhaul the compressor or rewind the motor. Capacity loss on hot days on an air-cooled unit Condenser coil corrosion or fouling, or hot air recirculating. Coil condition; plant screen or wall blocking airflow.Clean or recoat the coils, and clear anything that recirculates hot air.
What you see Likely cause, and what confirms it Next step Chillers cannot load; more chillers and pumps running than the load needs Low delta T in the building. Supply and return temperatures; coil and valve condition.Fix the distribution: failed valves, three-way valves and bypasses, and fouled coils.
What you see Likely cause, and what confirms it Next step Chiller tripping on drive or starter faults in hot weather Drive or starter overheating or failing. Fault log; switchroom temperature; drive age and parts support.Improve cooling to the switchroom and plan drive replacement before parts run out. Control panel the manufacturer no longer supports Obsolete controls stranding a sound chiller. Written support position from the manufacturer.Plan a controls retrofit, keeping the machine if it is otherwise sound.
What you see Likely cause, and what confirms it Next step High make-up water use; system pressure falling Leaks. Make-up meter; inspection of pipework, radiators and boiler.Find and fix the leaks, then restore water treatment. Black water when radiators are bled; cold bottoms on radiators Magnetite sludge from oxygen ingress. Water analysis shows high iron; filter catch.Fix leaks, clean and flush, dose inhibitor, and fit magnetic filtration. Relief valve discharging, pressure swinging Failed expansion vessel. Vessel charge pressure; diaphragm.Replace the expansion vessel or pressurisation unit.
What you see Likely cause, and what confirms it Next step Condensing boiler locking out, low flow faults Blocked heat exchanger. Pressure drop across the boiler; water quality.Clean the heat exchanger, and clean the system so it does not foul again. Water in the combustion chamber of a cast iron boiler Cracked section. Leak visible from inside; history of cold starts.Replace the cracked section, or the boiler. Corrosion inside a non-condensing boiler Running too cool. Return temperature records.Raise the return temperature with controls, or replace with a condensing boiler.
What you see Likely cause, and what confirms it Next step Building cannot reach temperature after a heat pump retrofit Emitters sized for higher flow temperatures. Heat loss vs emitter output at heat pump flow temperature.Upgrade the emitters, improve the fabric, or carry the peaks with a boiler. Boilers cycling every few minutes Oversizing or poor controls. Load profile from gas data; burner run hours vs starts.Sequence the boilers, or replace with modular boilers sized to the measured load. Condensing boilers achieving non-condensing efficiency High return temperatures from the building. Return temperature; bypasses; three-port valves.Lower return temperatures with weather compensation and return temperature control.
What you see Likely cause, and what confirms it Next step Calorifier stored below 60 °C Setpoint lowered or plant undersized for hot water. Temperature records; Legionella sampling.Restore the storage temperature, or upgrade the plant for the hot water demand.
What you see Likely cause, and what confirms it Next step Fire damper blades painted or obstructed Poor installation or maintenance. Inspection.Clear and test the dampers, and fit access panels. No damper test records, or dampers that cannot be reached Fire dampers of unknown condition. Records and access survey, against the test intervals for the asset’s market (Thresholds by market ).Add access panels, test every damper, and repair or replace failures.
What you see Likely cause, and what confirms it Next step Water stains on ceilings along duct runs, in summer Condensation from torn vapour barrier. Insulation inspection.Repair the insulation and vapour barrier, sealing every joint. Rust and drips at duct joints near cold plant Joint leakage and condensation. Leakage test of the section; insulation and vapour barrier inspection.Seal the joints and reinstate the vapour barrier.
What you see Likely cause, and what confirms it Next step Dust streaks around diffusers Dirty ductwork or poor filtration. Duct inspection; filter condition.Fix the filtration, then clean the ductwork to the hygiene standard. Fibres at diffusers Eroding internal lining or fibreglass ductboard. Inspection.Replace the lining with faced lining, or move attenuation to dedicated attenuators. Grease in a kitchen extract duct beyond the hood Fire risk from grease. Deposit thickness against the asset’s market (Thresholds by market ).Clean the full duct to the specification, adding access panels where needed.
What you see Likely cause, and what confirms it Next step Zones short of air after a fit-out Loss of balance or kinked flex. Airflow measurement.Rebalance, relocate diffusers, and replace kinked flex with short, straight runs. Noise and draughts at diffusers after a fit-out Airflow redistributed by the new layout. Airflow at each diffuser against design.Rebalance the system, and replace kinked or crushed flexible duct.
What you see Likely cause, and what confirms it Next step High bacterial counts Treatment failure, dead legs, stagnation. Records; system inspection; counts against the action levels for the asset’s market (Thresholds by market ).Disinfect and resample; restore treatment and remove dead legs. Drift visible from the tower, or a tower close to air intakes or windows Aerosol reaching people. Drift eliminator condition; distances to intakes, windows and public areas.Replace or refit eliminators, and review siting with the risk assessment.
What you see Likely cause, and what confirms it Next step Rising condenser approach on the chillers Scaled or fouled tower and tubes, or tower capacity lost. Tower inspection; water treatment records.Clean the tower and tubes, and check the tower's capacity. White powder on galvanised surfaces White rust from unbalanced water. Water chemistry.Rebalance the water treatment. Fill sagging or collapsed Biofouling and deposits. Visual; fill weight.Replace the fill, and correct the water treatment. Standby cell or tower left idle for weeks Stagnant water and biofilm. Operating records; water treatment in the idle cell.Run or drain idle cells, and disinfect before returning them to service.
What you see Likely cause, and what confirms it Next step Head pressure high on hot days, air-cooled plant Hot air recirculation or fouled coils. Temperature at coil inlet higher than ambient.Clean the coils, and remove the screens or walls that recirculate hot air. Plant screens added around air-cooled condensers Hot air trapped and recirculated. Coil inlet temperature compared with ambient.Open the screen, add baffles, or move the units.
What you see Likely cause, and what confirms it Next step Unit regassed repeatedly Refrigerant leak. Leak test; larger systems are also held to leak-rate triggers in some markets (Thresholds by market ).Pressure test and repair the leak, rather than regassing. Unit runs continuously and never reaches setpoint Undersized, low refrigerant, or fouled coils. Load calculation; refrigerant pressures; coil condition.Check the charge, coils and sizing; repair or resize. Unit starts and stops every few minutes Oversized or controls fault. Load; thermostat location.Check the controls; replace oversized units at renewal. Many units of the same age failing together End of life across the population. Installation dates; parts availability.Replace the units as one programme, or consolidate them into VRF or a central system.
What you see Likely cause, and what confirms it Next step Capacity loss on hot days Coil corrosion or hot air recirculation. Coil condition; siting.Clean the coils or replace them with coated coils, and clear any recirculation. Unit dead after a storm Electronics failure. Error codes; board replacement availability.Repair the board, or replace an older unit.
What you see Likely cause, and what confirms it Next step Water stains below indoor unit Blocked drain or failed pump. Drain inspection.Clear the drain or replace the condensate pump. Ducted system weak in some rooms Disconnected or kinked flexible duct. Roof space inspection.Reconnect and straighten the flexible ducts.
What you see Likely cause, and what confirms it Next step Carbon monoxide alarm near a rooftop unit supply Cracked heat exchanger. Combustion inspection.Shut the unit down; replace the heat exchanger or the unit.
What you see Likely cause, and what confirms it Next step Ceiling stains below fan coils Blocked or overflowing condensate drain. Drain pan inspection.Clear the drain, fix the falls and traps, and fit overflow switches above sensitive areas. Fan coil filters clogged or missing Maintenance lapsed. Filter condition and dates on a sample of units.Restore filter changes on a schedule, and clean coils and pans.
What you see Likely cause, and what confirms it Next step Zone too hot, VAV box at full open Box undersized for the load, or upstream supply starved. Airflow measurement; load change.Check the upstream supply and the box sizing, and rebalance. Zone too cold, VAV box at minimum Minimum airflow too high or reheat failed. Settings; reheat valve.Lower the minimum, or repair the reheat. Heating and cooling at the same time Reheat valve stuck or controls fighting. BMS trends.Free the reheat valve, and recommission the sequences. Many zones in manual override Controls problems worked around. BMS point list.Fix the faults behind the overrides, then recommission. Stuffy meeting rooms with VAV boxes at minimum Outside air short when the box turns down. Airflow and carbon dioxide in the room against the asset’s market (Thresholds by market ).Reset minimum airflows for ventilation, or add demand-controlled ventilation.
What you see Likely cause, and what confirms it Next step Dripping from chilled beams Chilled water below room dew point. Water temperature; humidity; dew point control.Add dew point control and condensation sensors.
What you see Likely cause, and what confirms it Next step Car park fans never run CO sensors failed or disabled. Calibration records; sensor test.Replace and calibrate the CO sensors, and restore automatic control. Car park fans always run Sensors failed safe, or controls overridden. BMS; sensor test.Replace failed sensors and remove overrides. Exhaust fumes lingering at car park pay stations or lift lobbies Carbon monoxide reaching people. Readings at occupied points against the asset’s market (Thresholds by market ).Test sensors and fan staging, and add extract or separation at occupied points.
What you see Likely cause, and what confirms it Next step Grease visible in ducts beyond the hood Cleaning frequency or extent inadequate. Cleaning records; inspection.Clean the full system, add access panels, and set the frequency to the cooking volume.
What you see Likely cause, and what confirms it Next step Fume cupboard alarms silenced Low face velocity. Face velocity test against the asset’s market (Thresholds by market ).Restore the alarm; test face velocity, and repair the fans and ductwork.
What you see Likely cause, and what confirms it Next step Mould in bathrooms and roof spaces Exhaust failed or discharging into voids. Fan and duct inspection.Reconnect the ducts, replace the fans, and extend discharges outside. Odour in occupied areas Exhaust re-entry or negative pressure. Discharge locations; pressure test.Move the discharge away from intakes, or rebalance the make-up air. Flue spillage from appliances Negative pressure from exhaust. Combustion and pressure test.Stop using the appliance; add or rebalance make-up air.