Every sign of failure the Technical Library records under Mechanical Services: 79 signs across 9 elements and spaces. Each row gives what you see, the likely cause and what confirms it, and the next step. Each heading opens the page the rows come from.

Air Handling Units (AHUs)

Hygiene, humidifiers and intakes

What you seeLikely cause, and what confirms itNext step
Musty smell at start-upMicrobial growth in drain pans, coils or wet insulation. Standing water and slime in the pan; wet insulation; swab results.Commission a hygiene inspection; clean the pans and coils, and replace wet insulation.
Water on the floor or ceiling belowBlocked drain or dry trap. Drain flow; trap depth against fan pressure.Clear the drain, and fix the trap depth and falls.

Outside air, dampers and heat recovery

What you seeLikely cause, and what confirms itNext step
High carbon dioxide in occupied spacesOutside air damper closed or minimum set too low. Damper position; outside air flow measured against the design and the asset’s market (Thresholds by market).Measure the outside air; repair the dampers and reset the minimum, with carbon dioxide control.
Heat recovery wheel or plate with frost, leaks or a seized bypassHeat recovery not working, or exhaust air carried back into supply. Temperatures across the recovery device; damper and bypass operation.Repair the bypass and seals, and confirm exhaust is not transferring to supply.

Coils, fans and casings

What you seeLikely cause, and what confirms itNext step
Cannot reach supply temperature; low chilled water delta TFouled cooling coil or failed valve. Coil pressure drop; air and water temperatures across the coil.Clean the coil or repair the valve; replace a corroded coil.
Vibration and noiseBearing wear, belt problems or imbalance. Vibration analysis.Replace bearings and belts, or upgrade to a direct-drive fan.
Rising fan energyOverloaded filters or fouled coils. Filter pressure drop.Change the filters and clean the coils.
Water carried into ductworkCoil face velocity too high or eliminators missing. Airflow measurement.Measure the airflow; reduce face velocity or reinstate the eliminators.

Building Management & Control System (BMCS)

Overrides, sequences and sensors

What you seeLikely cause, and what confirms itNext step
Plant running at nightSchedules overridden or lost. Schedule review; trends.Restore the schedules and release the overrides.
Many points in manualWorkarounds for faults. Point list.Fix the faults behind the overrides, then release them.
Hundreds of suppressed alarmsAlarm fatigue. Alarm list.Rationalise the alarms so the real ones are seen.
Energy high despite modern plantPoor sequences or drifted sensors. Trends; calibration.Recommission: calibrate sensors and rewrite sequences to current loads.
Carbon dioxide trends that never moveFailed or uncalibrated sensor. Spot reading against the trend: outdoor air is around 400 ppm, and occupied spaces read higher.Calibrate or replace the sensor, and check the ventilation it controls.

Obsolescence, hardware and ownership

What you seeLikely cause, and what confirms itNext step
Only one contractor can work on itProprietary system. Protocol and licensing.Secure the licences, programs and passwords; specify open protocols at the next upgrade.

Cyber security

What you seeLikely cause, and what confirms itNext step
BMS reachable from the internetInsecure remote access. Security assessment.Remove direct internet exposure; secure remote access and change default credentials.

Integration with fire and other systems

What you seeLikely cause, and what confirms itNext step
Air handling units keep running during a fire alarm testFire interface broken. Integrated test from the fire panel with the BMS logging each output.Repair the interface, update the cause-and-effect matrix, and retest jointly with the fire contractor.
Meters and other systems missing from the BMS since an upgradeIntegration lost when one side changed. Points list against the field devices; protocol and gateway versions.Reinstate the integration, and document it so the next change does not break it.

Central Cooling Plant

Refrigerant obsolescence and leaks

What you seeLikely cause, and what confirms itNext step
Evaporator approach risingLow refrigerant charge or fouled evaporator. Refrigerant log; leak test; evaporator inspection.Leak test and repair; inspect the evaporator.
Refrigerant added at each serviceLeak. Refrigerant log; leak test locates it; leak rate against the asset’s market (Thresholds by market).Find and repair the leak, rather than topping up.
High purge run time on an R123 or R11 machineAir leak on the low-pressure side. Purge records; leak test under pressure.Pressure leak test the low-pressure side, and repair it.

Tubes, compressors and condensers

What you seeLikely cause, and what confirms itNext step
Condenser approach rising over monthsFouled or scaled condenser tubes. Tube inspection; water treatment records; approach falls after cleaning.Clean the tubes, and correct the water treatment.
Surging noise at light loadOversized centrifugal at low load. Load profile; surge events in logs.Review the load profile; a variable speed drive or a smaller machine suits light loads.
Acidic oil or refrigerantMoisture or motor winding failure. Oil and refrigerant analysis.Analyse the oil and refrigerant; overhaul the compressor or rewind the motor.
Capacity loss on hot days on an air-cooled unitCondenser coil corrosion or fouling, or hot air recirculating. Coil condition; plant screen or wall blocking airflow.Clean or recoat the coils, and clear anything that recirculates hot air.

Low delta T and pumps

What you seeLikely cause, and what confirms itNext step
Chillers cannot load; more chillers and pumps running than the load needsLow delta T in the building. Supply and return temperatures; coil and valve condition.Fix the distribution: failed valves, three-way valves and bypasses, and fouled coils.

Starters, drives and controls

What you seeLikely cause, and what confirms itNext step
Chiller tripping on drive or starter faults in hot weatherDrive or starter overheating or failing. Fault log; switchroom temperature; drive age and parts support.Improve cooling to the switchroom and plan drive replacement before parts run out.
Control panel the manufacturer no longer supportsObsolete controls stranding a sound chiller. Written support position from the manufacturer.Plan a controls retrofit, keeping the machine if it is otherwise sound.

Central Heating Plant

Water treatment, pressurisation and distribution

What you seeLikely cause, and what confirms itNext step
High make-up water use; system pressure fallingLeaks. Make-up meter; inspection of pipework, radiators and boiler.Find and fix the leaks, then restore water treatment.
Black water when radiators are bled; cold bottoms on radiatorsMagnetite sludge from oxygen ingress. Water analysis shows high iron; filter catch.Fix leaks, clean and flush, dose inhibitor, and fit magnetic filtration.
Relief valve discharging, pressure swingingFailed expansion vessel. Vessel charge pressure; diaphragm.Replace the expansion vessel or pressurisation unit.

Boilers, burners and combustion

What you seeLikely cause, and what confirms itNext step
Condensing boiler locking out, low flow faultsBlocked heat exchanger. Pressure drop across the boiler; water quality.Clean the heat exchanger, and clean the system so it does not foul again.
Water in the combustion chamber of a cast iron boilerCracked section. Leak visible from inside; history of cold starts.Replace the cracked section, or the boiler.
Corrosion inside a non-condensing boilerRunning too cool. Return temperature records.Raise the return temperature with controls, or replace with a condensing boiler.

Controls and heat pumps

What you seeLikely cause, and what confirms itNext step
Building cannot reach temperature after a heat pump retrofitEmitters sized for higher flow temperatures. Heat loss vs emitter output at heat pump flow temperature.Upgrade the emitters, improve the fabric, or carry the peaks with a boiler.
Boilers cycling every few minutesOversizing or poor controls. Load profile from gas data; burner run hours vs starts.Sequence the boilers, or replace with modular boilers sized to the measured load.
Condensing boilers achieving non-condensing efficiencyHigh return temperatures from the building. Return temperature; bypasses; three-port valves.Lower return temperatures with weather compensation and return temperature control.

Hot water

What you seeLikely cause, and what confirms itNext step
Calorifier stored below 60 °CSetpoint lowered or plant undersized for hot water. Temperature records; Legionella sampling.Restore the storage temperature, or upgrade the plant for the hot water demand.

Ductwork & Air Distribution

Fire and smoke dampers

What you seeLikely cause, and what confirms itNext step
Fire damper blades painted or obstructedPoor installation or maintenance. Inspection.Clear and test the dampers, and fit access panels.
No damper test records, or dampers that cannot be reachedFire dampers of unknown condition. Records and access survey, against the test intervals for the asset’s market (Thresholds by market).Add access panels, test every damper, and repair or replace failures.

Condensation, leakage and wet exhaust

What you seeLikely cause, and what confirms itNext step
Water stains on ceilings along duct runs, in summerCondensation from torn vapour barrier. Insulation inspection.Repair the insulation and vapour barrier, sealing every joint.
Rust and drips at duct joints near cold plantJoint leakage and condensation. Leakage test of the section; insulation and vapour barrier inspection.Seal the joints and reinstate the vapour barrier.

Dirt, linings and hazardous materials

What you seeLikely cause, and what confirms itNext step
Dust streaks around diffusersDirty ductwork or poor filtration. Duct inspection; filter condition.Fix the filtration, then clean the ductwork to the hygiene standard.
Fibres at diffusersEroding internal lining or fibreglass ductboard. Inspection.Replace the lining with faced lining, or move attenuation to dedicated attenuators.
Grease in a kitchen extract duct beyond the hoodFire risk from grease. Deposit thickness against the asset’s market (Thresholds by market).Clean the full duct to the specification, adding access panels where needed.

Balance, flexible duct and noise

What you seeLikely cause, and what confirms itNext step
Zones short of air after a fit-outLoss of balance or kinked flex. Airflow measurement.Rebalance, relocate diffusers, and replace kinked flex with short, straight runs.
Noise and draughts at diffusers after a fit-outAirflow redistributed by the new layout. Airflow at each diffuser against design.Rebalance the system, and replace kinked or crushed flexible duct.

Heat Rejection Plant

Legionella, stagnation and drift

What you seeLikely cause, and what confirms itNext step
High bacterial countsTreatment failure, dead legs, stagnation. Records; system inspection; counts against the action levels for the asset’s market (Thresholds by market).Disinfect and resample; restore treatment and remove dead legs.
Drift visible from the tower, or a tower close to air intakes or windowsAerosol reaching people. Drift eliminator condition; distances to intakes, windows and public areas.Replace or refit eliminators, and review siting with the risk assessment.

Corrosion, scale, fill and mechanicals

What you seeLikely cause, and what confirms itNext step
Rising condenser approach on the chillersScaled or fouled tower and tubes, or tower capacity lost. Tower inspection; water treatment records.Clean the tower and tubes, and check the tower's capacity.
White powder on galvanised surfacesWhite rust from unbalanced water. Water chemistry.Rebalance the water treatment.
Fill sagging or collapsedBiofouling and deposits. Visual; fill weight.Replace the fill, and correct the water treatment.
Standby cell or tower left idle for weeksStagnant water and biofilm. Operating records; water treatment in the idle cell.Run or drain idle cells, and disinfect before returning them to service.

Hot air recirculation

What you seeLikely cause, and what confirms itNext step
Head pressure high on hot days, air-cooled plantHot air recirculation or fouled coils. Temperature at coil inlet higher than ambient.Clean the coils, and remove the screens or walls that recirculate hot air.
Plant screens added around air-cooled condensersHot air trapped and recirculated. Coil inlet temperature compared with ambient.Open the screen, add baffles, or move the units.

Localised HVAC

Refrigerant, VRF and compressors

What you seeLikely cause, and what confirms itNext step
Unit regassed repeatedlyRefrigerant leak. Leak test; larger systems are also held to leak-rate triggers in some markets (Thresholds by market).Pressure test and repair the leak, rather than regassing.
Unit runs continuously and never reaches setpointUndersized, low refrigerant, or fouled coils. Load calculation; refrigerant pressures; coil condition.Check the charge, coils and sizing; repair or resize.
Unit starts and stops every few minutesOversized or controls fault. Load; thermostat location.Check the controls; replace oversized units at renewal.
Many units of the same age failing togetherEnd of life across the population. Installation dates; parts availability.Replace the units as one programme, or consolidate them into VRF or a central system.

Outdoor units, coils and electronics

What you seeLikely cause, and what confirms itNext step
Capacity loss on hot daysCoil corrosion or hot air recirculation. Coil condition; siting.Clean the coils or replace them with coated coils, and clear any recirculation.
Unit dead after a stormElectronics failure. Error codes; board replacement availability.Repair the board, or replace an older unit.

Ducted systems and condensate

What you seeLikely cause, and what confirms itNext step
Water stains below indoor unitBlocked drain or failed pump. Drain inspection.Clear the drain or replace the condensate pump.
Ducted system weak in some roomsDisconnected or kinked flexible duct. Roof space inspection.Reconnect and straighten the flexible ducts.

Rooftop units, evaporative coolers and other systems

What you seeLikely cause, and what confirms itNext step
Carbon monoxide alarm near a rooftop unit supplyCracked heat exchanger. Combustion inspection.Shut the unit down; replace the heat exchanger or the unit.

Terminal Units

Fan coils and induction units

What you seeLikely cause, and what confirms itNext step
Ceiling stains below fan coilsBlocked or overflowing condensate drain. Drain pan inspection.Clear the drain, fix the falls and traps, and fit overflow switches above sensitive areas.
Fan coil filters clogged or missingMaintenance lapsed. Filter condition and dates on a sample of units.Restore filter changes on a schedule, and clean coils and pans.

VAV boxes and controls

What you seeLikely cause, and what confirms itNext step
Zone too hot, VAV box at full openBox undersized for the load, or upstream supply starved. Airflow measurement; load change.Check the upstream supply and the box sizing, and rebalance.
Zone too cold, VAV box at minimumMinimum airflow too high or reheat failed. Settings; reheat valve.Lower the minimum, or repair the reheat.
Heating and cooling at the same timeReheat valve stuck or controls fighting. BMS trends.Free the reheat valve, and recommission the sequences.
Many zones in manual overrideControls problems worked around. BMS point list.Fix the faults behind the overrides, then recommission.
Stuffy meeting rooms with VAV boxes at minimumOutside air short when the box turns down. Airflow and carbon dioxide in the room against the asset’s market (Thresholds by market).Reset minimum airflows for ventilation, or add demand-controlled ventilation.

Chilled beams

What you seeLikely cause, and what confirms itNext step
Dripping from chilled beamsChilled water below room dew point. Water temperature; humidity; dew point control.Add dew point control and condensation sensors.

Ventilation Systems

Car park ventilation

What you seeLikely cause, and what confirms itNext step
Car park fans never runCO sensors failed or disabled. Calibration records; sensor test.Replace and calibrate the CO sensors, and restore automatic control.
Car park fans always runSensors failed safe, or controls overridden. BMS; sensor test.Replace failed sensors and remove overrides.
Exhaust fumes lingering at car park pay stations or lift lobbiesCarbon monoxide reaching people. Readings at occupied points against the asset’s market (Thresholds by market).Test sensors and fan staging, and add extract or separation at occupied points.

Kitchen exhaust

What you seeLikely cause, and what confirms itNext step
Grease visible in ducts beyond the hoodCleaning frequency or extent inadequate. Cleaning records; inspection.Clean the full system, add access panels, and set the frequency to the cooking volume.

Fume cupboards

What you seeLikely cause, and what confirms itNext step
Fume cupboard alarms silencedLow face velocity. Face velocity test against the asset’s market (Thresholds by market).Restore the alarm; test face velocity, and repair the fans and ductwork.

Make-up air, re-entry, toilet exhaust and MVHR

What you seeLikely cause, and what confirms itNext step
Mould in bathrooms and roof spacesExhaust failed or discharging into voids. Fan and duct inspection.Reconnect the ducts, replace the fans, and extend discharges outside.
Odour in occupied areasExhaust re-entry or negative pressure. Discharge locations; pressure test.Move the discharge away from intakes, or rebalance the make-up air.
Flue spillage from appliancesNegative pressure from exhaust. Combustion and pressure test.Stop using the appliance; add or rebalance make-up air.