The typical service life of every component the Technical Library covers, in one place: 732 components across 103 elements and spaces, each with what shortens or extends it. Each element’s name opens its own page, where the figures sit with how it fails and what fixes it.

Substructure

Basement, Cellars & Retaining Walls

Reinforced concrete basement walls last the life of the building, and block or concrete retaining walls fifty years and more, but timber sleeper walls last only ten to twenty-five. The drains behind a wall last fifteen to thirty years, and their failure is behind much of what goes wrong.

ComponentTypical lifeWhat moves it
Reinforced concrete wallsLife of the buildingCracking; reinforcement corrosion
Applied tanking membranes20 to 40 yearsMovement; installation quality
Drained cavity membranes and pumpsMembranes 30 years and more; pumps 10 to 15Pump maintenance
Timber sleeper retaining walls10 to 25 yearsTreatment; drainage; soil contact
Blockwork and concrete retaining walls50 years and moreDrainage; reinforcement
Ground anchors25 to 50 yearsCorrosion protection
Agricultural drains behind walls15 to 30 yearsSilting; roots

Foundations

Concrete footings and piles last the life of the building, and timber piles last indefinitely while they stay below the water table; timber stumps last thirty to sixty years. What shortens a foundation's life is usually something around it: a tree, a leaking drain, or falling groundwater.

ComponentTypical lifeWhat moves it
Concrete footings and pilesLife of the buildingSoil movement; sulfates; construction quality
Timber piles below the water tableIndefinite while saturatedExposure when groundwater falls
Timber stumps30 to 60 yearsMoisture, termites, species, treatment
Concrete stumps50 years and moreReinforcement corrosion; lean
UnderpinningLife of the building if the cause is addressedRecurrence of the original cause

Slab on Ground

A slab lasts the life of the building, but its working surface does not: industrial joints and arrises last ten to twenty-five years, hardeners and coatings five to fifteen, and joint sealants five to ten. In a warehouse, the joints and the flatness decide when work is due.

ComponentTypical lifeWhat moves it
Concrete slabLife of the buildingGround movement; load; moisture
Industrial joints and arrises10 to 25 yearsWheel traffic; joint design
Joint sealants and fillers5 to 10 yearsTraffic; movement
Vapour barrierLife of the slab if intactDamage at construction
Floor hardeners and coatings5 to 15 yearsTraffic; chemicals

Sub-floor & Crawlspace

Bearers and joists last sixty to a hundred years if kept dry, but timber stumps last thirty to sixty, chemical termite barriers five to ten, and vapour barriers twenty to thirty. A sub-floor's life depends almost entirely on keeping it dry, ventilated and inspectable.

ComponentTypical lifeWhat moves it
Timber stumps30 to 60 yearsMoisture; termites; treatment
Bearers and joists60 to 100 years if dryVentilation; leaks; pests
Ant caps and termite barriers20 to 50 years; chemical barriers 5 to 10Bridging; disturbance
Vapour barriers20 to 30 yearsDamage; coverage
Sub-floor vents and air bricksLife of the building if kept clearBlockage
Crawlspace dehumidifiers8 to 12 yearsRun hours

Superstructure

Load-Bearing Masonry

Solid brick and stone walls last centuries if kept dry and restrained, and lime mortar fifty to a hundred years between repointing; timber lintels last fifty to a hundred and fifty years and steel lintels forty to eighty. What cuts a wall's life short is usually an alteration, or the loss of the floors and roof that hold it in place.

ElementTypical lifeWhat moves it
Solid brick and stone wallsCenturies if dry and restrainedWater; alterations; foundation movement
Lime mortar joints50 to 100 yearsExposure; hard repointing
Timber lintels and bond timbers50 to 150 yearsDecay; insects
Steel lintels40 to 80 yearsCorrosion
Brick archesLife of the buildingSpreading; abutment movement
Wall restraint straps and ties50 years and moreCorrosion

Structural Core

Cores, shear walls and bracing last the life of the building if they are protected and left intact. What shortens their life is rarely wear: it is the accumulated openings, removed bracing and corroded connections that steadily reduce what the lateral system can resist.

ElementTypical lifeWhat moves it
Concrete cores and shear wallsLife of the buildingAlterations; durability
Steel bracing and connectionsLife of the building if protectedCorrosion; removal
Timber bracing panelsLife of the building if keptRenovations; decay
Seismic retrofit elementsLife of the buildingMaintenance; damage in earthquakes

Structural Frame

A reinforced concrete or protected steel frame lasts the life of the building, often a hundred years and more, but its protection does not: coatings and membranes on concrete last ten to twenty years, exposed steel twenty-five to fifty between recoats, and car park decks thirty to sixty before major repair.

ElementTypical lifeWhat moves it
Reinforced concrete frameLife of the building, often 100 years and moreCover; carbonation; chlorides; water
Car park decks and ramps30 to 60 years before major repairChlorides; drainage; protection coatings
Structural steel frame, protectedLife of the buildingCoating and fire protection; water
Exposed steel25 to 50 years between major recoatingCorrosivity of the environment
Timber and mass timber framesLife of the building if dryMoisture; connections; fire protection
Protective coatings and membranes on concrete10 to 20 yearsTraffic; UV; product

Upper Floor Slabs & Structures

Concrete, post-tensioned and precast floors last the life of the building if their tendons and reinforcement stay protected, and dry timber joists eighty to a hundred and fifty years. Composite decking lasts forty to eighty years, and screeds and toppings twenty to fifty.

ElementTypical lifeWhat moves it
Concrete floorsLife of the buildingWater; alterations; overload
Post-tensioned slabsLife of the building if tendons protectedWater at anchorages; alterations
Hollowcore planksLife of the buildingBearings; cutting
Composite decking40 to 80 yearsCorrosion where wet
Timber joists80 to 150 years if dryDecay; notching; insects
Floor screeds and toppings20 to 50 yearsCracking; debonding

Façades

Architectural & Decorative Features

Natural stone lasts one to three hundred years and terracotta eighty to a hundred and twenty, but the iron cramps and anchors inside them last fifty to a hundred before they jack the stone apart, and lead weatherings and lime joints need renewing far sooner.

ComponentTypical lifeWhat moves it
Natural stone100 to 300 yearsStone type and bedding; pollution; salts; water on top surfaces
Terracotta and faience80 to 120 years and moreGlaze integrity; anchor condition; joint maintenance
Iron cramps and anchors50 to 100 years before they jack the stoneWater at the fixing
Render ornament40 to 80 yearsBond; armature corrosion; water from above
Lead and copper weatherings50 to 100 yearsFixing and detailing; theft in some areas
Lime mortar joints in ornament30 to 60 yearsExposure; top surfaces

Building Maintenance Units (BMU)

A building maintenance unit's structure, carriage and track last twenty-five to forty years and its cradle twenty to thirty, while controls, hoists and brakes last fifteen to twenty-five, and wire ropes are replaced on condition, typically every five to ten. The controls usually decide the mid-life investment.

ComponentTypical lifeWhat moves it
BMU structure, carriage and track25 to 40 yearsCoastal exposure; maintenance; fatigue at highly stressed welds
Slewing ring bearing20 to 30 yearsLubrication; use
Controls and electrical systems15 to 25 yearsObsolescence of parts; water ingress
Hoists and brakes15 to 25 yearsUse; maintenance
Wire ropesReplaced on condition, typically 5 to 10 yearsUse, corrosion, damage; discard criteria
Cradle20 to 30 yearsCorrosion; impact damage
Davit arms and sockets25 to 40 yearsWater in sockets; coating
Rope access anchors20 to 30 yearsCorrosion; roof works disturbing fixings; recertification

Canopies & Awnings

A steel awning frame lasts forty to seventy years, but its tie rods, fittings and anchorages in masonry last thirty to sixty, roof sheeting and gutters twenty to forty, and fabric eight to fifteen. The anchorages decide an awning's strength, and they are hidden in the wall.

ComponentTypical lifeWhat moves it
Steel awning frame40 to 70 yearsPaint cycle; water at connections
Tie rods, turnbuckles and clevises30 to 60 yearsCorrosion at threads and where rods enter the wall
Anchorages in masonry30 to 60 yearsWater reaching the anchorage; masonry condition
Roof sheeting and box gutters20 to 40 yearsMaintenance of gutters; coastal exposure
Soffit linings (pressed metal, fibre cement, timber)20 to 50 yearsWater from above; hazardous materials in older linings
Glass canopy fittings25 to 40 yearsStainless grade; sealant at fittings
Fabric8 to 15 yearsUV; wind damage

Cladding & Wall Systems

Cladding lives span a wide range: precast panels last the life of the building and stone fifty to a hundred years, while EIFS and render on sheet last twenty to thirty, and face-sealed joint sealants ten to twenty. Carbon steel fixings, hidden behind the face, last thirty to sixty years.

ComponentTypical lifeWhat moves it
Precast concrete panelLife of the buildingCover to reinforcement, carbonation, chloride exposure
Precast joint sealant (face-sealed)10 to 20 yearsExposure, joint design; see Sealants and Joints
Stone cladding50 to 100 yearsFixing material; thin marble bows; stone type
Carbon steel fixings and brackets30 to 60 yearsMoisture at the fixing, coastal exposure
Stainless steel and aluminium fixingsLife of the buildingDissimilar metal contact, crevice corrosion in marine air
ACP and solid aluminium panel finish20 to 35 yearsCoating type, UV, coastal exposure
EIFS and render on sheet20 to 30 yearsDrained or face-sealed, impact, detailing at openings
Insulated sandwich panel25 to 40 yearsCoating on the skins, cut-edge corrosion, core moisture
Timber weatherboards30 to 60 years with a maintained paint cyclePaint cycle, ground clearance, end grain sealing
Fibre cement weatherboards and sheet40 to 60 yearsPaint cycle, fixings, movement at joints

External Coating Systems

Coatings are short-lived by design: paint on timber lasts five to ten years, acrylic on masonry and render eight to fifteen, and protective coatings on steel ten to twenty-five to first major maintenance. Render itself lasts thirty to sixty years, so most coating work is a recurring cycle.

CoatingTypical lifeWhat moves it
Acrylic on masonry and render8 to 15 yearsExposure; preparation; colour (dark colours age faster)
Paint on timber5 to 10 yearsExposure; end grain sealing; timber movement
Texture and elastomeric coatings10 to 20 yearsFilm thickness; substrate movement
Anti-carbonation coatings10 to 20 yearsProduct; film thickness; UV
Mineral paints and limewash10 to 20 years (limewash 3 to 7 years)Exposure; substrate
Render30 to 60 yearsBond to substrate; cracking; water from above
Protective coatings on steel10 to 25 years to first major maintenanceCorrosivity of the site; system specification

Glazing Systems

Glazing systems outlast their seals: aluminium framing lasts forty to sixty years and steel windows sixty and more, but wet seals last ten to twenty years, gaskets and insulating glass units twenty to thirty, and hardware ten to twenty-five. Most glazing work is renewing the parts that age inside a sound frame.

ComponentTypical lifeWhat moves it
Aluminium framing40 to 60 yearsAnodising or powder coat condition; coastal exposure; thermal breaks
Steel windows60 years and more with maintenancePaint cycle; rust jacking at glass and in masonry
Timber windows30 to 60 yearsPaint cycle; sill decay
uPVC windows25 to 35 yearsUV, hardware
IGU edge seal20 to 30 yearsWater standing in the glazing rebate; sealant quality; UV on exposed seals
EPDM gaskets20 to 30 yearsUV; shrinkage at corners
Wet perimeter and cap seals10 to 20 yearsExposure; joint design
Structural silicone25 years and moreOriginal adhesion and cure; never assumed without testing
Hardware: hinges, stays, rollers, locks10 to 25 yearsUse; coastal corrosion

Masonry/Brickwork

Fired clay brick lasts a hundred to a hundred and fifty years and more, but what holds it in place does not: galvanised ties from before about 1980 last thirty to sixty years, and as little as fifteen in marine exposure, while galvanised lintels and shelf angles last forty to eighty.

ComponentTypical lifeWhat moves it
Fired clay brick100 to 150 years and moreShortened by salt crystallisation, frost and hard cement pointing
Lime mortar joints50 to 100 years sheltered; 30 to 50 years exposedExposure, roof drainage, rising damp
Cement mortar joints40 to 70 yearsCracking at movement rather than erosion; sulfate attack where wet
Galvanised mild-steel ties (before about 1980)30 to 60 years; as little as 15 to 25 years in marine exposure or black ash mortarZinc consumed once the mortar carbonates and stays damp
Stainless steel tiesLife of the buildingWorkmanship: omitted, misplaced or bridged ties
Galvanised steel lintels and shelf angles40 to 80 yearsCoastal exposure, water held behind them, missing cavity trays
Bitumen or polymer damp-proof course50 years and moreBridging by raised ground, paving, render or garden beds, rather than material failure
Injected chemical damp-proof course20 to 30 yearsProduct, installation and salt loading

Sealants & Joints

Sealants are among the shortest-lived parts of a façade: silicone lasts fifteen to twenty-five years on well-designed joints, polyurethane eight to fifteen, and acrylic five to ten in exposed positions. Most surviving polysulphide is past its life, so an older façade with original joints is usually due.

SealantTypical lifeWhat moves it
Silicone on well-designed joints15 to 25 yearsJoint design; surface preparation; exposure
Polyurethane8 to 15 yearsUV exposure; joint movement
Hybrid polymer10 to 20 yearsProduct grade; exposure
Polysulphide15 to 25 years originally; most surviving examples are past lifeAge-hardening
Acrylic5 to 10 years in exposed positionsNot a façade movement sealant
Preformed compression seals15 to 25 yearsCompression set; UV

Verandahs, Balconies & Balustrades

A concrete balcony lasts fifty to eighty years and more, but its membrane lasts fifteen to twenty-five, steel balustrades twenty-five to forty, and a timber deck structure only fifteen to thirty. Water reaching the reinforcement, the ledger or the post bases is what cuts these lives short.

ComponentTypical lifeWhat moves it
Concrete cantilever slab50 to 80 years and moreCover to top steel; waterproofing over it; chloride exposure
Steel balcony frames and brackets40 to 60 yearsCoating cycle; coastal exposure; water at connections
Timber deck structure15 to 30 yearsTimber species and treatment; ground clearance; fastener corrosion
Membrane under tiles15 to 25 yearsFalls, threshold height, outlets
Tiles and bedding20 to 30 yearsMembrane condition; movement joints
Steel balustrades25 to 40 yearsPaint or galvanising; post-base detail
Aluminium balustrades30 to 50 yearsFinish; fixings; dissimilar metals
Glass balustrade fittings and glass25 to 40 yearsClamp and spigot corrosion; glass type; edge damage

Roofs & Rainwater Goods

Chimney Stacks & Flues

A chimney's parts wear at very different rates. The masonry stack can last a century, while flaunching, pointing and stainless liners need renewing within decades, and a liner suited to one appliance can fail quickly under the next.

ComponentTypical lifeWhat moves it
Masonry stack80 to 120 yearsExposure on all faces; flue gases; frost
Flaunching and pointing20 to 40 yearsExposure
Lead flashings50 to 80 yearsFixing in chases
Clay liners50 to 80 yearsChimney fires; thermal shock
Stainless liners15 to 30 yearsFuel type; condensate; grade
Twin-wall flues20 to 30 yearsFuel; installation
Pumice and cast-in-place liners50 years and moreChimney fires; installation quality
Pots, cowls and caps40 to 80 years; metal cowls 15 to 25Frost; fixing in the flaunching; corrosion
Commercial kitchen exhaust ducts20 to 30 years with cleaningGrease build-up; access; fire history
Steel boiler and generator stacks20 to 40 yearsInternal acid corrosion; insulation and cladding; support

Insulation

Insulation rarely wears out; it stops working. Bulk batts can last fifty years if dry and undisturbed, but gaps, wetting, dust and vermin cut their performance long before the material itself fails.

InsulationTypical lifeWhat moves it
Bulk batts and blankets, dry and undisturbed30 to 50 yearsCompression, wetting, vermin
Loose fill20 to 40 yearsSettlement; displacement
Rigid boards in warm roofs25 to 50 yearsWater from leaks
Reflective foil20 to 40 yearsDust on the reflective face; damage
Spray foam30 years and moreAdhesion; shrinkage; what it hides
Insulated sandwich panels25 to 40 yearsJoint seals; facing corrosion; damage; condensation in chilled spaces
Extruded polystyrene in inverted roofs30 years and moreWater absorption over time; displacement
Vapour-permeable sarking and underlaysLife of the roof covering if undamagedTearing by trades; UV before the covering went on

Plant Screens & Parapets

Parapets and screens wear at very different rates. Masonry parapets last sixty to a hundred years and copings forty to eighty, while metal cappings, screen framing and louvres need renewing within twenty to forty.

ComponentTypical lifeWhat moves it
Masonry parapet60 to 100 yearsTwo-sided exposure; damp-proof course under coping
Stone and concrete copings40 to 80 yearsJoints; fixings
Metal cappings20 to 40 yearsCoastal exposure; fixings
Plant screen framing25 to 40 yearsCoatings; fixings through the membrane
Louvres and cladding on screens20 to 30 yearsFixings; wind
Terracotta and cast stone ornamentCentury material; iron cramps and dowels 50 to 100 yearsCramp corrosion; open joints; frost
Lead and zinc cappings40 to 80 yearsFixing; thermal movement; theft of lead
Acoustic screen panels20 to 30 yearsPanel weight on fixings; wind; vibration

Rainwater Systems

Rainwater goods range from uPVC eaves gutters, lasting twenty-five to forty years, to copper and lead, lasting fifty years and more, with coated steel box gutters at the short end. Material matters, but so does how the system is kept clear.

ComponentTypical lifeWhat moves it
Zinc-aluminium coated steel eaves gutters20 to 30 yearsCleaning regime; leaf litter; coastal exposure; ponding at joints
Galvanised or coated steel box gutters15 to 30 yearsFalls; water standing; foot traffic; debris at sumps
Stainless steel box gutters40 years and moreWeld quality at joints and sumps; chlorides; contact with mild steel swarf
Lead-lined box and parapet gutters50 to 80 yearsBay length and fixing; underside condensation; theft
Cast iron gutters and downpipes100 years and more with paintingPaint cycle; joint failure; frost; impact
Aluminium gutters30 to 50 yearsContact with copper or steel; coastal exposure
Copper gutters50 to 100 yearsThickness; joints; theft
uPVC eaves gutters and downpipes25 to 40 yearsUV embrittlement; joint seals; impact
Internal stacks and outlets30 to 50 yearsJoint type; outlet clamping rings; movement in tall buildings
Siphonic outlets and pipework30 to 50 years for pipework; outlets need regular maintenanceBlockage; air baffles damaged; changes to the roof
Asbestos cement gutters and downpipesPast their life on most buildingsBrittleness; impact; licensed removal when replaced

Roof Coverings

Life is a property of each zone of a roof, not of the roof as a whole. The bottom metre of sheet above the gutter, the slope facing the prevailing weather or the sea, the area under a tree, and the bays below plant or a copper flue all reach the end of their life first; a roof is usually renewed when its worst zones fail, while the rest still has years left.

CoveringTypical lifeWhat moves it
Zinc-aluminium coated steel, benign inland40 years and moreCoastal exposure halves it; industrial air; ponding at laps
Coated steel within about a kilometre of surf15 to 25 yearsUnwashed areas under eaves and laps corrode first
Galvanised iron30 to 50 yearsZinc thickness; exposure
Asbestos cement sheet40 to 60 years before it weathers to fibreExposure; lichen; foot traffic
Concrete tiles50 years and more; bedding and pointing 20 to 30Surface erosion; frost
Terracotta tiles80 years and more; bedding and pointing 20 to 30Frost; poor-quality batches
Natural slate80 to 150 years; nails 50 to 100Slate quality; nail material
Fibre cement slate25 to 40 yearsProduct generation
Asphalt shingles15 to 30 yearsHeat, UV, hail, wind
Lead80 to 100 years when bays are sized correctlyBay size, fixing, underside condensation
Copper70 to 100 yearsThickness; acid run-off
Zinc40 to 80 yearsUnderside ventilation
Standing-seam steel, unpainted zinc-aluminium coated60 years and moreSealant and fixing renewal within that life; debris; no inspection Building Enclosure, reporting the Metal Construction Association

Roof Safety Systems

Roof safety systems last decades, but their certification lasts a year. Stainless anchors and static lines last twenty to thirty years and fixed guardrails up to forty, while an energy absorber is replaced after any deployment, and a system out of inspection cannot be used however sound it looks.

ComponentTypical lifeWhat moves it
Stainless anchors and static lines20 to 30 yearsFixing substrate; coastal exposure; certification
Galvanised anchors15 to 25 yearsCoastal exposure
Energy absorbersReplace after any deployment; otherwise with the systemShock loading
Fixed guardrails25 to 40 yearsCoatings; fixings through the roof
Freestanding guardrails20 to 30 yearsCounterweight and feet condition; movement
Aluminium walkways25 to 40 yearsSupports; slip resistance
Fixed ladders25 to 40 yearsCorrosion of rungs and fixings
Deadweight anchors15 to 25 yearsMembrane condition beneath; roof slope; movement
Ladder safety systems (rail or cable)20 to 30 yearsCorrosion; carriers and sleeves wearing; certification
Roof hatches25 to 40 yearsSeals; hinges and stays; corrosion
Safety mesh under roof lightsLife of the roof coveringCorrosion of mesh and fixings; disturbed at re-roofing
Parapet-clamped and counterweighted edge protection20 to 30 yearsClamp fixings; parapet condition

Roof Structure

A dry, unaltered roof structure usually outlasts everything on it: timber framing eighty years and more, steel portal frames fifty to eighty. Its life is cut short by water, by alterations that cut or overload members, and by materials such as RAAC that were never designed to last.

StructureTypical lifeWhat moves it
Timber roof framing, dry80 to 120 years and moreLeaks, condensation, termites and borers
Nail-plated trussesLife of the building if dry and unalteredMoisture at plates; alterations
Steel portal frames50 to 80 yearsCoatings; corrosion at bases and eaves
Cold-formed purlins30 to 60 yearsCoating mass; condensation; coastal exposure; gutter leaks
Concrete roof slabs60 to 100 yearsMembrane maintenance; cover; chlorides
RAAC planksDesigned for 30 years and now past itMoisture; bearing length; cracking
Steel trusses with riveted or bolted connections80 to 100 years and more if kept dry and paintedCorrosion at bearings, gutters and connections
Glued laminated timberLife of the building if dryMoisture at bearings and exposed ends; adhesive in very old glulam
Timber and plywood flat roof decks30 to 60 yearsLeaks and condensation; ventilation

Skylights, Dormers & Glazed Atria

Roof lights are among the shortest-lived parts of a roof. Polycarbonate sheets last ten to twenty years and acrylic domes fifteen to twenty-five, against thirty to fifty for atrium framing, and every year in the sun makes translucent sheets more brittle and more fragile.

ComponentTypical lifeWhat moves it
Polycarbonate sheeting10 to 20 yearsUV protection grade; exposure
Fibreglass sheeting15 to 25 yearsResin and gel coat
Acrylic domes15 to 25 yearsUV; impact
Atrium framing30 to 50 yearsCoatings; drainage
Atrium seals and gaskets15 to 25 yearsUV; movement
Roof windows25 to 40 yearsFlashings; hardware
DormersWith the roof; cheeks and flashings 30 to 50 yearsCladding and flashings
Patent glazing bars50 to 80 years; seals and putty 15 to 25Corrosion of steel bars; paint; lead or putty seals
Laminated overhead glass30 years and moreInterlayer delamination at edges; seal failure
Automatic opening vents and smoke ventsMechanisms 15 to 25 yearsActuators, seals and controls; testing regime

Waterproofing Membranes

Membranes last fifteen to thirty years depending on type and protection, and liquid coatings less, but a membrane's life is decided at its details: upstands, outlets and penetrations fail long before the field wears out.

MembraneTypical lifeWhat moves it
Built-up roofing15 to 25 yearsSurfacing and maintenance; ponding
Modified bitumen, protected20 to 30 yearsBallast or paving above it
Modified bitumen, exposed15 to 20 yearsUV; foot traffic
Mastic asphalt, protected30 years and moreMovement; solar protection
TPO15 to 25 yearsProduct generation; seam quality
PVC15 to 25 yearsPlasticiser loss; compatibility
EPDM20 to 30 yearsSeam method; shrinkage
Liquid-applied coatings8 to 20 yearsFilm thickness; preparation; product
Inverted roof membranes (insulation and ballast above)30 years and moreProtected from UV and thermal shock; life set by details and drainage
Green roof and planter membranesLife of the planting build-up, if root resistantRoot barrier; drainage layer; access for repair

Internal Areas

Bathrooms & Wet Areas

A bathroom is refurbished as a whole every fifteen to twenty-five years, but its parts run on shorter clocks: silicone three to ten years, grout five to fifteen, screen seals three to seven. A well-installed membrane lasts the full cycle; one that was not can fail within months, and then it decides when the cycle really ends.

Component or qualityTypical lifeWhat moves it
Waterproofing membrane15 to 25 years if well installed; can fail within months if notInstallation quality; substrate movement
Grout5 to 15 years before cracking and stainingCleaning; movement
Silicone sealant at junctions3 to 10 yearsMould; movement; cleaning
Tapware and mixers10 to 20 yearsWater quality
Shower screens and seals10 to 20 years; seals 3 to 7Use; hardware
Exhaust fans10 to 15 yearsRun hours; dust
Bathroom refurbishment cycle15 to 25 yearsLeaks; wear; style

Commercial Kitchens

A commercial kitchen's fit-out lasts ten to fifteen years and its cooking equipment eight to fifteen, while hoods and cool room panels last fifteen to twenty-five. Menu and equipment changes usually end its fitness for purpose before anything wears out.

Component or qualityTypical lifeWhat moves it
Kitchen fit-out and finishes10 to 15 yearsUse; cleaning; operator changes
Exhaust hoods and filters15 to 25 years; filters cleaned weeklyGrease; cleaning
Exhaust fans10 to 15 yearsGrease; run hours
Cooking equipment8 to 15 yearsUse; maintenance
Cool room panels and refrigeration15 to 25 years; refrigeration 10 to 15Ice damage; refrigerant rules
Floors10 to 20 yearsTraffic; chemicals; water

Commercial Office Areas (Base-Build)

A tenant fit-out lasts seven to twelve years, usually a lease term, while base-building carpet lasts ten to fifteen, ceiling grids twenty to thirty and LED lighting fifteen to twenty. A floor's fitness for purpose is set as much by its market grade as by the condition of anything on it.

Component or qualityTypical lifeWhat moves it
Tenant fit-out7 to 12 years, usually a lease termLease events; tenant needs; workplace trends
Base-building carpet tiles10 to 15 yearsTraffic; quality; make-good practice
Suspended ceiling tiles and grid20 to 30 years; tiles sooner where damagedWater leaks; services works; appearance
Base-building lighting15 to 20 years for LED; fluorescent now obsoleteTechnology; energy rating
Terminal units and diffusers15 to 25 yearsAir conditioning page; controls
Base-building refurbishment cycle15 to 25 years for a major floor refurbishmentMarket grade; vacancy; energy targets
Market gradeDrifts down a grade over 15 to 25 years without investmentCompeting stock; rising expectations

Common Circulation Areas

Corridor carpet lasts eight to fifteen years and paint and wall coverings five to ten, while hard floors last fifteen to twenty-five and door hardware ten to fifteen. Corridors are usually refurbished every ten to twenty years.

Component or qualityTypical lifeWhat moves it
Corridor carpet8 to 15 yearsTraffic; quality; cleaning
Vinyl and hard floors15 to 25 yearsTraffic; maintenance
Paint and wall coverings5 to 10 yearsDamage; style
Fire and smoke door hardware10 to 15 yearsUse; abuse
Corridor refurbishment10 to 20 yearsWear; market
Lighting15 to 20 years for LEDTechnology

Common Internal Areas

Corridor carpet lasts eight to fifteen years, paint seven to twelve and CCTV seven to ten, while intercoms and access control last ten to fifteen and lobbies are refurbished every fifteen to twenty. Network shutdowns and collective decisions end their fitness for purpose as often as wear does.

Component or qualityTypical lifeWhat moves it
Corridor carpet8 to 15 yearsTraffic; moves
Paint and wall finishes7 to 12 yearsDamage from moves
Intercom and access control10 to 15 yearsTechnology; network shutdowns; vendor support
Lobby refurbishment15 to 20 yearsMarket; wear
Lighting15 to 20 years for LEDTechnology
CCTV7 to 10 yearsTechnology

Electrical & Communications Risers

A riser's structure lasts the life of the building and its cable trays thirty to fifty years, while communications cabling lasts fifteen to twenty-five and door hardware ten to twenty. Its fire stopping lasts only until the next contractor disturbs it, and its spare capacity until the next tenancy uses it up.

Component or qualityTypical lifeWhat moves it
Riser structure and doorsLife of the building; door hardware 10 to 20 yearsUse; alterations
Fire stoppingUntil next disturbedEvery new cable or pipe
Cable trays and support30 to 50 yearsOverloading
Communications cabling15 to 25 yearsTechnology
Spare capacityConsumed by each tenancy and upgradeDemand growth

Fireplaces

Wood heaters last fifteen to twenty-five years and gas heaters and log fires ten to twenty, while door seals and glass last five to ten and hearths and surrounds the life of the building. Changes around an appliance, such as fans, airtightness and new joinery, can make it unsafe long before it wears out.

ItemTypical lifeWhat moves it
Wood heaters15 to 25 yearsUse; firebox wear
Gas heaters and log fires10 to 20 yearsServicing
Hearths and surroundsLife of the buildingCracking; alterations
Door seals and glass5 to 10 yearsHeat

Flooring

Timber floors last thirty to fifty years with refinishing and tiles thirty to fifty, while vinyl lasts fifteen to twenty-five, laminate ten to twenty and carpet eight to fifteen. Moisture from below and poor substrates end more floors early than wear does.

TypeTypical lifeWhat moves it
Commercial carpet tiles10 to 15 yearsTraffic; quality
Residential carpet8 to 12 yearsUse; tenancy turnover
Vinyl15 to 25 yearsTraffic; moisture below
Timber30 to 50 years with refinishingMoisture; wear
Laminate10 to 20 yearsMoisture
Ceramic and stone tiles30 to 50 yearsMovement; installation

Integrated Building Systems

Interface hardware lasts ten to twenty years, integration software and protocols five to fifteen, and network equipment five to ten. The cause-and-effect matrix lasts only until a connected system changes, which is why integration is proven by testing after every change, not judged by its age.

ItemTypical lifeWhat moves it
Cause-and-effect matrixValid until any connected system changesUpgrades, fit-outs, modernisations
Interface hardware (relays, modules, gateways)10 to 20 yearsPanel and system replacement
Integration software and protocols5 to 15 yearsVendor support; security updates
Network equipment5 to 10 yearsVendor support; security
DocumentationOut of date at the first changeDiscipline of updating

Internal Doors & Hardware

Door leaves last twenty-five to fifty years and frames the life of the building, but their hardware turns over much faster: closers ten to fifteen years, locks and latches ten to twenty, hinges fifteen to thirty, and exit devices fifteen to twenty.

ComponentTypical lifeWhat moves it
Door leaves25 to 50 yearsUse; damage; moisture
FramesLife of the building if undamagedImpact; movement
Closers10 to 15 yearsCycles; adjustment
Hinges15 to 30 yearsDoor weight; cycles
Locks and latches10 to 20 yearsCycles; abuse
Exit devices15 to 20 yearsUse
Electronic locks10 to 15 yearsElectronics; vendor support
Seals5 to 15 yearsDamage; painting

Internal Stairwells

A stair's structure lasts the life of the building, while nosings last ten to twenty-five years, tread and landing finishes ten to twenty, door hardware ten to fifteen and paint seven to fifteen. Its fitness for purpose is mostly about escape: doors that close, a clear route, and light to see by.

Component or qualityTypical lifeWhat moves it
Stair structureLife of the buildingCorrosion of steel stairs; alterations
Nosings10 to 25 yearsTraffic; product
Floor finishes on treads and landings10 to 20 yearsTraffic; cleaning
Fire door hardware10 to 15 yearsUse; abuse
Paint and wall finishes7 to 15 yearsDamage; appearance
Stair lighting15 to 20 years for LEDTechnology

Internal Wall & Ceiling Finishes

Plasterboard lasts the life of the building if it stays dry and well fixed, and lath and plaster eighty to a hundred and twenty years, while suspended ceiling grids last twenty-five to forty years, their tiles fifteen to twenty-five, and paint five to ten. Water and age, not wear, bring ceilings down.

FinishTypical lifeWhat moves it
Paint5 to 10 yearsWear; moisture; style
PlasterboardLife of the building if dry and well fixedWater; movement; fixing
Lath and plaster80 to 120 yearsVibration; water; loss of key
Suspended ceiling tiles15 to 25 yearsWater; services works; appearance
Suspended ceiling grid25 to 40 yearsCorrosion; damage
Wall coverings10 to 15 yearsDamage; style

Kitchen

A residential kitchen is usually refurbished every fifteen to twenty-five years, often for style before it fails. Its working parts turn over faster: dishwashers eight to twelve years, cooktops, ovens and rangehoods ten to fifteen, and flexible hoses five to ten, which is why hose age matters more than how the kitchen looks.

Component or qualityTypical lifeWhat moves it
Kitchen refurbishment cycle15 to 25 yearsStyle; wear; leaks
Cabinetry15 to 25 yearsMoisture; hardware
Laminate benchtops10 to 20 yearsHeat; moisture at joints
Stone and engineered stone benchtops25 years and moreImpact; sealing
Cooktops and ovens10 to 15 yearsUse
Dishwashers8 to 12 yearsUse; water quality
Rangehoods10 to 15 yearsGrease; motors
Flexible hoses5 to 10 yearsBurst risk with age

Lift Cars & Machine Rooms

Car interior finishes last ten to twenty years and car flooring five to fifteen, while landing frames last fifteen to twenty-five and machine room cooling fifteen to twenty. Interiors date before they wear out, and are best renewed with the controls at modernisation.

Component or qualityTypical lifeWhat moves it
Car interior finishes10 to 20 yearsUse; goods carried in passenger lifts
Car flooring5 to 15 yearsTraffic; trolleys
Landing door frames and finishes15 to 25 yearsImpact; cleaning
Car ventilation fans and lighting10 to 15 yearsRun hours
Machine room ventilation and cooling15 to 20 yearsHeat load; maintenance

Loading Docks & Goods Handling

Roller shutters and dock doors last fifteen to twenty years, with springs and motors replaced sooner, levellers fifteen to twenty-five, and floor joints ten to twenty before major repair, while line marking lasts only two to five. Changes in the vehicles and volumes delivering often end a dock's fitness for purpose before wear does.

Component or qualityTypical lifeWhat moves it
Roller shutters and dock doors15 to 20 years; springs and motors soonerCycles; impact; maintenance
Dock levellers15 to 25 yearsLoads; impact
Dock floor joints and surfaces10 to 20 years before major repairWheel loads; impact
Line marking and signage2 to 5 yearsTraffic
Compactors and waste equipment10 to 15 yearsUse; maintenance
Bollards and guards10 to 20 yearsImpact

Lobbies & Atria

Atrium glazing seals and gaskets last fifteen to twenty-five years, smoke control equipment twenty to twenty-five and high-level lighting fifteen to twenty, while balustrades last thirty to fifty. Height makes every renewal expensive, so access usually decides when the work is done.

Component or qualityTypical lifeWhat moves it
Finishes refurbishment15 to 25 yearsMarket; wear
Atrium glazing seals and gaskets15 to 25 yearsUV; movement
Atrium glass25 to 40 yearsBreakage; coatings
Smoke control equipment20 to 25 yearsTesting; controls
High-level lighting15 to 20 yearsTechnology; access
Balustrades30 to 50 yearsFixings; code changes

Main Entrance & Reception Areas

An entrance's finishes, desk and lighting are usually renewed every ten to fifteen years, while automatic door operators and turnstiles last ten to fifteen, matting five to ten, and stone floors thirty to fifty with honing and sealing. Market expectations, not wear, usually end the cycle.

Component or qualityTypical lifeWhat moves it
Entrance refurbishment (finishes, desk, lighting)10 to 15 yearsMarket positioning; wear
Automatic door operators10 to 15 yearsCycles; maintenance; weather
Revolving doors20 to 30 years with overhaulUse; maintenance
Entrance matting5 to 10 yearsTraffic; cleaning
Stone and terrazzo floors30 to 50 years with honing and sealingTraffic; grit; cleaning
Turnstiles and access control10 to 15 yearsTechnology; vendor support
Reception joinery10 to 20 yearsUse; style

Maintenance Access Areas

Steel platforms, ladders and guardrails last twenty-five to forty years, walkway boards twenty to forty, and hatches twenty to thirty. Fitness for purpose changes whenever plant is added somewhere no one planned access to, which is the usual way these spaces fall short.

Component or qualityTypical lifeWhat moves it
Steel platforms and ladders25 to 40 yearsCorrosion; damage
Access hatches20 to 30 yearsHinges; seals; damage
Walkway boards in roof spaces20 to 40 yearsDecay; damage
Guardrails25 to 40 yearsFixings; corrosion
Fitness for current plant locationsChanges when plant is addedPlant added without access

Partitioning Systems

Plasterboard partitions last the life of the fit-out or longer, and glazed partitions, operable walls and toilet partitions fifteen to twenty-five years. Their fire and acoustic performance lasts only until the next penetration, which is why it is checked after every round of works.

TypeTypical lifeWhat moves it
Plasterboard partitionsLife of the fit-out or longerDamage; alterations
Glazed partitions15 to 25 yearsFit-out changes; hardware
Operable walls15 to 25 years with servicingUse; track wear
Toilet partitions15 to 25 yearsMoisture; abuse
Acoustic and fire performanceUntil next penetration or alterationServices works; fit-outs

Plant Rooms

A plant room's fabric lasts the life of the building, while ventilation fans and louvres last fifteen to twenty-five years, bunds and drainage twenty to thirty, and gas detection five to ten with annual calibration. What usually ends a plant room's fitness for purpose is the day its largest item needs replacing and cannot get out.

ProvisionTypical lifeWhat moves it
Room fabric and floorsLife of the buildingWater; chemicals; alterations
Ventilation fans and louvres15 to 25 yearsRun hours; corrosion
Refrigerant and gas detection5 to 10 years; sensors calibrated annuallySensor drift
Bunds and drainage20 to 30 yearsCorrosion; damage
Lifting beams and equipmentLife of the building with periodic inspectionCertification
Floor coatings5 to 15 yearsTraffic; spills

Public Amenities

Amenities are refurbished every fifteen to twenty years, while tapware and flush valves last ten to fifteen and membranes fifteen to twenty-five. Rising occupancy and rising expectations end their fitness for purpose as often as wear does.

Component or qualityTypical lifeWhat moves it
Amenities refurbishment15 to 20 yearsWear; market; leaks
Wet area membranes15 to 25 yearsInstallation; movement
Tapware and flush valves10 to 15 yearsWater quality; use
Toilet partitions15 to 25 yearsMoisture; damage
Exhaust fans10 to 15 yearsRun hours
End-of-trip lockers and fittings10 to 15 yearsUse

Residential Units/Guest Rooms

A unit's parts run on different clocks: paint five to ten years, carpet eight to twelve, appliances ten to fifteen, and kitchens and bathrooms fifteen to twenty-five. Hotels refresh soft goods every five to seven years, and rising rental and brand standards can end a unit's fitness for purpose without any single failure.

Component or qualityTypical lifeWhat moves it
Kitchen cabinetry and benchtops15 to 25 yearsUse; moisture; style
Appliances10 to 15 yearsUse
Bathroom refurbishment15 to 25 yearsWaterproofing; wear
Carpet8 to 12 yearsUse; tenancy turnover
Hard floors20 to 30 yearsWear; acoustics
Paint5 to 10 yearsTenancy turnover
Hotel soft goods5 to 7 yearsBrand standards
Hotel case goods and bathrooms10 to 15 yearsBrand standards

Retail Tenancies (Base-Build)

A retail fit-out lasts five to ten years and a shopfront fifteen to twenty-five, while base-building service provisions last twenty-five to forty and centres are refurbished every ten to fifteen. Tenant mix and trade usually end a tenancy's fitness for purpose before its fabric does.

Component or qualityTypical lifeWhat moves it
Tenant fit-out5 to 10 yearsLease term; brand refits
Shopfronts15 to 25 yearsDamage; centre refurbishment
Base-building service provisions25 to 40 yearsTenant mix changes
Demising walls and fire separationLife of the building if maintainedPenetrations by fit-outs
Centre or precinct refurbishment10 to 15 yearsCompeting centres; retail trends

Service Corridors

Floor coatings and paint in service corridors last five to ten years and wall protection ten to twenty, while fire and security doors last fifteen to twenty-five, with hardware replaced sooner. Operations, not age, wear these spaces out: every delivery and bin run takes something from them.

Component or qualityTypical lifeWhat moves it
Floor coatings5 to 10 yearsTraffic; spills; cleaning
Wall protection10 to 20 yearsImpact
Fire and security doors15 to 25 years; hardware soonerAbuse; traffic
Paint5 to 10 yearsDamage
Lighting15 to 20 years for LEDTechnology

Specialised Occupancy Areas

Laboratory fit-outs, fume cupboards and medical gas outlets last fifteen to twenty-five years and emergency showers fifteen to twenty, while nurse call systems last ten to fifteen and classrooms are refurbished every fifteen to twenty. A change in how the space is used ends its fitness for purpose more often than wear.

Component or qualityTypical lifeWhat moves it
Laboratory fit-out and fume cupboards15 to 25 yearsResearch needs; exhaust performance
Emergency showers and eyewash15 to 20 yearsTesting; water quality
Medical gas outlets and alarms15 to 25 yearsCompliance; clinical change
Nurse call systems10 to 15 yearsVendor support
Classroom refurbishment15 to 20 yearsPedagogy; technology
Lecture theatre AV7 to 10 yearsTechnology
Clinical finishes (sheet vinyl, wall protection)10 to 20 yearsCleaning regimes; damage

Specialist & Non-Standard Features

Pool and spa plant lasts eight to fifteen years, sauna heaters and steam generators ten to fifteen, cellar cooling eight to twelve, and smart home platforms only five to ten. The supplier often matters more than the age: a bespoke system ends when no one can repair it.

FeatureTypical lifeWhat moves it
Pool and spa plant8 to 15 yearsChemicals; use
Sauna heaters and steam generators10 to 15 yearsWater quality; use
Cellar cooling units8 to 12 yearsRun hours
Smart home platforms5 to 10 yearsVendor support
Aquarium systems10 to 15 yearsMaintenance

Storage & Archive Areas

Mobile shelving and storage cages last twenty to thirty years, chemical cabinets fifteen to twenty-five, and archive environmental control fifteen to twenty. A store's fitness for purpose changes whenever its contents do, which is why the survey starts with what is actually in it.

Component or qualityTypical lifeWhat moves it
Mobile shelving and compactus20 to 30 yearsLoad; track wear
Storage cages20 to 30 yearsDamage; corrosion in damp basements
Chemical storage cabinets15 to 25 yearsCorrosion; damage
Archive environmental control15 to 20 yearsEquipment life
Fitness for the stored contentsChanges whenever contents changeNew uses; denser storage

External Elements

Ancillary Structures

Ancillary structures last as long as their bases and fixings. Steel sheds and carports last decades and shade sail fabric about a decade, while timber posts set in the ground decay first where they meet it.

StructureTypical lifeWhat moves it
Steel sheds and carports25 to 40 yearsCoatings; coastal exposure; impact
Timber pergolas and structures15 to 30 yearsDecay at post bases; treatment; maintenance
Shade sail fabric8 to 12 yearsUV; tension; wind
Shade sail masts and fixings20 to 30 yearsCorrosion; footing design
Flagpoles20 to 30 yearsFatigue; corrosion at the base
Asbestos cement shedsPast life wherever weatheredWeathering; damage
Water feature equipment10 to 15 yearsWater quality; pumps

Fencing, Gates & Signage

Fences and walls last decades, but the parts that keep people safe do not: gate operators last ten to fifteen years and their safety devices five to ten. On any powered gate, the safety devices are the first thing to check.

ElementTypical lifeWhat moves it
Timber fences15 to 25 yearsPost decay; treatment
Steel and aluminium fences25 to 40 yearsCoatings; coastal exposure
Masonry boundary walls50 years and moreFoundations; roots; lean
Gate operators and controls10 to 15 yearsUse; weather; maintenance
Gate safety devices (photo-eyes, edges)5 to 10 yearsDamage; alignment; weather
Boom gates10 to 15 yearsUse; impact
Signs10 to 20 yearsUV fading; vandalism

Landscaping & Irrigation

Landscaping lasts as long as it is maintained. Trees can outlive the building, while irrigation controllers last around a decade and podium planter waterproofing twenty to thirty years, with the structure below at risk when it fails.

ElementTypical lifeWhat moves it
TreesDecades to centuriesSpecies; site; maintenance
Shrubs and planting5 to 20 yearsSpecies; care; water
Irrigation controllers8 to 12 yearsTechnology; weather
Irrigation pipework and emitters10 to 20 yearsUV; damage; water quality
Green wall systems10 to 20 years; plants soonerIrrigation; plant selection; maintenance
Podium planter waterproofing20 to 30 yearsRoot barriers; drainage

Pavements & Hardstand

A pavement has two lives: the surface, which needs resealing every seven to ten years, and the structure beneath, which lasts decades if the surface keeps the water out. Keeping water out decides which fails first.

ComponentTypical lifeWhat moves it
Asphalt wearing course15 to 20 years, with resealing at 7 to 10Traffic; sun; water
Asphalt pavement structure20 to 40 yearsBase condition; drainage; loads
Concrete pavement30 to 40 yearsJoints; subgrade; loads
Segmental pavers25 to 40 yearsBedding; edge restraint; traffic
Line marking2 to 5 yearsTraffic; product
Kerbs and edge restraints30 to 50 yearsImpact; settlement

Recreational Facilities

Recreation equipment wears quickly against the building around it. Play equipment lasts ten to twenty years and rubber surfacing seven to fifteen, while loose fill needs topping up every year, and the surfacing most often decides whether a playground is safe.

ElementTypical lifeWhat moves it
Playground equipment10 to 20 yearsUse; materials; weather
Impact-absorbing surfacingLoose fill topped up yearly; rubber 7 to 15 yearsWear; displacement
Tennis court surfaces7 to 15 years; resurfacing more oftenSurface type; cracking
Court fencing and nets15 to 25 years; nets 2 to 5Corrosion; damage
Gym equipment7 to 12 yearsUse; maintenance
Barbecues8 to 15 yearsUse; cleaning

Stormwater Drainage

Stormwater pipes and pits last fifty years and more; what fails first is the maintenance. Treatment media need replacing every one to five years and subsoil drains within decades, and blockage causes most failures long before the pipes wear out.

ElementTypical lifeWhat moves it
Concrete and PVC stormwater pipes50 years and moreRoots; ground movement; installation
Clay and older pipes50 to 80 yearsRoots; joint failure
Pit structures and grates30 to 50 yearsTraffic loads; corrosion
On-site detention tanks50 years and moreMaintenance; access
Treatment device media and filters1 to 5 yearsSediment load
Subsoil drains15 to 30 yearsSilting; roots

Mechanical Services

Air Handling Units (AHUs)

Indoor air handling units last twenty-five to thirty years and rooftop units fifteen to twenty-five, but their working parts turn over faster: motors fifteen to twenty years, humidifiers and damper actuators ten to fifteen, belts two to four. A sound casing can often be refurbished in place rather than replaced.

ComponentTypical lifeWhat moves it
AHU casing (indoor)25 to 30 yearsCondensation; drain pan leaks
AHU casing (rooftop)15 to 25 yearsWeather; coastal exposure; panel seals
Fans20 to 25 yearsMaintenance; balance
Fan motors (including EC motors)15 to 20 yearsRun hours; heat
Belts2 to 4 yearsTension; alignment
Cooling and heating coils15 to 25 yearsCleaning; water treatment; coastal air
Heat recovery wheels15 to 20 yearsSeals; drives
Humidifiers10 to 15 yearsWater quality
Damper actuators10 to 15 yearsUse; controls
FiltersMonths to a yearDust load; grade

Building Management & Control System (BMCS)

A BMS ages at different speeds: head end hardware lasts five to eight years and its software five to ten before a major upgrade, while plant controllers last fifteen to twenty and sensors ten to fifteen with calibration. Vendor support, not wear, usually ends its life.

ComponentTypical lifeWhat moves it
Head end software5 to 10 years before major upgradeOperating system and vendor support
Head end hardware5 to 8 yearsIT refresh
Plant controllers15 to 20 yearsVendor support; parts
Unitary controllers10 to 15 yearsVendor support
Sensors10 to 15 years with calibrationDrift; type
Actuators10 to 15 yearsUse
Network infrastructure10 to 15 yearsProtocol support

Central Cooling Plant

Water-cooled centrifugal chillers last twenty to thirty years and air-cooled machines fifteen to twenty, while pumps last fifteen to twenty-five and their starters and drives ten to twenty. Refrigerant rules often end a machine's useful life before wear does.

ComponentTypical lifeWhat moves it
Water-cooled centrifugal chiller20 to 30 yearsWater treatment; overhaul history; refrigerant
Water-cooled screw chiller20 to 25 yearsOil management; run hours
Air-cooled chiller15 to 20 yearsCondenser coil corrosion, especially near the coast
Absorption chiller20 to 25 yearsVacuum integrity; corrosion inhibitor
Primary pumps15 to 25 years; seals and bearings 5 to 10Run hours; alignment; water quality
Starters and variable speed drives10 to 20 yearsHeat and dust in the plant room; harmonics
Plant controls and chiller panels10 to 15 years before parts support endsManufacturer support
Chilled water pipework (steel)40 to 60 yearsWater treatment; external condensation and insulation

Central Heating Plant

Cast iron and steel shell boilers last twenty-five to thirty-five years and condensing boilers fifteen to twenty, as do burners, pumps and air-to-water heat pumps. Water treatment is the cheapest life extension available for every part of the system.

ComponentTypical lifeWhat moves it
Cast iron sectional boiler25 to 35 yearsThermal shock; water quality
Steel shell boiler25 to 30 yearsWater treatment; firing cycles
Condensing boiler15 to 20 yearsWater quality; heat exchanger material
Burners and gas trains15 to 20 yearsMaintenance; combustion tuning
Air-to-water heat pump15 to 20 yearsCoastal exposure; cycling; refrigerant
Primary pumps15 to 20 yearsRun hours; water quality
Pressurisation units and expansion vessels10 to 20 yearsDiaphragm life; pressure setting
Calorifiers20 to 25 yearsWater quality; temperature regime
Steel distribution pipework40 to 60 yearsOxygen ingress; water treatment
Radiators40 years and moreInternal corrosion from oxygenated water

Ductwork & Air Distribution

Galvanised ductwork lasts thirty to fifty years and more, but its insulation lasts twenty to thirty, its sealants and linings fifteen to twenty-five, and flexible duct fifteen to twenty. Fit-outs and fire damper testing usually decide the work long before the metal wears out.

ComponentTypical lifeWhat moves it
Galvanised ductwork30 to 50 years and moreMoisture; corrosive exhaust
Duct sealants and gaskets15 to 25 yearsTemperature; age
Flexible duct15 to 20 yearsDamage; UV in roof spaces
External insulation and vapour barrier20 to 30 yearsDamage; condensation
Internal lining15 to 25 yearsAir velocity; moisture
Grilles and diffusers20 to 30 yearsFit-out changes
Fire dampers20 to 30 years with testingCorrosion; obstruction; fusible link age

Heat Rejection Plant

Galvanised steel cooling towers last fifteen to twenty years, stainless or fibreglass twenty to thirty, and concrete thirty to forty, while fill and drift eliminators last ten to fifteen. Water treatment decides how long all of them actually last.

ComponentTypical lifeWhat moves it
Galvanised steel cooling tower15 to 20 yearsWater treatment; white rust; basin corrosion
Stainless or fibreglass cooling tower20 to 30 yearsUV on fibreglass; structural supports
Concrete tower30 to 40 yearsConcrete deterioration
Fill10 to 15 yearsFouling; collapse under weight of deposits
Drift eliminators10 to 15 yearsUV; damage; fouling
Fans, motors, gearboxes15 to 20 yearsVibration; lubrication
Dry coolers20 to 25 yearsCoil corrosion; fan motors
Air-cooled condenser coils15 to 20 years; 5 to 10 unprotected near the coastSalt air; coating

Localised HVAC

Split systems last ten to fifteen years, ducted reverse-cycle twelve to eighteen, and VRF and packaged rooftop units fifteen to twenty. Units installed together tend to fail together, so a building's local systems are best planned as a population rather than one by one.

EquipmentTypical lifeWhat moves it
Wall-mounted split10 to 15 yearsElectronics; coastal exposure
Ducted reverse-cycle12 to 18 yearsRun hours; roof space heat
VRF outdoor units15 to 20 yearsCompressor; coastal exposure
VRF indoor units and branch boxes15 to 20 yearsElectronics; fans
Packaged rooftop units15 to 20 yearsWeather; coil corrosion; heat exchanger
Air-source heat pumps15 to 20 yearsCycling; coastal exposure
Evaporative coolers10 to 15 yearsWater quality; pads; corrosion
Underfloor heating pipe in slab40 years and morePipe type; oxygen barrier
Underfloor electric mats20 to 30 yearsDamage at installation

Terminal Units

Fan coil units last fifteen to twenty years and VAV box casings twenty to thirty, but their motors, controllers and actuators last ten to fifteen. In most buildings it is the controls on the units, rather than the boxes themselves, that decide when work is due.

ComponentTypical lifeWhat moves it
Fan coil units15 to 20 yearsFan motors; coils; drain pans
FCU fan motors10 to 15 yearsRun hours
VAV box casing and damper20 to 30 yearsRarely limiting
VAV controllers and actuators10 to 15 yearsElectronics obsolescence
Airflow sensors10 to 20 years, with recalibrationDust fouling; drift
Chilled beams25 to 30 yearsCoil cleaning; condensation control
Induction units25 to 35 yearsMostly at end of life now
Control valves and actuators10 to 15 yearsWater quality; use

Ventilation Systems

Exhaust and car park jet fans last fifteen to twenty years and kitchen exhaust fans ten to fifteen, while carbon monoxide sensors last five to ten with calibration. Welded kitchen exhaust ductwork lasts twenty-five to forty years, if it is kept clean of grease.

ComponentTypical lifeWhat moves it
Exhaust fans (general)15 to 20 yearsRun hours; corrosion in wet exhaust
Car park jet fans15 to 20 yearsMoisture; exhaust contaminants
CO sensors5 to 10 years, with calibrationSensor technology; drift
Kitchen exhaust fans10 to 15 yearsGrease; heat
Kitchen exhaust ductwork (welded steel)25 to 40 yearsCleaning access; grease fires
Fume cupboards15 to 25 yearsChemicals; sash mechanisms; controls
MVHR units15 to 20 yearsFilter maintenance; fan motors

Electrical Services

Communications, Security & Specialist Systems

Network switches and comms equipment last five to ten years and IP cameras and recorders seven to ten, while copper structured cabling lasts fifteen to twenty-five and fibre backbones twenty-five and more. Network retirements, not wear, often set the deadline.

ComponentTypical lifeWhat moves it
Structured cabling (copper)15 to 25 yearsCategory standards; bandwidth needs
Fibre backbone25 years and morePhysical damage
Network switches and comms equipment5 to 10 yearsVendor support
IP CCTV cameras and recorders7 to 10 yearsTechnology; firmware support
Analogue CCTVAt end of lifeReplace
Access control controllers10 to 15 yearsVendor support
Intercoms10 to 15 yearsTechnology; line dependence
MATV amplifiers and distribution10 to 20 yearsStandards changes
Nurse call systems10 to 15 yearsVendor support

Emergency Lighting

Nickel-cadmium and nickel-metal hydride batteries last four to six years and lithium iron phosphate eight to ten, while LED emergency luminaires and exit signs last fifteen to twenty. The batteries decide most of the work, and they fail quietly until a full-duration test.

ComponentTypical lifeWhat moves it
Nickel-cadmium and nickel-metal hydride batteries4 to 6 yearsHeat in ceiling spaces; charging
Lithium iron phosphate batteries8 to 10 yearsHeat; battery management
LED emergency luminaires and exit signs15 to 20 yearsDriver and charger; heat
Fluorescent emergency fittings10 to 15 yearsLamp availability ending
Central battery systems15 to 20 years; batteries 5 to 10Battery room temperature
Monitoring panels and software10 to 15 yearsVendor support
Photoluminescent signs20 to 25 yearsFading; charging light levels

Emergency Power

A diesel generator set lasts twenty-five to thirty years, or by run hours, and transfer switches twenty to thirty, but starting batteries last three to five years and UPS batteries three to seven. Batteries are the first thing to check when a generator fails to start.

ComponentTypical lifeWhat moves it
Diesel generator set25 to 30 years (or by run hours)Maintenance; exercising under load
Starting batteries3 to 5 yearsHeat; charger condition
Automatic transfer switches20 to 30 yearsOperation; maintenance
Static UPS10 to 15 yearsHeat; capacitor and fan replacement
VRLA batteries3 to 7 yearsTemperature; cycling
Lithium batteries10 to 15 yearsTemperature; management system
Fuel tanks20 to 40 yearsCorrosion; water; bund integrity
Stored diesel fuel1 to 2 years without treatmentWater; microbial growth; oxidation

Lighting

LED luminaires last fifteen to twenty years and their drivers ten to fifteen, against twenty to twenty-five for fluorescent fittings, which the phase-out of mercury lamps is retiring sooner. Steel columns corrode at the ground line, out of sight, long before anyone notices.

ComponentTypical lifeWhat moves it
LED luminaires50,000 hours or more to 70 per cent output; 15 to 20 yearsHeat; driver quality
LED drivers10 to 15 yearsHeat; surges
Fluorescent fittings20 to 25 yearsBallasts; lamp supply ending
External luminaires15 to 20 yearsIngress protection; coastal exposure
Steel lighting columns25 to 40 yearsBase corrosion; impact
Aluminium columns30 to 50 yearsBase corrosion in salt and soil
Concrete columns30 to 50 yearsReinforcement corrosion

Lighting Control System

Sensors, controllers and gateways last ten to fifteen years and time clocks and contactors fifteen to twenty, while proprietary networked systems often last only eight to fifteen before support ends. Commissioning, not hardware, usually decides whether a system saves anything.

ComponentTypical lifeWhat moves it
Time clocks and contactors15 to 20 yearsContact wear; battery backup
Occupancy and daylight sensors10 to 15 yearsTechnology; damage; dirt
DALI controllers and gateways10 to 15 yearsVendor support
Proprietary networked systems8 to 15 yearsVendor support; software and app support
Wall controllers and scene plates15 to 20 yearsUse

Lightning Protection

Copper and aluminium conductors and air terminals last thirty to fifty years and earth electrodes twenty to forty, while test joints and clamps last twenty to thirty. Roof works and theft can break a system long before age does.

ComponentTypical lifeWhat moves it
Copper and aluminium conductors30 to 50 yearsFixings; theft; dissimilar metals; coastal exposure
Air terminals30 to 50 yearsFixings; damage
Earth electrodes20 to 40 yearsSoil corrosivity; excavation
Test joints and clamps20 to 30 yearsCorrosion; tampering
Surge protection devicesUntil they absorb enough surges; often 5 to 15 yearsLightning activity; switching surges

Main Electrical Supply

Main switchboards last thirty to forty years and transformers twenty-five to fifty, but their breakers reach the end of manufacturer support after twenty to twenty-five. Long before anything wears out, electrification and EV charging can make the supply too small.

ComponentTypical lifeWhat moves it
LV main switchboard30 to 40 yearsSwitchroom environment; loading; maintenance
Air and moulded case breakers20 to 25 years before support endsOperation and testing; manufacturer support
Oil-filled transformers30 to 50 yearsLoading; oil condition; cooling
Dry-type transformers25 to 35 yearsHeat; dust
HV switchgear30 to 40 yearsInsulation; type (oil, SF₆, vacuum)
Power factor correction capacitors10 to 15 yearsHarmonics; heat
Surge protection devicesUntil they absorb enough surges; check indicatorsSurge exposure
Incoming cablesLife of the buildingOverload; damage

Power Distribution

PVC wiring lasts forty to sixty years and distribution boards twenty-five to forty, while RCDs and RCBOs last fifteen to twenty-five. Rubber-insulated wiring is past its life wherever it is found.

ComponentTypical lifeWhat moves it
PVC wiring40 to 60 yearsHeat; overload; damage
Rubber-insulated wiringPast its life wherever foundReplace
Distribution boards25 to 40 yearsDevice support; alterations; environment
Busducts30 to 40 yearsJoint maintenance; loading
RCDs and RCBOs15 to 25 yearsTesting; surges
Socket outlets and switches20 to 30 yearsUse; loose terminals
Sub-meters15 to 25 yearsTechnology; communications

Solar Photovoltaic (PV) Systems

Modules last twenty-five to thirty years, losing about half a per cent of output a year, and their frames as long, but string and central inverters last only ten to fifteen. The roof beneath often needs replacing before the array does.

ComponentTypical lifeWhat moves it
Modules25 to 30 years, losing about half a per cent of output a yearQuality; heat; defects
String and central inverters10 to 15 yearsHeat; surges
Microinverters and optimisers15 to 25 yearsHeat on the roof
Mounting frames25 to 30 yearsCoastal exposure; fixings
DC connectors and isolators10 to 25 yearsInstallation quality; water ingress
Batteries10 to 15 yearsChemistry; cycling; heat

Fire Services

Automatic Sprinkler Systems

Sprinkler systems last a long time if the water inside them is managed: wet steel pipework fifty years and more, dry galvanised pipework twenty to forty, and heads sample tested after fifty years, or twenty for fast-response types. What ends a system's usefulness sooner is usually a change in what the building stores.

ComponentTypical lifeWhat moves it
Black steel wet pipework50 years and moreWater chemistry; microbiologically influenced corrosion
Galvanised dry pipework20 to 40 yearsWater left in pipes; condensation
CPVC pipework30 to 50 yearsChemical incompatibility
Standard sprinkler heads50 years, then sample testingEnvironment; corrosion; loading
Fast-response heads20 years, then sample testingEnvironment
Alarm and dry pipe valves25 to 40 years with internal inspectionWater quality; maintenance
Control valves30 years and moreExercising
Flow and tamper switches15 to 25 yearsElectrical components

Fire Detection & Alarm Systems

Detection systems last as long as their panels stay supported: fifteen to twenty years for a panel, ten to fifteen for detectors, ten for domestic smoke alarms, and three to five for standby batteries. A system can be fully compliant and still at the end of its life.

ComponentTypical lifeWhat moves it
Control and indicating panel15 to 20 years before manufacturer support endsVendor support; programming tools
Point smoke and heat detectors10 to 15 yearsContamination; environment; manufacturer advice
Domestic smoke alarms10 yearsBuilt-in end of life
Aspirating systems15 to 20 years; filters and fans soonerPipe condition; environment
Beam detectors10 to 15 yearsMounting stability
EWIS amplifiers and speakers15 to 20 yearsHeat; vendor support
Standby batteries3 to 5 yearsTemperature; charger
Fire-rated cablingLife of the buildingDamage; alterations

Fire Pumping Systems

A fire pump's casing and impeller last twenty-five to thirty-five years and its engine or motor twenty to thirty, while controllers last fifteen to twenty and starting batteries three to five. A pump that is never flow tested can lose performance for years without anyone noticing.

ComponentTypical lifeWhat moves it
Fire pumps (casing and impeller)25 to 35 yearsWater quality; run time; cavitation
Electric motors20 to 30 yearsRun time; damp
Diesel engines25 to 30 yearsExercise; maintenance
Controllers15 to 20 yearsVendor support
Jockey pumps10 to 15 yearsCycling
Starting batteries3 to 5 yearsTemperature; charger
Steel tanks20 to 30 yearsInternal corrosion; coatings
Concrete tanks40 years and moreJoints; leaks

Hydrant & Hose Reel Systems

Hydrant systems are long-lived: galvanised pipework thirty to fifty years, booster assemblies twenty-five to forty, and valves twenty to thirty, while hose reel hoses last ten to fifteen. A system can outlast its usefulness, though, when the building grows around it or access to it is lost.

ComponentTypical lifeWhat moves it
Hydrant valves and landing valves20 to 30 yearsOperation; corrosion; vandalism
Booster assemblies25 to 40 yearsDamage; corrosion; caps stolen
Galvanised pipework30 to 50 yearsInternal corrosion; MIC
Dry riser inlets and valves20 to 30 yearsVandalism; corrosion
Hose reel hoses10 to 15 yearsUV; abrasion
Hose reel units20 to 30 yearsCorrosion; damage

Passive Fire Protection

Passive fire protection lasts the life of the building if nobody breaches it. Masonry walls and floors, plasterboard walls and spray-applied protection all last as long as the building while intact, but penetration seals, fire doors and their hardware wear and are disturbed far sooner.

ElementTypical lifeWhat moves it
Masonry and concrete compartment walls and floorsLife of the buildingPenetrations; alterations
Plasterboard fire-resisting wallsLife of the building if intactDamage; services penetrations
Penetration seals20 to 30 years if undisturbedFurther works; product
Fire doors20 to 30 years with maintenanceUse; abuse; maintenance
Door closers and hardware10 to 15 yearsUse
Intumescent seals10 to 20 yearsPainting over; damage
Intumescent coatings on steel15 to 25 yearsDamage; moisture; overcoating
Spray-applied fire protectionLife of the building if undisturbedDamage; water

Portable Fire Equipment

Portable equipment is short-lived and easily overlooked: stored-pressure extinguishers last ten to twenty years with periodic pressure testing, fire blankets seven to ten, and hoses five to ten. Its condition is a quick guide to how fire safety is managed in the rest of the building.

EquipmentTypical lifeWhat moves it
Stored-pressure extinguishers10 to 20 years with periodic pressure testingCorrosion; damage; test results
Carbon dioxide extinguishers20 years and more with pressure testingCylinder testing
Hoses and horns5 to 10 yearsCracking; UV
Fire blankets7 to 10 yearsDamage; packaging
Signage and mounting10 to 20 yearsFading; damage

Smoke Management Systems

Smoke control equipment lasts fifteen to twenty-five years: fans twenty to twenty-five, and dampers, curtains, vent actuators and control panels fifteen to twenty. A system's working life can end sooner, though, when the building around it changes and the design no longer fits.

ComponentTypical lifeWhat moves it
Smoke exhaust and pressurisation fans20 to 25 yearsRarely run; motor and bearing condition
Smoke dampers and actuators15 to 20 yearsRarely operated; seize
Fire fan control panels15 to 20 yearsVendor support
Smoke curtains15 to 20 yearsFabric; motors; batteries
AOV actuators and controls15 to 20 yearsWeather; operation
Fire-rated cablingLife of the buildingDamage; alterations

Specialist Suppression Systems

Suppression systems last twenty to thirty years in their cylinders and valves, and fifteen to twenty in their panels, but regulation often ends an agent's life first: halon is already restricted, HFC agents fall under fluorinated gas rules, and PFAS foams are being withdrawn.

ComponentTypical lifeWhat moves it
Gas cylinders and valves20 to 30 years with periodic hydrostatic testingPressure testing intervals; corrosion
Detection and control panels15 to 20 yearsVendor support
Pre-action valves20 to 30 yearsMaintenance; water quality
Kitchen system cylinders and linksFusible links replaced at least annuallyGrease; heat
Foam concentrate10 to 20 yearsStorage; type; regulation
Water mist pumps and nozzles15 to 25 yearsWater quality; nozzle blockage

Hydraulic Services

Gas Services

Copper and polyethylene gas piping last fifty years and more and steel above ground forty to sixty, but buried steel lasts twenty to forty and regulators fifteen to twenty-five. In many buildings, electrification now decides the end of the gas system before wear does.

ComponentTypical lifeWhat moves it
Steel piping above ground40 to 60 yearsDamp; coating
Buried steel20 to 40 yearsSoil corrosivity; cathodic protection
Copper piping50 years and moreDamage
Polyethylene50 years and moreThird-party damage
Regulators15 to 25 yearsNetwork conditions; debris
Emergency shut-off valves15 to 25 yearsTesting
LPG tanks20 to 30 years with periodic inspectionCorrosion; certification

Hot & Warm Water Plant

Storage water heaters last eight to fifteen years and heat pump and continuous-flow heaters ten to fifteen, while calorifiers last twenty to twenty-five. Replacing a heater is routine; keeping the water hot enough, and safe at the tap, is the harder part.

ComponentTypical lifeWhat moves it
Storage water heaters8 to 15 yearsAnode replacement; water hardness; temperature
Heat pump water heaters10 to 15 yearsCompressor; coastal exposure
Solar collectors15 to 25 yearsFrost; overheating; seals
Continuous-flow heaters10 to 15 yearsScale; flow
Calorifiers20 to 25 yearsWater quality; inspection
Circulating pumps10 to 15 yearsRun hours; scale
Thermostatic mixing valves10 to 15 years with annual serviceScale; debris; maintenance
Copper hot water pipework40 to 60 yearsWater chemistry; velocity

Pumping Systems

Booster pumps last fifteen to twenty years, while pressure vessels, variable speed drives and submersible stormwater pumps last ten to fifteen and sewage pumps eight to fifteen. A pump's age matters less than whether anyone will know when it stops.

ComponentTypical lifeWhat moves it
Booster pumps15 to 20 yearsRun hours; water quality
Variable speed drives10 to 15 yearsHeat; surges
Pressure vessels10 to 15 yearsDiaphragm life; charge pressure
Submersible stormwater pumps10 to 15 yearsSilt and debris; run hours
Sewage pumps8 to 15 yearsRags and wipes; H2S corrosion
Float switches and level controls5 to 10 yearsFouling; tangling
Concrete pits30 to 50 yearsH2S attack in sewage pits
Control panels and alarms15 to 20 yearsDamp; vendor support

Sanitary & Drainage Systems

Cast iron stacks and drains last fifty to seventy-five years, clay drains fifty to a hundred if undisturbed, and PVC fifty and more, while pitch fibre drains are past their life wherever they are found. Tree roots and ground movement end many drains early.

ComponentTypical lifeWhat moves it
Cast iron stacks and drains50 to 75 yearsWater chemistry; hydrogen sulphide
Clay drains50 to 100 years if undisturbedTrees; ground movement
Pitch fibre drainsPast life wherever foundReplace
PVC drains50 years and moreGround movement; installation
Sanitary fixtures20 to 40 yearsUse; vandalism; style
Tapware and cisterns10 to 20 yearsWater quality; wear
Wet area membranes15 to 25 yearsInstallation; movement

Specialist Hydraulics

Concrete pool shells last thirty to fifty years, but their finishes last ten to twenty, filters ten to fifteen, and pumps and heaters less. Gates, outlet covers and chemical storage decide safety long before the shell decides the budget.

ComponentTypical lifeWhat moves it
Concrete pool shells30 to 50 yearsWaterproofing; ground movement; chemical balance
Pool surface finishes (render, tiles, membranes)10 to 20 yearsWater chemistry; maintenance
Pool filters10 to 15 years; media 5 to 10Backwashing; water quality
Pool pumps and heaters8 to 15 yearsChemicals; run hours
Chemical dosing equipment8 to 12 yearsCorrosive environment
Rainwater tanks20 to 40 yearsMaterial; sediment
Recycled water treatment plant15 to 20 years; membranes and lamps soonerMaintenance; feed quality
Irrigation systems10 to 20 yearsUV; damage; controllers

Trade Waste Systems

Concrete grease arrestors last twenty to forty years and steel fifteen to twenty-five, while plastic and fibreglass units and oil interceptors last twenty-five to forty. Most failures come sooner, from loads the arrestor was never sized for and pump-outs that are too infrequent.

ComponentTypical lifeWhat moves it
Concrete grease arrestors20 to 40 yearsHydrogen sulphide and acid attack on concrete
Steel arrestors15 to 25 yearsInternal corrosion
Plastic and fibreglass arrestors25 to 40 yearsGround movement; lid damage
Oil interceptors25 to 40 yearsAlarms; baffles; coalescer media
Baffles and internal fittings10 to 20 yearsCorrosion
Access covers15 to 30 yearsTraffic loads; corrosion

Water Supply

Copper and PEX pipework last fifty years and more, but galvanised steel lasts forty to sixty and often less, and brass fittings in plastic systems ten to thirty. Water chemistry decides how long copper actually lasts.

ComponentTypical lifeWhat moves it
Copper pipework50 years and moreWater chemistry; velocity; installation
Galvanised steel pipework40 to 60 years, often lessWater chemistry; internal corrosion
PEX pipework50 years and moreUV exposure; fittings
Brass fittings in plastic systems10 to 30 yearsDezincification in aggressive waters
Backflow prevention devices15 to 25 years with annual testingWater quality; debris; maintenance
Pressure-limiting valves10 to 20 yearsDebris; diaphragms
Cold water storage tanks20 to 40 yearsMaterial; lining; access and cleaning
Isolation valves15 to 30 yearsRarely operated; seize

Vertical Transportation

Accessibility Lifts

Accessibility lifts have short-lived parts on a longer-lived structure: batteries last three to five years and safety edges five to ten, while the drive and platform last fifteen to thirty. A unit's life is decided as much by whether its maker still supplies parts as by wear.

ComponentTypical lifeWhat moves it
Platform lift drive (screw, chain or hydraulic)15 to 25 yearsUse; lubrication; exposure
Controls and safety circuits10 to 15 yearsManufacturer support; exposure
Batteries3 to 5 yearsCharging; temperature
Safety edges and sensors5 to 10 yearsDamage; exposure
Gates and doors10 to 20 yearsAbuse; interlocks
Stair lift rails and carriages10 to 15 yearsUse
Platform and carriage structure20 to 30 yearsCorrosion on external units; impact
Hydraulic rams and seals15 to 20 yearsLeaks; oil condition; cold
Emergency call equipment10 to 15 yearsNetwork retirement rather than wear
Platform floor coverings and edging8 to 15 yearsWear; weather

Dock Levellers & Goods Hoists

Dock equipment works hard and wears fast. Bumpers last three to eight years and dock seals five to ten, levellers ten to twenty-five, and goods hoists twenty to thirty, but the real measure is the duty: vehicle movements per dock, and the weight of the forklifts crossing each lip.

ComponentTypical lifeWhat moves it
Hydraulic dock leveller15 to 25 yearsCycles; load ratings; impact
Mechanical dock leveller10 to 20 yearsSpring and hinge wear
Hydraulic power packs and cylinders10 to 15 yearsSeals; contamination
Lip hinges and deck plates10 to 20 yearsImpact; fatigue cracking
Vehicle restraints10 to 15 yearsImpact; controls
Dock seals and shelters5 to 10 yearsAbrasion; UV
Dock bumpers3 to 8 yearsTruck impacts
Goods hoists20 to 30 years; controls 15 to 20Duty; door abuse
Dock doors and door tracks10 to 20 yearsImpact; cycles; wind
Dock pit concrete and curb angle20 to 30 yearsImpact; water; forklift braking
Scissor lift tables15 to 20 yearsCycles; hydraulics; pit drainage
Dock lighting and signal systems10 to 15 yearsImpact; weather; lamp type

Escalators & Moving Walks

An escalator is renewed in parts around a long-lived truss. Handrails last five to ten years and step chains fifteen to twenty-five, while the truss lasts forty years and more, and its condition decides whether a unit is modernised or replaced.

ComponentTypical lifeWhat moves it
Truss40 years and moreCorrosion; water
Drive machine and gearbox20 to 30 yearsDuty; lubrication
Step chains15 to 25 yearsLoad; lubrication; wear
Steps and pallets20 to 30 yearsDamage; wear
Handrails5 to 10 yearsUV; cracking; tension
Controllers15 to 20 yearsManufacturer support
Comb platesReplaced as teeth breakDamage
Balustrade panels and decking20 to 30 yearsImpact; vandalism; style
Step rollers and tracks10 to 20 yearsDuty; lubrication; alignment
Safety devices and switches15 to 20 yearsTesting regime; moisture
Lighting and demarcationRenewed with stepsDamage; visibility requirements

Passenger & Goods Lifts

A lift's parts age at very different rates: controllers, drives and door equipment fifteen to twenty years, ropes ten to twenty, machines twenty-five to forty, and guide rails and safety gear longer still. What usually ends a controller's life is the end of parts support rather than wear.

ComponentTypical lifeWhat moves it
Controllers and drives15 to 20 yearsManufacturer support; electronics
Door operators and equipment15 to 20 yearsTraffic; abuse; maintenance
Geared machines25 to 35 yearsGear wear; lubrication
Gearless machines30 to 40 yearsBearings; brake
Suspension ropes10 to 20 yearsTrips; sheave condition; lubrication
Hydraulic cylinders25 to 30 yearsCorrosion of buried cylinders; seals
Car interiors10 to 20 yearsUse; style
Guide rails, buffers and safety gear30 to 40 yearsRarely limiting; must be tested
Landing and car door interlocks20 to 30 yearsTraffic; abuse; alignment
Overspeed governor and safety gear30 to 40 years, subject to testingTest results; pit conditions; corrosion
Fixtures, buttons and indicators10 to 20 yearsUse; vandalism; parts support
Emergency communication equipment10 to 15 yearsNetwork retirement rather than wear
Shaft wiring and travelling cables25 to 35 yearsFlexing; heat; rodents

Building Code Compliance

Disabled Access (DDA)

Access features wear at different rates. Ramps and paths last decades, while the fittings and finishes along the route need renewing far sooner. Typical lives are a guide; traffic, cleaning and use move them.

ElementTypical lifeWhat moves it
Ramps and paths30 to 50 yearsSurface wear; settlement
Tactile indicators (adhesive or discrete)5 to 15 yearsTraffic; adhesive failure; cleaning
Accessible toilet fittings15 to 25 yearsUse; vandalism
Door closers and automatic door operators10 to 15 yearsUse; adjustment
Hearing augmentation systems10 to 15 yearsTechnology; maintenance
Signage10 to 20 yearsUV; damage

Hazardous Materials

Hazardous materials do not wear out on a schedule; they change condition. Bonded materials stay safe while sound and undisturbed, and weathering, damage and works turn them into a hazard, so condition and disturbance matter more than age.

MaterialWhat happens over timeWhat moves it
Bonded asbestos cementWeathers, erodes and cracks; becomes friable at the surfaceExposure; lichen; impact
Friable asbestosDeteriorates and releases fibresVibration; water; disturbance
Vinyl tiles and adhesivesStable unless sanded or removedWorks
Lead paintChalks, flakes and peelsWeather; friction at windows and doors
PCB capacitorsLeak as they ageAge; heat
Asbestos registersBecome outdated after works and with timeReview cycles

Occupational Health & Safety (OHS)

The physical safety measures in a building wear with traffic and time, and the records that support them go out of date as soon as the building changes. Typical lives are a guide; traffic, cleaning and alterations move them.

ElementTypical lifeWhat moves it
Stair nosings and treads10 to 25 yearsTraffic; cleaning
Anti-slip treatments1 to 5 yearsTraffic; cleaning products
Fixed ladders and platforms25 to 40 yearsCorrosion; damage
Glass manifestation5 to 15 yearsCleaning; damage
Safety signs10 to 20 yearsUV; damage
Records and registersMust be kept currentChanges to the building

Environmental

Electric Vehicle (EV) Charging

Charging equipment is short-lived against the building around it. Chargers and load management last around a decade, the cabling and distribution behind them last decades, and software support often decides when a charger becomes obsolete.

ComponentTypical lifeWhat moves it
AC chargers8 to 12 yearsUse; weather; software support
DC fast chargers8 to 12 years; modules soonerHeat; use; manufacturer support
Cabling and distribution25 to 40 yearsInstallation quality; loading
Load management systems8 to 12 yearsSoftware and communications support
Charger software and back-end servicesDepends on vendorProtocol support; vendor viability

Energy Efficiency Upgrades

An upgrade's life is set less by wear than by how long its savings last. Equipment typically lasts ten to twenty years or more, but the savings from recommissioning can drift within a few years unless they are monitored.

UpgradeTypical lifeWhat moves it
LED fittings15 to 20 yearsDrivers; heat
Variable speed drives10 to 15 yearsHeat; harmonics
Heat pumps and efficient plant15 to 25 yearsMaintenance; sizing
BMS recommissioning savings2 to 5 years before driftOverrides; staff changes
Insulation and glazing upgradesLife of the buildingMoisture; installation
Solar PV25 to 30 years; inverters 10 to 15Inverters; roof

Sub-metering

Meters outlast their usefulness more often than they wear out. Electronic meters last fifteen to twenty years, but communications, batteries and data platforms fail far sooner, and accuracy declines before a meter stops working.

ComponentTypical lifeWhat moves it
Electronic electricity meters15 to 20 yearsTechnology; communications
Mechanical water meters10 to 15 years before accuracy dropsVolume passed; water quality
Battery-powered meter communications5 to 10 yearsBattery life
Thermal meters10 to 15 yearsSensor drift; flow meter fouling
Data gateways and software5 to 10 yearsVendor support; networks

Water Conservation

Water saving measures last only as long as they keep working as intended. Fixtures and controls need renewing within ten to twenty years, and the savings depend on leaks being found and controls not being bypassed.

MeasureTypical lifeWhat moves it
Tapware and showerheads10 to 20 yearsWater quality; use
Toilets and cisterns20 to 30 years; internals 5 to 10Valve and seal wear
Urinal controls10 to 15 yearsSensors; batteries
Water meters10 to 20 yearsAccuracy; batteries
Irrigation controllers8 to 12 yearsTechnology