Can hurt someone now. Made safe at once. These are the 129 findings the Technical Library grades as safety, across 102 elements and spaces, each with what it means for timing. Each element’s name opens its own page, where the finding sits with its causes and remedies.
Scope
A grading describes a kind of finding in general. What a finding means in a particular building depends on that building’s own evidence, and the same sign can be graded differently once it is read. None of this is a diagnosis, and none of it is a price.
Finding Impact What it means for timing Retaining wall leaning or moving beside a public area, building or boundary; radon above action levels 4 Essential Exclude people and loads, prop or remediate now.
Finding Impact What it means for timing Rapid or large movement with wide cracks, distorted openings that threaten egress, or loss of bearing to walls and columns 4 Essential Prop and engineer now.
Finding Impact What it means for timing Trip edges in walkways; settlement under racking causing lean; damaged post-tensioning 4 Essential Isolate area and fix now.
Finding Impact What it means for timing Floor collapse risk from decay or termites; radon above action levels 4 Essential Prop and remediate now.
Finding Impact What it means for timing Walls bowing significantly; crushed bearings under beams; bulging stone faces; unreinforced masonry parapets in seismic areas 4 Essential Prop and engineer now.
Finding Impact What it means for timing Bracing removed in a portal frame building; significant openings in cores without engineering; earthquake damage 4 Essential Brace temporarily and engineer now.
Finding Impact What it means for timing Punching shear distress; significant section loss at critical members; spalling over occupied areas; post-fire damage 4 Essential Prop, exclude and engineer now.
Finding Impact What it means for timing Floors overloaded beyond design; cut tendons; severe decay at joist bearings 4 Essential Remove loads or prop now.
Finding Impact What it means for timing Loose, cracked or displaced ornament over a public or occupied area; recent fragments fallen 4 Essential Remove loose material and protect below immediately (netting, sidewalk shed, exclusion).
Finding Impact What it means for timing Structural crack, brake fault, failed safety device, or failed inspection item on equipment carrying people 4 Essential Tag out of service immediately; repair before any use.
Finding Impact What it means for timing Sag, slack or failed rod, cracked anchorage, damaged post, or glass breakage over a footpath or entrance 4 Essential Close the footpath below or prop immediately; engineer within days.
Finding Impact What it means for timing Loose, cracked or displaced panel or stone over a footpath, entry or occupied area; anchor visibly failed 4 Essential Make safe immediately: remove, net or hoard; engineer within days.
Finding Impact What it means for timing Loose render over a public or occupied area; deteriorating lead paint where children live or play 4 Essential Remove loose render and protect below; stabilise lead paint under controls immediately.
Finding Impact What it means for timing Broken or loose glass at height over a public or occupied area; SSG glass moving; spontaneous breakage of non-heat-soaked toughened glass above a footpath 4 Essential Make safe immediately: remove, protect below, restrict access; engineer and glazier within days.
Finding Impact What it means for timing Loose, displaced or bulging brickwork over a footpath, entrance or occupied area; parapet or chimney out of plumb; outer leaf detached from ties 4 Essential Make safe immediately (exclusion zone, netting or take-down), engineer within days, repair within months.
Finding Impact What it means for timing Sealant or panels so failed that cladding or glazing is loose 4 Essential Make safe now.
Finding Impact What it means for timing Balustrade that moves under hand pressure, missing glass panel, loose post; cantilever rotation or root cracking; decayed or loose deck ledger 4 Essential Close or barricade immediately; engineer within days. Cantilever tip dropped with cracking along the wall line; deck ledger separating from the wall 4 Essential Close the balcony or deck now and prop.
Finding Impact What it means for timing Stack leaning with open joints or loose upper courses; loose pots; breast removed without support; flue gas leakage 4 Essential Make safe now; appliance out of use. Working flue with signs of leakage or carbon monoxide alarm activations 4 Essential Take the appliance out of use until the flue is tested. Stack over a roof, path or street loose or cracked after a storm or earthquake 4 Essential Make safe now. Timbers built into or touching a working flue; combustibles against an unlined flue 4 Essential Take the appliance out of use until separated.
Finding Impact What it means for timing Loose-fill asbestos; foil over damaged wiring; batts over downlights or transformers 4 Essential Isolate and assess now; do not disturb.
Finding Impact What it means for timing Parapet leaning or bowing over a public area; loose copings; screens loose 4 Essential Make safe now: remove, restrain or exclude below. Loose copings or screen panels over a street or entrance 4 Essential Secure or remove now. Terracotta or ornament with corroded cramps, units loose or cracked, over a street 4 Essential Make safe now: remove loose units, net or hoard below.
Finding Impact What it means for timing Ponding on a light roof with visible deflection; blocked outlets with water building against a parapet 4 Essential Clear and relieve now; stop access. Gutters, brackets or cast iron loose over entrances and paths 4 Essential Secure or remove now. Internal stack or gutter leaking near switchboards, risers or electrical equipment 4 Essential Isolate and repair now.
Finding Impact What it means for timing Fragile roof (asbestos cement, translucent sheet) reached without walkways, mesh or edge protection 4 Essential Stop access until controls are in place. Loose sheets, tiles, cappings or flashings above a footpath or entrance 4 Essential Secure or remove now.
Finding Impact What it means for timing Plant, gutters or roof lights maintained near an unprotected edge or fragile surface 4 Essential Stop access until protected. Fragile roof lights or sheeting on access routes with no mesh, covers or guardrails 4 Essential Protect or bar access now.
Finding Impact What it means for timing Visible sag with cracking, buckled members or failed connections; RAAC planks showing cracking, deflection or wet 4 Essential Prop and restrict use now. Ponding on a light roof with visible deflection 4 Essential Relieve the water and restrict access now.
Finding Impact What it means for timing Unprotected fragile roof lights where people work; overhead glass that is not laminated over occupied areas, with breakage history 4 Essential Protect now: mesh, covers, guardrails or restrict access. Monolithic toughened or wired glass in overhead positions above occupied space 4 Essential Protect below or replace with laminated glass.
Finding Impact What it means for timing Membrane torn or lifted by wind; ballast displaced at corners and edges over public areas 4 Essential Secure now. Ponding on a light deck with visible deflection; outlets blocked with water rising 4 Essential Clear and relieve now.
Finding Impact What it means for timing Water damaging structure, electrical fittings or another dwelling; hot water above safe temperatures for vulnerable occupants 4 Essential Stop use of the shower or fix now.
Finding Impact What it means for timing Grease build-up in ducts; suppression not covering appliances; gas interlocks bypassed; cool room releases failed; CO from backdraught 4 Essential Rectify before cooking continues.
Finding Impact What it means for timing Rooms without required sprinkler, detection, emergency lighting or exit coverage; egress paths blocked by the fit-out 4 Essential Rectify before occupation continues.
Finding Impact What it means for timing Obstructed escape routes; fire doors not closing; failed emergency lighting; smoke vents not opening 4 Essential Rectify now.
Finding Impact What it means for timing Non-compliant flat entrance doors; storage and charging in escape routes; failed emergency lighting 4 Essential Rectify now.
Finding Impact What it means for timing Unsealed riser floors; storage in risers; water on electrical equipment 4 Essential Rectify now.
Finding Impact What it means for timing Carbon monoxide or spillage; inadequate clearances; unflued heaters in bedrooms 4 Essential Stop use now.
Finding Impact What it means for timing Trip hazards; slippery floors with incidents; damaged asbestos-containing tiles 4 Essential Make safe now.
Finding Impact What it means for timing Fire interfaces failing (AHUs, smoke control, lifts, doors, gas) 4 Essential Rectify now; fire watch if needed.
Finding Impact What it means for timing Exit doors locked or with wrong hardware; electronic locks not releasing; fire doors not closing 4 Essential Rectify now.
Finding Impact What it means for timing Propped or failed stair doors; storage in stairs; failed emergency lighting; locked final exits; unsafe locking 4 Essential Rectify now.
Finding Impact What it means for timing Sagging ceilings; damaged asbestos-containing finishes; flaking lead paint where children are present 4 Essential Exclude, make safe and remediate now.
Finding Impact What it means for timing Gas leaks or unsafe clearances; aged flexible hoses; overloaded circuits 4 Essential Rectify now.
Finding Impact What it means for timing Water in pits affecting safety equipment; machine rooms with unsafe access or storage 4 Essential Rectify now.
Finding Impact What it means for timing No pedestrian segregation; dock doors with failed safety devices or springs; open edges; fumes entering the building 4 Essential Rectify now.
Finding Impact What it means for timing Non-laminated overhead glass over occupied areas with breakage history; low or climbable balustrades at upper levels; smoke control failing tests 4 Essential Protect, restrict access or rectify now.
Finding Impact What it means for timing Unsafe automatic or revolving doors; slippery entry with incidents; security that does not release on alarm 4 Essential Rectify now.
Finding Impact What it means for timing Unidentified confined spaces; unguarded hatches; no safe access to plant above ceilings or on roofs 4 Essential Rectify before next access.
Finding Impact What it means for timing Fire-rated partitions breached; unsafe glazing; operable walls with failing tracks 4 Essential Rectify now.
Finding Impact What it means for timing Failed refrigerant or gas detection; blocked exits; storage at switchboards; water over switchboards 4 Essential Rectify now.
Finding Impact What it means for timing Legionella risk from little-used showers; accessible facilities unavailable 4 Essential Flush, disinfect, restore now.
Finding Impact What it means for timing Missing or failed smoke alarms; entry doors not self-closing in apartment buildings; severe mould 4 Essential Rectify now.
Finding Impact What it means for timing Fire separation breached between tenancies; sprinkler or detection coverage missing after fit-out 4 Essential Rectify before trading continues.
Finding Impact What it means for timing Exits blocked; exit doors locked; fire doors propped 4 Essential Clear and rectify now.
Finding Impact What it means for timing Fume cupboards failing containment; untested or blocked safety showers; medical gas faults; ligature points in mental health areas 4 Essential Take out of use and rectify now.
Finding Impact What it means for timing Electrical hazards near water; overloaded floors; pool and spa safety failures 4 Essential Isolate now.
Finding Impact What it means for timing Floor overload; incompatible dangerous goods; storage blocking sprinklers or egress; battery charging in cages 4 Essential Remove or rectify now.
Finding Impact What it means for timing Leaning or damaged structures over occupied areas; damaged asbestos cement; water features with exposed electrics; bin stores against walls with fire risk 4 Essential Exclude, make safe or remove now.
Finding Impact What it means for timing Powered gate safety devices failing; pool barrier non-compliant; boundary wall leaning toward a public area; exit signs wrong or missing 4 Essential Disable, close or rectify now.
Finding Impact What it means for timing Defective trees over occupied areas; vegetation creating bushfire risk 4 Essential Prune, remove or exclude now.
Finding Impact What it means for timing Trip hazards in pedestrian routes; large potholes in traffic areas 4 Essential Make safe now: patch, grind or barricade.
Finding Impact What it means for timing Inadequate surfacing; entrapment hazards; broken equipment; gas leaks 4 Essential Close and fix now.
Finding Impact What it means for timing Broken or missing grates in traffic or pedestrian areas; flooding into switchrooms or basements 4 Essential Make safe now.
Finding Impact What it means for timing Legionella risk from an adiabatic humidifier; heavy microbial growth in a unit serving a healthcare or occupied space; contaminated intake near a cooling tower or exhaust 4 Essential Isolate or clean now; hygiene and engineer review.
Finding Impact What it means for timing BMS exposed to the internet with default credentials; fire interface failing 4 Essential Isolate and secure now; test fire interfaces.
Finding Impact What it means for timing Ammonia or large refrigerant leak; plant room without required refrigerant detection or ventilation; pressure relief discharging into the room 4 Essential Isolate and ventilate now; plant room safety measures before restart.
Finding Impact What it means for timing Gas leak, carbon monoxide or spillage, failed flame safeguard or safety valve, inadequate plant room ventilation 4 Essential Isolate now; gas fitter and engineer before restart.
Finding Impact What it means for timing Fire or smoke dampers missing, obstructed, failed or untested; deteriorating asbestos in duct materials 4 Essential Rectify now; fire engineer and licensed asbestos removal.
Finding Impact What it means for timing Legionella above the action levels in the regulation; tower near air intakes or public areas with damaged drift eliminators 4 Essential Disinfect and follow the prescribed response now.
Finding Impact What it means for timing Cracked heat exchanger on a gas rooftop unit; refrigerant leak in a small room without detection 4 Essential Isolate now.
Finding Impact What it means for timing Water leaking onto electrical equipment; asbestos in deteriorating induction units 4 Essential Isolate now.
Finding Impact What it means for timing Grease build-up in kitchen ductwork; car park ventilation not responding to CO; fume cupboard failing test; flue spillage from negative pressure 4 Essential Stop use or clean and repair now.
Finding Impact What it means for timing Lift emergency phones or alarm diallers not working; access-controlled escape doors not releasing; nurse call failures 4 Essential Rectify now.
Finding Impact What it means for timing Escape routes, stairs or exits without working emergency lighting or exit signs; fittings that will not operate on local failure 4 Essential Rectify now.
Finding Impact What it means for timing Generator serving life-safety loads fails to start or carry load; fuel leak; lithium battery fire risk without separation 4 Essential Rectify now; interim measures.
Finding Impact What it means for timing Columns corroded or damaged at the base; suspended fittings with failed fixings; leaking PCB capacitors 4 Essential Remove, secure or isolate now.
Finding Impact What it means for timing Stairs or egress paths left dark by sensor faults or settings 4 Essential Fix now.
Finding Impact What it means for timing Loose conductors at height over public areas; protection missing on hazardous stores 4 Essential Secure or rectify now.
Finding Impact What it means for timing Exposed live parts; burning or overheating; water on or above the board; PCB oil leaking 4 Essential Isolate or protect now.
Finding Impact What it means for timing Perished rubber wiring; exposed live parts; scorched accessories; no RCD on wet area or outdoor circuits; aluminium branch wiring without remediation 4 Essential Isolate, make safe or rewire now.
Finding Impact What it means for timing Burnt connectors or isolators; exposed live DC; loose modules; battery overheating 4 Essential Isolate now.
Finding Impact What it means for timing Control valves closed; storage hazard beyond design; heads covered or obstructed over large areas; water supply below design 4 Essential Restore protection or reduce the hazard now; fire watch until done.
Finding Impact What it means for timing Zones isolated or detectors covered in occupied areas; alarm signalling not reaching the brigade; inaudible warning; failed interfaces to lifts, doors or smoke control 4 Essential Restore protection now; fire watch until done.
Finding Impact What it means for timing Pump fails to start; controller in off or manual; pump supply unprotected; performance well below design 4 Essential Restore now; fire watch and brigade notification.
Finding Impact What it means for timing Booster or hydrants inaccessible or inoperable; dry riser failing pressure test; flow well below requirement 4 Essential Restore now; notify the brigade.
Finding Impact What it means for timing Stair or escape route doors not closing; breached riser or stair penetrations; fire doors wedged open; flat entrance doors not fire-rated in apartment buildings 4 Essential Rectify now; fire watch or interim measures where needed.
Finding Impact What it means for timing Wrong type at a high hazard (water at switchboards, none at commercial cooking); discharged units in high-risk areas 4 Essential Replace now.
Finding Impact What it means for timing System does not start on alarm; stair doors cannot be opened; stair pressurisation failed; AOVs not opening 4 Essential Rectify now; interim measures.
Finding Impact What it means for timing Carbon dioxide safeguards failed; system isolated in a protected room; kitchen system disabled 4 Essential Rectify now.
Finding Impact What it means for timing Gas leak; uncapped live pipe; failed emergency shut-off; LPG separation breached 4 Essential Isolate and rectify now.
Finding Impact What it means for timing Failed TMVs in healthcare, aged care, childcare or accessible bathrooms; positive Legionella; relief valve blocked; gas heater flue spillage 4 Essential Isolate, disinfect or rectify now.
Finding Impact What it means for timing Sump serving switchrooms or lift pits with failed pumps or alarms; sewage pit with no ventilation or failed lid 4 Essential Restore now; temporary pumping.
Finding Impact What it means for timing Sewage leaking into occupied spaces; sewer gas in occupied rooms; no backflow protection in flood-prone basements 4 Essential Rectify now.
Finding Impact What it means for timing Unsafe pool outlets; pool barriers failed; chemical storage able to release chlorine gas; cross-connection to drinking water; Legionella in a spa or feature 4 Essential Close, isolate or rectify now.
Finding Impact What it means for timing Broken covers in trafficked areas; hydrogen sulphide exposure; oil discharging to stormwater 4 Essential Make safe and contain now.
Finding Impact What it means for timing Failed backflow device on a high-hazard connection; unprotected cross-connection; lead above drinking water limits; Legionella in cold storage 4 Essential Isolate or rectify now; notify the utility or health authority where required.
Finding Impact What it means for timing Safety edges, pans or interlocks failed or bypassed 4 Essential Take out of service until proved. No working emergency call from the platform, or no emergency lowering 4 Essential Take out of service until restored. Unit or its rail obstructing an escape stair 4 Essential Clear now.
Finding Impact What it means for timing Free-fall protection failed or absent on a leveller in use 4 Essential Take out of use now; this is the failure that kills. Goods hoist landing door opening without the car present 4 Essential Take out of use until the interlock is proved. Cracked lips, decks or hinges under load 4 Essential Take out of use now. Open dock edges with no barrier, gate or closed door 4 Essential Protect now. No vehicle restraint or chocking in use at an operating dock 4 Essential Stop loading until a restraint procedure is in place. Staff riding a goods hoist 4 Essential Stop now; signage alone is not a control.
Finding Impact What it means for timing Safety devices bypassed, disconnected or failing on test 4 Essential Stop the unit until every device is proved. Broken comb teeth; step to skirt gaps beyond limit; missing skirt deflectors 4 Essential Stop until fixed. Brake out of its stopping distance limits, or auxiliary brake defective 4 Essential Stop until adjusted and retested. Handrail speed mismatch, cracked handrail or missing inlet guard 4 Essential Stop or restrict until corrected. Cracked or broken steps, or missing demarcation lines 4 Essential Stop until replaced.
Finding Impact What it means for timing Landing door openable without the car present; car moves with doors open; brake or safety gear defect 4 Essential Remove from service until fixed. Emergency communication not working, or reaching no one who answers 4 Essential Remove from service until restored. Levelling errors creating a trip step at a landing 4 Essential Correct now; restrict use if significant. Fire-fighting or evacuation lift not performing its fire functions 4 Essential Restore now; notify the fire strategy owner.
Finding Impact What it means for timing Lifted tactile indicators or damaged ramps creating trip hazards; no means of evacuation for people with disability 4 Essential Rectify now.
Finding Impact What it means for timing Damaged friable asbestos in accessible areas; deteriorating lead paint where children are present; leaking PCBs 4 Essential Isolate and remediate now.
Finding Impact What it means for timing Unprotected access to plant at height; unidentified confined spaces; dangerous glazing; slippery entries 4 Essential Rectify now.
Finding Impact What it means for timing Overloaded circuits or boards; unsafe installations; extension-lead charging 4 Essential Isolate and rectify now.
Finding Impact What it means for timing Fabric upgrade causing condensation and mould affecting health 4 Essential Rectify now.
Finding Impact What it means for timing Cross-connection of recycled water to drinking water 4 Essential Isolate now.
Nothing matches that. Try fewer letters.
Moyne Ross
Technical Library · Updated 14 November 2026