Every measured value the Technical Library records for Australia: 80 thresholds across 54 elements and spaces, each with the code or standard it comes from. Each element’s name opens its own page, where the value sits with how the element fails and what fixes it.

Values from NCC 2025. NCC 2022 still governs in New South Wales, Queensland, South Australia, Tasmania and the Northern Territory until at least May 2027 (where each state stands); check the edition in force where the asset is.

Substructure

Basement, Cellars & Retaining Walls

MeasureThresholdSource
Wall crack categories (AS 2870)Negligible under 0.1 mm; very slight under 1 mm; slight under 5 mm; moderate 5 to 15 mm; severe 15 to 25 mmStandards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source)

Foundations

MeasureThresholdSource
Wall crack categories (AS 2870)Negligible under 0.1 mm; very slight under 1 mm; slight under 5 mm; moderate 5 to 15 mm; severe 15 to 25 mmStandards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source)
Floor offset from a 3 m straight edge (AS 2870)Negligible under 8 mm; very slight under 10 mm; slight under 15 mm; moderate 15 to 25 mm; severe over 25 mmStandards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source)
Floor slopes (AS 2870)Local slopes steeper than 1 in 100 (10 mm per metre) are clearly visible; overall slopes beyond 1 in 150 (about 6.7 mm per metre) are undesirableStandards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source)

Slab on Ground

MeasureThresholdSource
Floor offset from a 3 m straight edge (AS 2870)Negligible under 8 mm; very slight under 10 mm; slight under 15 mm; moderate 15 to 25 mm; severe over 25 mmStandards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source)
Crack width in house slabs (AS 2870)Negligible under 0.3 mm; very slight under 1 mm; slight under 2 mm; moderate 2 to 4 mm; severe 4 to 10 mmStandards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source)

Sub-floor & Crawlspace

MeasureThresholdSource
Subfloor ground clearanceAt least 150 mm under the lowest member; 400 mm where termite management relies on inspectionNCC 2025 Housing Provisions, Part 6.2 Subfloor ventilation, 6.2.1
Subfloor ventilation openingsAt least 2,000, 4,000 or 6,000 mm² per metre of wall in climate zones A, B and C; half where the ground is sealed with a membrane; 50 per cent more where excessively damp; spaced evenly, no more than 600 mm from cornersNCC 2025 Housing Provisions, Part 6.2 Subfloor ventilation, 6.2.1

Superstructure

Load-Bearing Masonry

MeasureThresholdSource
Wall crack categories (AS 2870)Negligible under 0.1 mm; very slight under 1 mm; slight under 5 mm; moderate 5 to 15 mm; severe 15 to 25 mm; limits half as wide again for plasterboard partitionsStandards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source)

Façades

Canopies & Awnings

MeasureThresholdSource
Awnings over public footways (New South Wales)Awnings more than 10 years old inspected by a structural engineerPlanning Circular BS 13-001 Safety of awnings over public lands

Cladding & Wall Systems

MeasureThresholdSource
Cladding clearance to ground (houses)150 mm to finished ground; 100 mm in low-rainfall or sandy, well-drained areas; 50 mm above paving that falls away; cladding taken 50 mm below the lowest floor framingNCC 2025 Housing Provisions, Part 7.5 Timber and composite wall cladding, 7.5.7

Glazing Systems

MeasureThresholdSource
Side panels beside doorways (houses)Framed side panels within 300 mm of a doorway: Grade A safety glassNCC 2025 Housing Provisions, Part 8.4 Glazing: human impact

Masonry/Brickwork

MeasureThresholdSource
Masonry damage categories (AS 2870, Appendix C)Category 0 under 0.1 mm; 1 under 1 mm; 2 under 5 mm; 3 from 5 to 15 mm; 4 from 15 to 25 mmStandards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source)

Verandahs, Balconies & Balustrades

MeasureThresholdSource
BarriersRequired where the surface is 1 m or more above the ground beneath; at least 1 m high; openings that will not pass a 125 mm sphere; above 4 m, no climbable horizontal elements between 150 mm and 760 mmNCC 2025 Volume One, Part D3 Construction of exits

Roofs & Rainwater Goods

Chimney Stacks & Flues

MeasureThresholdSource
Chimney or flue terminal heightAt least 300 mm above any part of the building within 3.6 m horizontallyNCC 2025 Housing Provisions, Part 12.4 Heating appliances, fireplaces, chimneys and flues
Hearth extent, open fireplacesAt least 300 mm in front of the opening and 150 mm beyond each sideNCC 2025 Housing Provisions, Part 12.4 Heating appliances, fireplaces, chimneys and flues

Insulation

MeasureThresholdSource
Downlight clearances as lost insulationAbout 20 downlights with 50 mm clearance, or 3 with 200 mm, use up 0.5 per cent of a 200 m² ceilingNCC 2025 Housing Provisions, Part 13.2 Building fabric
Installed insulationBulk insulation kept at full thickness; reflective sheets lapped at least 150 mm or tapedNCC 2025 Housing Provisions, Part 13.2 Building fabric

Plant Screens & Parapets

MeasureThresholdSource
Roof edge barrierAt least 1 m high where a roof with general access is 1 m or more above the surface belowNCC 2025 Volume One, Part D3 Construction of exits, D3D17

Rainwater Systems

MeasureThresholdSource
Design stormEaves gutters: 5 per cent annual chance (1 in 20); box gutters: 1 per cent annual chance (1 in 100)AS/NZS 3500.3:2025 Plumbing and drainage, Part 3: Stormwater drainage
Eaves gutters on housesFall at least 1:500 unless designed to AS/NZS 3500.3; brackets at no more than 1.2 m centresNCC 2025 Housing Provisions, Part 7.4 Gutters and downpipes
Eaves gutter overflow on houses, at 150 mm/h0.17 L/s per metre of gutter for a 4 m ridge-to-gutter length; 0.25 L/s for 6 m; 0.33 L/s for 8 mNCC 2025 Housing Provisions, Part 7.4 Gutters and downpipes

Roof Coverings

MeasureThresholdSource
Sheet roofing end lapsAt least 150 mm above 15 degrees; 200 mm from 5 to 15 degreesNCC 2025 Housing Provisions, Part 7.2 Sheet roofing
Sarking under tilesLaps at least 150 mm; fixed at no more than 300 mm centres; sags no deeper than 40 mmNCC 2025 Housing Provisions, Part 7.3 Roof tiles and shingles

Roof Safety Systems

MeasureThresholdSource
Roof edge barrierAt least 1 m high where a roof with general access is 1 m or more above the surface belowNCC 2025 Volume One, Part D3 Construction of exits, D3D17

Waterproofing Membranes

MeasureThresholdSource
Minimum fall, external membranes1 in 100 (10 mm per metre)AS 4654.2-2012 Waterproofing membranes for external above-ground use, Part 2: Design and installation

Internal Areas

Bathrooms & Wet Areas

MeasureThresholdSource
Hot water at sanitary fixturesNo more than 45 °C in aged care, healthcare, early childhood centres and schools; 50 °C in most other buildingsNCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services

Common Circulation Areas

MeasureThresholdSource
Travel distance, Class 5 to 9No more than 20 m to an exit or point of choice, and no more than 40 m to one of two exitsNCC 2025 Volume One, Part D2 Provision for escape, D2D5
Apartment entry doors to an exitWithin 6 m of an exit or point of choiceNCC 2025 Volume One, Part D2 Provision for escape, D2D5
Fire door gaps (AS 1905.1)3 mm at the top and sides; no more than 10 mm at the bottomFire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source)

Common Internal Areas

MeasureThresholdSource
Fire door gaps (AS 1905.1)3 mm at the top and sides; no more than 10 mm at the bottomFire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source)

Electrical & Communications Risers

MeasureThresholdSource
Fire door gaps (AS 1905.1)3 mm at the top and sides; no more than 10 mm at the bottomFire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source)

Fireplaces

MeasureThresholdSource
Hearth extent, open fireplacesAt least 300 mm in front of the opening and 150 mm beyond each sideNCC 2025 Housing Provisions, Part 12.4 Heating appliances, fireplaces, chimneys and flues
Chimney or flue terminal heightAt least 300 mm above any part of the building within 3.6 m horizontallyNCC 2025 Housing Provisions, Part 12.4 Heating appliances, fireplaces, chimneys and flues

Integrated Building Systems

MeasureThresholdSource
Stair pressurisation (AS 1668.1)Door opening force at the handle no more than 110 N; air flowing through open stair doors at 1 m/sStair pressurisation performance in high-rise buildings (Fire, 2023, 6(4), 132) (quoted by a secondary source)
Alarm level at unit entry doors (Class 2 and 3)85 dB(A) with a smoke alarm system, or 100 dB(A) with a smoke detection systemNCC 2025 Volume One, Specification 20 Smoke detection and alarm systems

Internal Doors & Hardware

MeasureThresholdSource
Fire door gaps (AS 1905.1)3 mm at the top and sides; no more than 10 mm at the bottomFire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source)

Internal Stairwells

MeasureThresholdSource
Risers and goings, public stairsRisers 115 to 190 mm and goings 250 to 355 mm, constant through each flight; 2R + G between 550 and 700 mm; no more than 18 risers a flightNCC 2025 Volume One, Part D3 Construction of exits, D3D14
HandrailsOn at least one side, and on both sides where the stair is 2 m wide or more; at least 865 mm above the nosings; continuous between landingsNCC 2025 Volume One, Part D3 Construction of exits, D3D22
Barrier heightAt least 865 mm above the nosings on a flight, and 1 m at landings and floorsNCC 2025 Volume One, Part D3 Construction of exits, D3D17
Openings between treadsRisers must not let a 125 mm sphere pass between treadsNCC 2025 Volume One, Part D3 Construction of exits, D3D19
Fire door gaps (AS 1905.1)3 mm at the top and sides; no more than 10 mm at the bottomFire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source)

Kitchen

MeasureThresholdSource
Hot water at sanitary fixturesNo more than 45 °C in aged care, healthcare, early childhood centres and schools; 50 °C in most other buildingsNCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services

Lobbies & Atria

MeasureThresholdSource
Barriers at upper levelsAt least 1 m high where the floor is 1 m or more above the level below; openings that will not pass a 125 mm sphereNCC 2025 Volume One, Part D3 Construction of exits

Public Amenities

MeasureThresholdSource
Hot water at sanitary fixturesNo more than 45 °C in aged care, healthcare, early childhood centres and schools; 50 °C in most other buildingsNCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services

Residential Units/Guest Rooms

MeasureThresholdSource
Alarm level at unit entry doors (Class 2 and 3)85 dB(A) with a smoke alarm system, or 100 dB(A) with a smoke detection systemNCC 2025 Volume One, Specification 20 Smoke detection and alarm systems
Hot water at sanitary fixturesNo more than 45 °C in aged care, healthcare, early childhood centres and schools; 50 °C in most other buildingsNCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services

Service Corridors

MeasureThresholdSource
Travel distance, Class 5 to 9No more than 20 m to an exit or point of choice, and no more than 40 m to one of two exitsNCC 2025 Volume One, Part D2 Provision for escape, D2D5

Specialised Occupancy Areas

MeasureThresholdSource
Fume cupboard face velocity (AS/NZS 2243.8)Average of 0.5 m/s, with no reading below 0.3 m/s; tested at least every 12 monthsLocal exhaust ventilation (LEV)

Specialist & Non-Standard Features

MeasureThresholdSource
Pool barriers (Queensland)At least 1200 mm high; no more than 100 mm under the barrier; a 900 mm non-climbable zone; 300 mm clear inside; boundary fences used as barriers at least 1800 mmPool fences: requirements for pool barriers

External Elements

Fencing, Gates & Signage

MeasureThresholdSource
Pool barriers (Queensland)At least 1200 mm high; no more than 100 mm under the barrier; a 900 mm non-climbable zone; 300 mm clear insidePool fences: requirements for pool barriers

Mechanical Services

Central Cooling Plant

MeasureThresholdSource
R22 supplyFrom 1 January 2020, bulk R22 imports may only service existing equipment, within about 45 tonnes (45,000 kg) a year until 2029; from 1 January 2030 imports are banned and servicing relies on reclaimed refrigerantR22 phase out fact sheet

Ventilation Systems

MeasureThresholdSource
Fume cupboard face velocity (AS/NZS 2243.8)Average of 0.5 m/s, with no reading below 0.3 m/s; tested at least every 12 monthsLocal exhaust ventilation (LEV): WorkSafe Queensland guidance

Electrical Services

Emergency Lighting

MeasureThresholdSource
Rated durationTypically 90 minutesAS/NZS 2293.1:2026 Emergency lighting and exit signs for buildings, Part 1: System design, installation and operation
Where emergency lighting is requiredEvery path of travel on a storey over 300 m²; rooms over 100 m² that do not open to a lit corridor or open space; rooms over 300 m²NCC 2025 Volume One, Part E4 Visibility in an emergency, exit signs and warning systems, E4D2

Lighting Control System

MeasureThresholdSource
Area per lighting controlNo more than 250 m² of lighting per demand-operated control, other than in a single functional spaceNCC 2025 Volume One, Part J7 Artificial lighting and power
Daylight zone controlSeparate control of the natural lighting zone in Class 5, 6 or 8 buildings over 250 m²NCC 2025 Volume One, Part J7 Artificial lighting and power
Time switchesOnly where a space is regularly occupied: more than 1 person per 40 m², or used more than once every 15 minutesNCC 2025 Volume One, Part J7 Artificial lighting and power

Power Distribution

MeasureThresholdSource
Fixed RCD testing (Victoria, after AS/NZS 3760)Push-button test every 6 months; operating-time test every 12 months in high and medium risk areas, every 2 years in low risk areasElectrical safety (inspection and testing timeframes)

Fire Services

Automatic Sprinkler Systems

MeasureThresholdSource
When sprinklers are requiredThroughout a building where any part has an effective height of more than 25 m; new apartment buildings of four storeys and more since the 2019 amendmentsNCC 2025 Volume One, Part E1 Fire fighting equipment, E1D5

Fire Detection & Alarm Systems

MeasureThresholdSource
Alarm level at unit entry doors (Class 2 and 3)85 dB(A) at the entry door with a smoke alarm system, or 100 dB(A) with a smoke detection system, in place of measuring inside the unitNCC 2025 Volume One, Specification 20 Smoke detection and alarm systems

Fire Pumping Systems

MeasureThresholdSource
Boosted hydrant pressure (New South Wales, AS 2419.1:2021)700 kPa at the most hydraulically disadvantaged outlet in each pressure zonePosition statement summary: FRNSW pump performance for high rise buildings (quoted by a secondary source)

Hydrant & Hose Reel Systems

MeasureThresholdSource
Boosted hydrant pressure (AS 2419.1:2021, as applied in New South Wales)700 kPa at the most disadvantaged outletPosition statement summary: FRNSW pump performance for high rise buildings (quoted by a secondary source)
Unassisted residual pressure at a feed hydrant flowing 10 L/s (AS 2419.1)150 kPa in New South Wales; 200 kPa in the other states and territoriesFire and Rescue NSW fire hydrant testing 2017 (report MHL2534) (quoted by a secondary source)
Hose reelsWithin 4 m of an exit; a hose reel system serves any fire compartment over 500 m² without internal hydrantsNCC 2025 Volume One, Part E1 Fire fighting equipment

Passive Fire Protection

MeasureThresholdSource
Fire door gaps (AS 1905.1)3 mm at the top and sides; no more than 10 mm at the bottomFire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source)
Smoke door leavesSolid-core leaves at least 35 mm thick, or leaves able to resist smoke at 200 °C for 30 minutes, with smoke sealsNCC 2025 Volume One, Specification 12 Fire doors, smoke doors, fire windows and shutters

Portable Fire Equipment

MeasureThresholdSource
Extinguishers in apartment buildingsAn ABE extinguisher of at least 2.5 kg within 10 m of each unit’s entry doorNCC 2025 Volume One, Part E1 Fire fighting equipment

Smoke Management Systems

MeasureThresholdSource
Stair pressurisation (AS 1668.1)Door opening force at the handle no more than 110 N; air flowing through open stair doors at 1 m/sStair pressurisation performance in high-rise buildings (Fire, 2023, 6(4), 132) (quoted by a secondary source)

Hydraulic Services

Hot & Warm Water Plant

MeasureThresholdSource
Hot water at sanitary fixturesNo more than 45 °C in aged care, healthcare patient areas, early childhood centres and schools; 50 °C in most other casesNCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services
Storage heater reliefRated working pressure, or 1400 kPa if lower, not exceeded; water kept below 99 °CNCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services

Pumping Systems

MeasureThresholdSource
Water pressureWorking pressure at least 50 kPa at outlets; static pressure no more than 500 kPa within the buildingNCC 2025 Volume Three (Plumbing Code), Part B1 Cold water services, B1P6

Specialist Hydraulics

MeasureThresholdSource
Pool barriers (Queensland)At least 1200 mm high; no more than 100 mm under the barrier; a 900 mm non-climbable zone; 300 mm clear inside; boundary fences used as barriers at least 1800 mmPool fences: requirements for pool barriers

Water Supply

MeasureThresholdSource
Water pressureWorking pressure at least 50 kPa at outlets; static pressure no more than 500 kPa within the buildingNCC 2025 Volume Three (Plumbing Code), Part B1 Cold water services, B1P6

Vertical Transportation

Accessibility Lifts

MeasureThresholdSource
Travel limits by lift typeLow-rise platform lift: no more than 1000 mm; low-rise, low-speed constant pressure lift: no more than 2 m unenclosed or 4 m enclosedNCC 2025 Volume One, Part E3 Lift installations, E3D7

Passenger & Goods Lifts

MeasureThresholdSource
Stretcher-sized liftWhere lifts serve storeys above an effective height of 12 m, at least one takes a raised stretcher in a space 600 mm by 2000 mm by 1400 mm highNCC 2025 Volume One, Part E3 Lift installations, E3D3

Building Code Compliance

Occupational Health & Safety (OHS)

MeasureThresholdSource
Risers and goings, public stairsRisers 115 to 190 mm; goings 250 to 355 mmNCC 2025 Volume One, Part D3 Construction of exits, D3D14

Environmental

Electric Vehicle (EV) Charging

MeasureThresholdSource
EV charging readiness in car parksDedicated EV boards on each storey, sized for future 7 kW (32 A) chargers in 10 per cent of spaces (Class 5 and 6) or 20 per cent (Class 3, 7b, 8 and 9)NCC 2025 Volume One, Part J9 Energy monitoring and on-site distributed energy resources, J9D4
Sub-metering space on EV boardsAt least 36 mm of DIN rail per circuitNCC 2025 Volume One, Part J9 Energy monitoring and on-site distributed energy resources, J9D4

Sub-metering

MeasureThresholdSource
Energy meteringOver 500 m²: time-of-use metering of gas and electricity; over 2500 m²: separate meters for air conditioning, lighting, appliance power, central hot water and liftsNCC 2025 Volume One, Part J9 Energy monitoring and on-site distributed energy resources, J9D3