Every measured value the Technical Library records for Australia: 80 thresholds across 54 elements and spaces, each with the code or standard it comes from. Each element’s name opens its own page, where the value sits with how the element fails and what fixes it.
Values from NCC 2025. NCC 2022 still governs in New South Wales, Queensland, South Australia, Tasmania and the Northern Territory until at least May 2027 (where each state stands); check the edition in force where the asset is.
Substructure
Basement, Cellars & Retaining Walls
| Measure | Threshold | Source |
|---|---|---|
| Wall crack categories (AS 2870) | Negligible under 0.1 mm; very slight under 1 mm; slight under 5 mm; moderate 5 to 15 mm; severe 15 to 25 mm | Standards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source) |
Foundations
| Measure | Threshold | Source |
|---|---|---|
| Wall crack categories (AS 2870) | Negligible under 0.1 mm; very slight under 1 mm; slight under 5 mm; moderate 5 to 15 mm; severe 15 to 25 mm | Standards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source) |
| Floor offset from a 3 m straight edge (AS 2870) | Negligible under 8 mm; very slight under 10 mm; slight under 15 mm; moderate 15 to 25 mm; severe over 25 mm | Standards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source) |
| Floor slopes (AS 2870) | Local slopes steeper than 1 in 100 (10 mm per metre) are clearly visible; overall slopes beyond 1 in 150 (about 6.7 mm per metre) are undesirable | Standards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source) |
Slab on Ground
| Measure | Threshold | Source |
|---|---|---|
| Floor offset from a 3 m straight edge (AS 2870) | Negligible under 8 mm; very slight under 10 mm; slight under 15 mm; moderate 15 to 25 mm; severe over 25 mm | Standards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source) |
| Crack width in house slabs (AS 2870) | Negligible under 0.3 mm; very slight under 1 mm; slight under 2 mm; moderate 2 to 4 mm; severe 4 to 10 mm | Standards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source) |
Sub-floor & Crawlspace
| Measure | Threshold | Source |
|---|---|---|
| Subfloor ground clearance | At least 150 mm under the lowest member; 400 mm where termite management relies on inspection | NCC 2025 Housing Provisions, Part 6.2 Subfloor ventilation, 6.2.1 |
| Subfloor ventilation openings | At least 2,000, 4,000 or 6,000 mm² per metre of wall in climate zones A, B and C; half where the ground is sealed with a membrane; 50 per cent more where excessively damp; spaced evenly, no more than 600 mm from corners | NCC 2025 Housing Provisions, Part 6.2 Subfloor ventilation, 6.2.1 |
Superstructure
Load-Bearing Masonry
| Measure | Threshold | Source |
|---|---|---|
| Wall crack categories (AS 2870) | Negligible under 0.1 mm; very slight under 1 mm; slight under 5 mm; moderate 5 to 15 mm; severe 15 to 25 mm; limits half as wide again for plasterboard partitions | Standards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source) |
Façades
Canopies & Awnings
| Measure | Threshold | Source |
|---|---|---|
| Awnings over public footways (New South Wales) | Awnings more than 10 years old inspected by a structural engineer | Planning Circular BS 13-001 Safety of awnings over public lands |
Cladding & Wall Systems
| Measure | Threshold | Source |
|---|---|---|
| Cladding clearance to ground (houses) | 150 mm to finished ground; 100 mm in low-rainfall or sandy, well-drained areas; 50 mm above paving that falls away; cladding taken 50 mm below the lowest floor framing | NCC 2025 Housing Provisions, Part 7.5 Timber and composite wall cladding, 7.5.7 |
Glazing Systems
| Measure | Threshold | Source |
|---|---|---|
| Side panels beside doorways (houses) | Framed side panels within 300 mm of a doorway: Grade A safety glass | NCC 2025 Housing Provisions, Part 8.4 Glazing: human impact |
Masonry/Brickwork
| Measure | Threshold | Source |
|---|---|---|
| Masonry damage categories (AS 2870, Appendix C) | Category 0 under 0.1 mm; 1 under 1 mm; 2 under 5 mm; 3 from 5 to 15 mm; 4 from 15 to 25 mm | Standards and Tolerances Guide (December 2023), reproducing the AS 2870 damage categories (quoted by a secondary source) |
Verandahs, Balconies & Balustrades
| Measure | Threshold | Source |
|---|---|---|
| Barriers | Required where the surface is 1 m or more above the ground beneath; at least 1 m high; openings that will not pass a 125 mm sphere; above 4 m, no climbable horizontal elements between 150 mm and 760 mm | NCC 2025 Volume One, Part D3 Construction of exits |
Roofs & Rainwater Goods
Chimney Stacks & Flues
| Measure | Threshold | Source |
|---|---|---|
| Chimney or flue terminal height | At least 300 mm above any part of the building within 3.6 m horizontally | NCC 2025 Housing Provisions, Part 12.4 Heating appliances, fireplaces, chimneys and flues |
| Hearth extent, open fireplaces | At least 300 mm in front of the opening and 150 mm beyond each side | NCC 2025 Housing Provisions, Part 12.4 Heating appliances, fireplaces, chimneys and flues |
Insulation
| Measure | Threshold | Source |
|---|---|---|
| Downlight clearances as lost insulation | About 20 downlights with 50 mm clearance, or 3 with 200 mm, use up 0.5 per cent of a 200 m² ceiling | NCC 2025 Housing Provisions, Part 13.2 Building fabric |
| Installed insulation | Bulk insulation kept at full thickness; reflective sheets lapped at least 150 mm or taped | NCC 2025 Housing Provisions, Part 13.2 Building fabric |
Plant Screens & Parapets
| Measure | Threshold | Source |
|---|---|---|
| Roof edge barrier | At least 1 m high where a roof with general access is 1 m or more above the surface below | NCC 2025 Volume One, Part D3 Construction of exits, D3D17 |
Rainwater Systems
| Measure | Threshold | Source |
|---|---|---|
| Design storm | Eaves gutters: 5 per cent annual chance (1 in 20); box gutters: 1 per cent annual chance (1 in 100) | AS/NZS 3500.3:2025 Plumbing and drainage, Part 3: Stormwater drainage |
| Eaves gutters on houses | Fall at least 1:500 unless designed to AS/NZS 3500.3; brackets at no more than 1.2 m centres | NCC 2025 Housing Provisions, Part 7.4 Gutters and downpipes |
| Eaves gutter overflow on houses, at 150 mm/h | 0.17 L/s per metre of gutter for a 4 m ridge-to-gutter length; 0.25 L/s for 6 m; 0.33 L/s for 8 m | NCC 2025 Housing Provisions, Part 7.4 Gutters and downpipes |
Roof Coverings
| Measure | Threshold | Source |
|---|---|---|
| Sheet roofing end laps | At least 150 mm above 15 degrees; 200 mm from 5 to 15 degrees | NCC 2025 Housing Provisions, Part 7.2 Sheet roofing |
| Sarking under tiles | Laps at least 150 mm; fixed at no more than 300 mm centres; sags no deeper than 40 mm | NCC 2025 Housing Provisions, Part 7.3 Roof tiles and shingles |
Roof Safety Systems
| Measure | Threshold | Source |
|---|---|---|
| Roof edge barrier | At least 1 m high where a roof with general access is 1 m or more above the surface below | NCC 2025 Volume One, Part D3 Construction of exits, D3D17 |
Waterproofing Membranes
| Measure | Threshold | Source |
|---|---|---|
| Minimum fall, external membranes | 1 in 100 (10 mm per metre) | AS 4654.2-2012 Waterproofing membranes for external above-ground use, Part 2: Design and installation |
Internal Areas
Bathrooms & Wet Areas
| Measure | Threshold | Source |
|---|---|---|
| Hot water at sanitary fixtures | No more than 45 °C in aged care, healthcare, early childhood centres and schools; 50 °C in most other buildings | NCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services |
Common Circulation Areas
| Measure | Threshold | Source |
|---|---|---|
| Travel distance, Class 5 to 9 | No more than 20 m to an exit or point of choice, and no more than 40 m to one of two exits | NCC 2025 Volume One, Part D2 Provision for escape, D2D5 |
| Apartment entry doors to an exit | Within 6 m of an exit or point of choice | NCC 2025 Volume One, Part D2 Provision for escape, D2D5 |
| Fire door gaps (AS 1905.1) | 3 mm at the top and sides; no more than 10 mm at the bottom | Fire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source) |
Common Internal Areas
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (AS 1905.1) | 3 mm at the top and sides; no more than 10 mm at the bottom | Fire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source) |
Electrical & Communications Risers
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (AS 1905.1) | 3 mm at the top and sides; no more than 10 mm at the bottom | Fire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source) |
Fireplaces
| Measure | Threshold | Source |
|---|---|---|
| Hearth extent, open fireplaces | At least 300 mm in front of the opening and 150 mm beyond each side | NCC 2025 Housing Provisions, Part 12.4 Heating appliances, fireplaces, chimneys and flues |
| Chimney or flue terminal height | At least 300 mm above any part of the building within 3.6 m horizontally | NCC 2025 Housing Provisions, Part 12.4 Heating appliances, fireplaces, chimneys and flues |
Integrated Building Systems
| Measure | Threshold | Source |
|---|---|---|
| Stair pressurisation (AS 1668.1) | Door opening force at the handle no more than 110 N; air flowing through open stair doors at 1 m/s | Stair pressurisation performance in high-rise buildings (Fire, 2023, 6(4), 132) (quoted by a secondary source) |
| Alarm level at unit entry doors (Class 2 and 3) | 85 dB(A) with a smoke alarm system, or 100 dB(A) with a smoke detection system | NCC 2025 Volume One, Specification 20 Smoke detection and alarm systems |
Internal Doors & Hardware
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (AS 1905.1) | 3 mm at the top and sides; no more than 10 mm at the bottom | Fire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source) |
Internal Stairwells
| Measure | Threshold | Source |
|---|---|---|
| Risers and goings, public stairs | Risers 115 to 190 mm and goings 250 to 355 mm, constant through each flight; 2R + G between 550 and 700 mm; no more than 18 risers a flight | NCC 2025 Volume One, Part D3 Construction of exits, D3D14 |
| Handrails | On at least one side, and on both sides where the stair is 2 m wide or more; at least 865 mm above the nosings; continuous between landings | NCC 2025 Volume One, Part D3 Construction of exits, D3D22 |
| Barrier height | At least 865 mm above the nosings on a flight, and 1 m at landings and floors | NCC 2025 Volume One, Part D3 Construction of exits, D3D17 |
| Openings between treads | Risers must not let a 125 mm sphere pass between treads | NCC 2025 Volume One, Part D3 Construction of exits, D3D19 |
| Fire door gaps (AS 1905.1) | 3 mm at the top and sides; no more than 10 mm at the bottom | Fire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source) |
Kitchen
| Measure | Threshold | Source |
|---|---|---|
| Hot water at sanitary fixtures | No more than 45 °C in aged care, healthcare, early childhood centres and schools; 50 °C in most other buildings | NCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services |
Lobbies & Atria
| Measure | Threshold | Source |
|---|---|---|
| Barriers at upper levels | At least 1 m high where the floor is 1 m or more above the level below; openings that will not pass a 125 mm sphere | NCC 2025 Volume One, Part D3 Construction of exits |
Public Amenities
| Measure | Threshold | Source |
|---|---|---|
| Hot water at sanitary fixtures | No more than 45 °C in aged care, healthcare, early childhood centres and schools; 50 °C in most other buildings | NCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services |
Residential Units/Guest Rooms
| Measure | Threshold | Source |
|---|---|---|
| Alarm level at unit entry doors (Class 2 and 3) | 85 dB(A) with a smoke alarm system, or 100 dB(A) with a smoke detection system | NCC 2025 Volume One, Specification 20 Smoke detection and alarm systems |
| Hot water at sanitary fixtures | No more than 45 °C in aged care, healthcare, early childhood centres and schools; 50 °C in most other buildings | NCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services |
Service Corridors
| Measure | Threshold | Source |
|---|---|---|
| Travel distance, Class 5 to 9 | No more than 20 m to an exit or point of choice, and no more than 40 m to one of two exits | NCC 2025 Volume One, Part D2 Provision for escape, D2D5 |
Specialised Occupancy Areas
| Measure | Threshold | Source |
|---|---|---|
| Fume cupboard face velocity (AS/NZS 2243.8) | Average of 0.5 m/s, with no reading below 0.3 m/s; tested at least every 12 months | Local exhaust ventilation (LEV) |
Specialist & Non-Standard Features
| Measure | Threshold | Source |
|---|---|---|
| Pool barriers (Queensland) | At least 1200 mm high; no more than 100 mm under the barrier; a 900 mm non-climbable zone; 300 mm clear inside; boundary fences used as barriers at least 1800 mm | Pool fences: requirements for pool barriers |
External Elements
Fencing, Gates & Signage
| Measure | Threshold | Source |
|---|---|---|
| Pool barriers (Queensland) | At least 1200 mm high; no more than 100 mm under the barrier; a 900 mm non-climbable zone; 300 mm clear inside | Pool fences: requirements for pool barriers |
Mechanical Services
Central Cooling Plant
| Measure | Threshold | Source |
|---|---|---|
| R22 supply | From 1 January 2020, bulk R22 imports may only service existing equipment, within about 45 tonnes (45,000 kg) a year until 2029; from 1 January 2030 imports are banned and servicing relies on reclaimed refrigerant | R22 phase out fact sheet |
Ventilation Systems
| Measure | Threshold | Source |
|---|---|---|
| Fume cupboard face velocity (AS/NZS 2243.8) | Average of 0.5 m/s, with no reading below 0.3 m/s; tested at least every 12 months | Local exhaust ventilation (LEV): WorkSafe Queensland guidance |
Electrical Services
Emergency Lighting
| Measure | Threshold | Source |
|---|---|---|
| Rated duration | Typically 90 minutes | AS/NZS 2293.1:2026 Emergency lighting and exit signs for buildings, Part 1: System design, installation and operation |
| Where emergency lighting is required | Every path of travel on a storey over 300 m²; rooms over 100 m² that do not open to a lit corridor or open space; rooms over 300 m² | NCC 2025 Volume One, Part E4 Visibility in an emergency, exit signs and warning systems, E4D2 |
Lighting Control System
| Measure | Threshold | Source |
|---|---|---|
| Area per lighting control | No more than 250 m² of lighting per demand-operated control, other than in a single functional space | NCC 2025 Volume One, Part J7 Artificial lighting and power |
| Daylight zone control | Separate control of the natural lighting zone in Class 5, 6 or 8 buildings over 250 m² | NCC 2025 Volume One, Part J7 Artificial lighting and power |
| Time switches | Only where a space is regularly occupied: more than 1 person per 40 m², or used more than once every 15 minutes | NCC 2025 Volume One, Part J7 Artificial lighting and power |
Power Distribution
| Measure | Threshold | Source |
|---|---|---|
| Fixed RCD testing (Victoria, after AS/NZS 3760) | Push-button test every 6 months; operating-time test every 12 months in high and medium risk areas, every 2 years in low risk areas | Electrical safety (inspection and testing timeframes) |
Fire Services
Automatic Sprinkler Systems
| Measure | Threshold | Source |
|---|---|---|
| When sprinklers are required | Throughout a building where any part has an effective height of more than 25 m; new apartment buildings of four storeys and more since the 2019 amendments | NCC 2025 Volume One, Part E1 Fire fighting equipment, E1D5 |
Fire Detection & Alarm Systems
| Measure | Threshold | Source |
|---|---|---|
| Alarm level at unit entry doors (Class 2 and 3) | 85 dB(A) at the entry door with a smoke alarm system, or 100 dB(A) with a smoke detection system, in place of measuring inside the unit | NCC 2025 Volume One, Specification 20 Smoke detection and alarm systems |
Fire Pumping Systems
| Measure | Threshold | Source |
|---|---|---|
| Boosted hydrant pressure (New South Wales, AS 2419.1:2021) | 700 kPa at the most hydraulically disadvantaged outlet in each pressure zone | Position statement summary: FRNSW pump performance for high rise buildings (quoted by a secondary source) |
Hydrant & Hose Reel Systems
| Measure | Threshold | Source |
|---|---|---|
| Boosted hydrant pressure (AS 2419.1:2021, as applied in New South Wales) | 700 kPa at the most disadvantaged outlet | Position statement summary: FRNSW pump performance for high rise buildings (quoted by a secondary source) |
| Unassisted residual pressure at a feed hydrant flowing 10 L/s (AS 2419.1) | 150 kPa in New South Wales; 200 kPa in the other states and territories | Fire and Rescue NSW fire hydrant testing 2017 (report MHL2534) (quoted by a secondary source) |
| Hose reels | Within 4 m of an exit; a hose reel system serves any fire compartment over 500 m² without internal hydrants | NCC 2025 Volume One, Part E1 Fire fighting equipment |
Passive Fire Protection
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (AS 1905.1) | 3 mm at the top and sides; no more than 10 mm at the bottom | Fire door intumescent seal regulations (quoting AS 1905.1 clearances) (quoted by a secondary source) |
| Smoke door leaves | Solid-core leaves at least 35 mm thick, or leaves able to resist smoke at 200 °C for 30 minutes, with smoke seals | NCC 2025 Volume One, Specification 12 Fire doors, smoke doors, fire windows and shutters |
Portable Fire Equipment
| Measure | Threshold | Source |
|---|---|---|
| Extinguishers in apartment buildings | An ABE extinguisher of at least 2.5 kg within 10 m of each unit’s entry door | NCC 2025 Volume One, Part E1 Fire fighting equipment |
Smoke Management Systems
| Measure | Threshold | Source |
|---|---|---|
| Stair pressurisation (AS 1668.1) | Door opening force at the handle no more than 110 N; air flowing through open stair doors at 1 m/s | Stair pressurisation performance in high-rise buildings (Fire, 2023, 6(4), 132) (quoted by a secondary source) |
Hydraulic Services
Hot & Warm Water Plant
| Measure | Threshold | Source |
|---|---|---|
| Hot water at sanitary fixtures | No more than 45 °C in aged care, healthcare patient areas, early childhood centres and schools; 50 °C in most other cases | NCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services |
| Storage heater relief | Rated working pressure, or 1400 kPa if lower, not exceeded; water kept below 99 °C | NCC 2025 Volume Three (Plumbing Code), Part B2 Heated water services |
Pumping Systems
| Measure | Threshold | Source |
|---|---|---|
| Water pressure | Working pressure at least 50 kPa at outlets; static pressure no more than 500 kPa within the building | NCC 2025 Volume Three (Plumbing Code), Part B1 Cold water services, B1P6 |
Specialist Hydraulics
| Measure | Threshold | Source |
|---|---|---|
| Pool barriers (Queensland) | At least 1200 mm high; no more than 100 mm under the barrier; a 900 mm non-climbable zone; 300 mm clear inside; boundary fences used as barriers at least 1800 mm | Pool fences: requirements for pool barriers |
Water Supply
| Measure | Threshold | Source |
|---|---|---|
| Water pressure | Working pressure at least 50 kPa at outlets; static pressure no more than 500 kPa within the building | NCC 2025 Volume Three (Plumbing Code), Part B1 Cold water services, B1P6 |
Vertical Transportation
Accessibility Lifts
| Measure | Threshold | Source |
|---|---|---|
| Travel limits by lift type | Low-rise platform lift: no more than 1000 mm; low-rise, low-speed constant pressure lift: no more than 2 m unenclosed or 4 m enclosed | NCC 2025 Volume One, Part E3 Lift installations, E3D7 |
Passenger & Goods Lifts
| Measure | Threshold | Source |
|---|---|---|
| Stretcher-sized lift | Where lifts serve storeys above an effective height of 12 m, at least one takes a raised stretcher in a space 600 mm by 2000 mm by 1400 mm high | NCC 2025 Volume One, Part E3 Lift installations, E3D3 |
Building Code Compliance
Occupational Health & Safety (OHS)
| Measure | Threshold | Source |
|---|---|---|
| Risers and goings, public stairs | Risers 115 to 190 mm; goings 250 to 355 mm | NCC 2025 Volume One, Part D3 Construction of exits, D3D14 |
Environmental
Electric Vehicle (EV) Charging
| Measure | Threshold | Source |
|---|---|---|
| EV charging readiness in car parks | Dedicated EV boards on each storey, sized for future 7 kW (32 A) chargers in 10 per cent of spaces (Class 5 and 6) or 20 per cent (Class 3, 7b, 8 and 9) | NCC 2025 Volume One, Part J9 Energy monitoring and on-site distributed energy resources, J9D4 |
| Sub-metering space on EV boards | At least 36 mm of DIN rail per circuit | NCC 2025 Volume One, Part J9 Energy monitoring and on-site distributed energy resources, J9D4 |
Sub-metering
| Measure | Threshold | Source |
|---|---|---|
| Energy metering | Over 500 m²: time-of-use metering of gas and electricity; over 2500 m²: separate meters for air conditioning, lighting, appliance power, central hot water and lifts | NCC 2025 Volume One, Part J9 Energy monitoring and on-site distributed energy resources, J9D3 |