Every measured value the Technical Library records for the United States: 70 thresholds across 47 elements and spaces, each with the code or standard it comes from. Each element’s name opens its own page, where the value sits with how the element fails and what fixes it.

Superstructure

Structural Frame

MeasureThresholdSource
Floor imposed loads (IBC Table 1607.1, as adopted in Massachusetts)Offices 50 psf (2.4 kPa); corridors above the first floor 80 psf (3.8 kPa); light storage 125 psf (6.0 kPa)780 CMR Table 1607.1 Minimum uniformly distributed live loads (Massachusetts State Building Code, adopting the IBC table) (quoted by a secondary source)

Upper Floor Slabs & Structures

MeasureThresholdSource
Floor imposed loads (IBC Table 1607.1, as adopted in Massachusetts)Offices 50 psf (2.4 kPa); corridors above the first floor 80 psf (3.8 kPa); light storage 125 psf (6.0 kPa)780 CMR Table 1607.1 Minimum uniformly distributed live loads (Massachusetts State Building Code, adopting the IBC table) (quoted by a secondary source)

Façades

Building Maintenance Units (BMU)

MeasureThresholdSource
Inspection intervals (powered platforms)Supporting building structure: at intervals not exceeding 12 months; equipment: at the manufacturer’s intervals, not exceeding 12 months1910.66 Powered platforms for building maintenance
Roof perimeter guard and davitsGuard no more than 152 mm (6 in) inboard of the parapet or curb; setback no more than 457 mm (18 in); davits over 36 kg moved with their centre of gravity at or below 914 mm1910.66 Powered platforms for building maintenance

External Coating Systems

MeasureThresholdSource
Lead-based paintLead at or above 1.0 mg/cm² by XRF, or 0.5 per cent by weight in a laboratory sample24 CFR 35.86 Definitions (lead-based paint)

Sealants & Joints

MeasureThresholdSource
PCBs in caulkCaulk installed between 1950 and 1979 can contain as much as 40 per cent PCBsPolychlorinated biphenyls (PCBs) in building materials

Roofs & Rainwater Goods

Plant Screens & Parapets

MeasureThresholdSource
Guardrails (workplaces)1070 mm (42 in) high, plus or minus 75 mm; resisting 890 N29 CFR 1910.29 Fall protection systems and falling object protection criteria

Roof Safety Systems

MeasureThresholdSource
Guardrails (workplaces)1070 mm (42 in) high, plus or minus 75 mm; resisting 890 N29 CFR 1910.29 Fall protection systems and falling object protection criteria
Personal fall arrest (workplaces)Free fall no more than 1.8 m; deceleration distance no more than 1.1 m; arresting force no more than 8 kN; anchorage holding 22.2 kN per person attached29 CFR 1910.140 Personal fall protection systems
Fixed ladders needing fall protectionOver 7.3 m (24 ft): a ladder safety or personal fall arrest systemWalking-working surfaces and fall protection

Waterproofing Membranes

MeasureThresholdSource
Minimum slope, most membranesAbout a quarter inch per foot (about 21 mm per metre, roughly 1 in 50)2024 International Building Code

Internal Areas

Commercial Kitchens

MeasureThresholdSource
Carbon monoxide, workplace exposure50 ppm averaged over 8 hours29 CFR 1910.1000 Air contaminants (Table Z-1)

Common Circulation Areas

MeasureThresholdSource
Fire door gaps (NFPA 80)About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottomMeasuring door gaps around and under fire doors (quoted by a secondary source)

Common Internal Areas

MeasureThresholdSource
Fire door gaps (NFPA 80)About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottomMeasuring door gaps around and under fire doors (quoted by a secondary source)

Electrical & Communications Risers

MeasureThresholdSource
Fire door gaps (NFPA 80)About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottomMeasuring door gaps around and under fire doors (quoted by a secondary source)
Working space in front of electrical equipmentAt least 0.9 m deep and 762 mm wide (or the width of the equipment), with 1.98 m of headroom, for equipment up to 150 V to ground29 CFR 1910.303 Electrical: General

Fireplaces

MeasureThresholdSource
Carbon monoxide, workplace exposure50 ppm averaged over 8 hours29 CFR 1910.1000 Air contaminants (Table Z-1)

Flooring

MeasureThresholdSource
Changes in levelUp to 6.4 mm may be vertical; 6.4 to 13 mm bevelled no steeper than 1:22010 ADA Standards for Accessible Design, 303

Integrated Building Systems

MeasureThresholdSource
Alarm level, public modeAt least 15 dB above the average ambient levelAudibility vs. intelligibility of fire alarm systems (FPE Extra, issue 69) (quoted by a secondary source)

Internal Doors & Hardware

MeasureThresholdSource
Fire door gaps (NFPA 80)About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottomMeasuring door gaps around and under fire doors (quoted by a secondary source)
Opening force, interior hinged doorsNo more than 22.2 N (5 lbf); fire doors excepted2010 ADA Standards for Accessible Design, 404.2.9

Internal Stairwells

MeasureThresholdSource
Fire door gaps (NFPA 80)About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottomMeasuring door gaps around and under fire doors (quoted by a secondary source)

Internal Wall & Ceiling Finishes

MeasureThresholdSource
Lead-based paintLead at or above 1.0 mg/cm² by XRF, or 0.5 per cent by weight in a laboratory sample24 CFR 35.86 Definitions (lead-based paint)

Lift Cars & Machine Rooms

MeasureThresholdSource
Levelling and sill gapWithin 13 mm from rated load to no load; no more than 32 mm between car sill and landing2010 ADA Standards for Accessible Design, 407.4
Car lightingAt least 54 lux at the car controls, platform and threshold2010 ADA Standards for Accessible Design, 407.4.5

Loading Docks & Goods Handling

MeasureThresholdSource
Carbon monoxide, workplace exposure50 ppm averaged over 8 hours29 CFR 1910.1000 Air contaminants (Table Z-1)

Main Entrance & Reception Areas

MeasureThresholdSource
Opening force, interior doorsNo more than 22.2 N2010 ADA Standards for Accessible Design, 404.2.9
Door clear widthAt least 815 mm with the door open 90 degrees2010 ADA Standards for Accessible Design, 404.2.3
Changes in levelUp to 6.4 mm may be vertical; 6.4 to 13 mm bevelled no steeper than 1:22010 ADA Standards for Accessible Design, 303

Maintenance Access Areas

MeasureThresholdSource
Fixed ladder rungs25 to 36 cm (10 to 14 in) apart; at least 41 cm (16 in) wide29 CFR 1910.23 Ladders
Guardrails (workplaces)1070 mm (42 in) high, plus or minus 75 mm29 CFR 1910.29 Fall protection systems and falling object protection criteria
Hydrogen sulfide, workplace exposureCeiling of 20 ppm; a single peak of 50 ppm for no more than 10 minutes29 CFR 1910.1000 Air contaminants (Table Z-1), Table Z-2

Plant Rooms

MeasureThresholdSource
Refrigerant leak repair triggerComfort cooling appliances with 50 lb (about 23 kg) or more of ozone-depleting refrigerant: repair when leaking more than 10 per cent a year40 CFR 82.157 Appliance maintenance and leak repair
Working space in front of electrical equipmentAt least 762 mm (30 in) wide and, at the lowest voltage class, 0.9 m (3 ft) deep29 CFR 1910.303 Electrical: General
Fixed ladder rungs25 to 36 cm (10 to 14 in) apart; at least 41 cm (16 in) wide29 CFR 1910.23 Ladders

Retail Tenancies (Base-Build)

MeasureThresholdSource
Clearance below sprinkler deflectorsAt least 457 mm (18 in) to the top of storage29 CFR 1910.159 Automatic sprinkler systems

Service Corridors

MeasureThresholdSource
Clearance below sprinkler deflectorsAt least 457 mm (18 in) to the top of storage29 CFR 1910.159 Automatic sprinkler systems

Storage & Archive Areas

MeasureThresholdSource
Floor imposed loads (IBC Table 1607.1, as adopted in Massachusetts)Offices 50 psf (2.4 kPa); light storage 125 psf (6.0 kPa)780 CMR Table 1607.1 Minimum uniformly distributed live loads (Massachusetts State Building Code, adopting the IBC table) (quoted by a secondary source)
Clearance below sprinkler deflectorsAt least 457 mm (18 in) to the top of storage29 CFR 1910.159 Automatic sprinkler systems

External Elements

Fencing, Gates & Signage

MeasureThresholdSource
Doors and gates on accessible routesAt least 815 mm clear; no more than 22.2 N to open (interior)2010 ADA Standards for Accessible Design, 404

Pavements & Hardstand

MeasureThresholdSource
Changes in levelUp to 6.4 mm may be vertical; 6.4 to 13 mm bevelled no steeper than 1:2; higher changes are treated as a ramp or step2010 ADA Standards for Accessible Design, 303
Accessible car spacesAt least 2440 mm wide, with an adjacent access aisle2010 ADA Standards for Accessible Design, 502

Mechanical Services

Central Cooling Plant

MeasureThresholdSource
Refrigerant leak repair triggerAppliances holding 50 lb (about 23 kg) or more of ozone-depleting refrigerant: repair when leaking more than 10 per cent a year for comfort cooling, 20 per cent for commercial refrigeration, 30 per cent for industrial process refrigeration40 CFR 82.157 Appliance maintenance and leak repair

Ductwork & Air Distribution

MeasureThresholdSource
Fire and smoke damper testingOne year after construction, then every 6 yearsUFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026)

Localised HVAC

MeasureThresholdSource
Refrigerant leak repair triggerAppliances holding 50 lb (about 23 kg) or more of ozone-depleting refrigerant: repair when leaking more than 10 per cent a year for comfort cooling, 20 per cent for commercial refrigeration, 30 per cent for industrial process refrigeration40 CFR 82.157 Appliance maintenance and leak repair

Ventilation Systems

MeasureThresholdSource
Carbon monoxide, workplace exposure50 ppm averaged over 8 hours29 CFR 1910.1000 Air contaminants (Table Z-1)

Electrical Services

Emergency Lighting

MeasureThresholdSource
Full-duration testBattery units run for at least 90 minutes each yearUFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026)

Main Electrical Supply

MeasureThresholdSource
Working space in front of electrical equipmentAt least 762 mm (30 in) wide and, at the lowest voltage class, 0.9 m (3 ft) deep29 CFR 1910.303 Electrical: General

Fire Services

Automatic Sprinkler Systems

MeasureThresholdSource
Clearance below sprinkler deflectorsAt least 457 mm (18 in) to the top of storage29 CFR 1910.159 Automatic sprinkler systems
Main drain test declineMore than 10 per cent below the previous reading: evaluate immediately; more than 20 per cent: treat as an emergencyUFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026)
Test intervalsMain drain flow test every 12 months; inspector’s test valve opened at least every 2 years29 CFR 1910.159 Automatic sprinkler systems

Fire Detection & Alarm Systems

MeasureThresholdSource
Alarm level, public modeAt least 15 dB above the average ambient level; 75 dB(A) at the pillow in sleeping roomsAudibility vs. intelligibility of fire alarm systems (FPE Extra, issue 69) (quoted by a secondary source)

Fire Pumping Systems

MeasureThresholdSource
Weekly pump runElectric pumps 10 minutes; engine-driven pumps 30 minutesUFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026)
Flow test declineMore than 10 per cent below the previous or acceptance reading: evaluate immediately; more than 20 per cent: emergencyUFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026)

Passive Fire Protection

MeasureThresholdSource
Fire door gaps (NFPA 80)About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottomMeasuring door gaps around and under fire doors (quoted by a secondary source)
Fire door inspection (NFPA 80)Every 12 monthsMeasuring door gaps around and under fire doors (quoted by a secondary source)

Portable Fire Equipment

MeasureThresholdSource
Travel distance to an extinguisher (workplaces)22.9 m for Class A hazards; 15.2 m for Class B29 CFR 1910.157 Portable fire extinguishers

Specialist Suppression Systems

MeasureThresholdSource
Clean agent hold time (NFPA 2001)At least 10 minutes, or long enough for trained personnel to respond; end of hold commonly taken at 80 per cent of the minimum design concentrationClean agent enclosure design (FPE Extra, issue 74) (quoted by a secondary source)
Halocarbon discharge time (NFPA 2001)About 10 secondsLeakage rates and hold times for clean agent fire suppression enclosures (quoted by a secondary source)

Hydraulic Services

Pumping Systems

MeasureThresholdSource
Hydrogen sulfide, workplace exposureCeiling of 20 ppm; a single peak of 50 ppm for no more than 10 minutes29 CFR 1910.1000 Air contaminants (Table Z-1), Table Z-2

Vertical Transportation

Accessibility Lifts

MeasureThresholdSource
Levelling and sill gapWithin 13 mm (1/2 in) of the landing from rated load to no load; no more than 32 mm between car sill and landing2010 ADA Standards for Accessible Design, 407.4

Escalators & Moving Walks

MeasureThresholdSource
Rated speed at a 30° incline (ASME A17.1)Up to 0.5 m/sInnovative technologies that improve escalator passenger safety (Symposium on Lift and Escalator Technologies) (quoted by a secondary source)

Passenger & Goods Lifts

MeasureThresholdSource
Levelling and sill gapWithin 13 mm (1/2 in) of the landing from rated load to no load; no more than 32 mm between car sill and landing2010 ADA Standards for Accessible Design, 407.4
Car lightingAt least 54 lux at the car controls, platform and threshold2010 ADA Standards for Accessible Design, 407.4.5

Building Code Compliance

Disabled Access (DDA)

MeasureThresholdSource
Door clear widthAt least 815 mm with the door open 90 degrees2010 ADA Standards for Accessible Design, 404.2.3
Opening force, interior doorsNo more than 22.2 N2010 ADA Standards for Accessible Design, 404.2.9
Ramps and changes in levelRamps no steeper than 1:12; level changes up to 6.4 mm vertical, 6.4 to 13 mm bevelled no steeper than 1:22010 ADA Standards for Accessible Design, 303 and 405

Hazardous Materials

MeasureThresholdSource
Lead-based paintLead at or above 1.0 mg/cm², or 0.5 per cent by weight24 CFR 35.86 Definitions (lead-based paint)

Occupational Health & Safety (OHS)

MeasureThresholdSource
Guardrails (workplaces)1070 mm (42 in) high, plus or minus 75 mm29 CFR 1910.29 Fall protection systems and falling object protection criteria
Fixed ladder rungs25 to 36 cm (10 to 14 in) apart; at least 41 cm (16 in) wide29 CFR 1910.23 Ladders