Every measured value the Technical Library records for the United States: 70 thresholds across 47 elements and spaces, each with the code or standard it comes from. Each element’s name opens its own page, where the value sits with how the element fails and what fixes it.
Superstructure
Structural Frame
| Measure | Threshold | Source |
|---|---|---|
| Floor imposed loads (IBC Table 1607.1, as adopted in Massachusetts) | Offices 50 psf (2.4 kPa); corridors above the first floor 80 psf (3.8 kPa); light storage 125 psf (6.0 kPa) | 780 CMR Table 1607.1 Minimum uniformly distributed live loads (Massachusetts State Building Code, adopting the IBC table) (quoted by a secondary source) |
Upper Floor Slabs & Structures
| Measure | Threshold | Source |
|---|---|---|
| Floor imposed loads (IBC Table 1607.1, as adopted in Massachusetts) | Offices 50 psf (2.4 kPa); corridors above the first floor 80 psf (3.8 kPa); light storage 125 psf (6.0 kPa) | 780 CMR Table 1607.1 Minimum uniformly distributed live loads (Massachusetts State Building Code, adopting the IBC table) (quoted by a secondary source) |
Façades
Building Maintenance Units (BMU)
| Measure | Threshold | Source |
|---|---|---|
| Inspection intervals (powered platforms) | Supporting building structure: at intervals not exceeding 12 months; equipment: at the manufacturer’s intervals, not exceeding 12 months | 1910.66 Powered platforms for building maintenance |
| Roof perimeter guard and davits | Guard no more than 152 mm (6 in) inboard of the parapet or curb; setback no more than 457 mm (18 in); davits over 36 kg moved with their centre of gravity at or below 914 mm | 1910.66 Powered platforms for building maintenance |
External Coating Systems
| Measure | Threshold | Source |
|---|---|---|
| Lead-based paint | Lead at or above 1.0 mg/cm² by XRF, or 0.5 per cent by weight in a laboratory sample | 24 CFR 35.86 Definitions (lead-based paint) |
Sealants & Joints
| Measure | Threshold | Source |
|---|---|---|
| PCBs in caulk | Caulk installed between 1950 and 1979 can contain as much as 40 per cent PCBs | Polychlorinated biphenyls (PCBs) in building materials |
Roofs & Rainwater Goods
Plant Screens & Parapets
| Measure | Threshold | Source |
|---|---|---|
| Guardrails (workplaces) | 1070 mm (42 in) high, plus or minus 75 mm; resisting 890 N | 29 CFR 1910.29 Fall protection systems and falling object protection criteria |
Roof Safety Systems
| Measure | Threshold | Source |
|---|---|---|
| Guardrails (workplaces) | 1070 mm (42 in) high, plus or minus 75 mm; resisting 890 N | 29 CFR 1910.29 Fall protection systems and falling object protection criteria |
| Personal fall arrest (workplaces) | Free fall no more than 1.8 m; deceleration distance no more than 1.1 m; arresting force no more than 8 kN; anchorage holding 22.2 kN per person attached | 29 CFR 1910.140 Personal fall protection systems |
| Fixed ladders needing fall protection | Over 7.3 m (24 ft): a ladder safety or personal fall arrest system | Walking-working surfaces and fall protection |
Waterproofing Membranes
| Measure | Threshold | Source |
|---|---|---|
| Minimum slope, most membranes | About a quarter inch per foot (about 21 mm per metre, roughly 1 in 50) | 2024 International Building Code |
Internal Areas
Commercial Kitchens
| Measure | Threshold | Source |
|---|---|---|
| Carbon monoxide, workplace exposure | 50 ppm averaged over 8 hours | 29 CFR 1910.1000 Air contaminants (Table Z-1) |
Common Circulation Areas
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (NFPA 80) | About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottom | Measuring door gaps around and under fire doors (quoted by a secondary source) |
Common Internal Areas
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (NFPA 80) | About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottom | Measuring door gaps around and under fire doors (quoted by a secondary source) |
Electrical & Communications Risers
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (NFPA 80) | About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottom | Measuring door gaps around and under fire doors (quoted by a secondary source) |
| Working space in front of electrical equipment | At least 0.9 m deep and 762 mm wide (or the width of the equipment), with 1.98 m of headroom, for equipment up to 150 V to ground | 29 CFR 1910.303 Electrical: General |
Fireplaces
| Measure | Threshold | Source |
|---|---|---|
| Carbon monoxide, workplace exposure | 50 ppm averaged over 8 hours | 29 CFR 1910.1000 Air contaminants (Table Z-1) |
Flooring
| Measure | Threshold | Source |
|---|---|---|
| Changes in level | Up to 6.4 mm may be vertical; 6.4 to 13 mm bevelled no steeper than 1:2 | 2010 ADA Standards for Accessible Design, 303 |
Integrated Building Systems
| Measure | Threshold | Source |
|---|---|---|
| Alarm level, public mode | At least 15 dB above the average ambient level | Audibility vs. intelligibility of fire alarm systems (FPE Extra, issue 69) (quoted by a secondary source) |
Internal Doors & Hardware
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (NFPA 80) | About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottom | Measuring door gaps around and under fire doors (quoted by a secondary source) |
| Opening force, interior hinged doors | No more than 22.2 N (5 lbf); fire doors excepted | 2010 ADA Standards for Accessible Design, 404.2.9 |
Internal Stairwells
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (NFPA 80) | About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottom | Measuring door gaps around and under fire doors (quoted by a secondary source) |
Internal Wall & Ceiling Finishes
| Measure | Threshold | Source |
|---|---|---|
| Lead-based paint | Lead at or above 1.0 mg/cm² by XRF, or 0.5 per cent by weight in a laboratory sample | 24 CFR 35.86 Definitions (lead-based paint) |
Lift Cars & Machine Rooms
| Measure | Threshold | Source |
|---|---|---|
| Levelling and sill gap | Within 13 mm from rated load to no load; no more than 32 mm between car sill and landing | 2010 ADA Standards for Accessible Design, 407.4 |
| Car lighting | At least 54 lux at the car controls, platform and threshold | 2010 ADA Standards for Accessible Design, 407.4.5 |
Loading Docks & Goods Handling
| Measure | Threshold | Source |
|---|---|---|
| Carbon monoxide, workplace exposure | 50 ppm averaged over 8 hours | 29 CFR 1910.1000 Air contaminants (Table Z-1) |
Main Entrance & Reception Areas
| Measure | Threshold | Source |
|---|---|---|
| Opening force, interior doors | No more than 22.2 N | 2010 ADA Standards for Accessible Design, 404.2.9 |
| Door clear width | At least 815 mm with the door open 90 degrees | 2010 ADA Standards for Accessible Design, 404.2.3 |
| Changes in level | Up to 6.4 mm may be vertical; 6.4 to 13 mm bevelled no steeper than 1:2 | 2010 ADA Standards for Accessible Design, 303 |
Maintenance Access Areas
| Measure | Threshold | Source |
|---|---|---|
| Fixed ladder rungs | 25 to 36 cm (10 to 14 in) apart; at least 41 cm (16 in) wide | 29 CFR 1910.23 Ladders |
| Guardrails (workplaces) | 1070 mm (42 in) high, plus or minus 75 mm | 29 CFR 1910.29 Fall protection systems and falling object protection criteria |
| Hydrogen sulfide, workplace exposure | Ceiling of 20 ppm; a single peak of 50 ppm for no more than 10 minutes | 29 CFR 1910.1000 Air contaminants (Table Z-1), Table Z-2 |
Plant Rooms
| Measure | Threshold | Source |
|---|---|---|
| Refrigerant leak repair trigger | Comfort cooling appliances with 50 lb (about 23 kg) or more of ozone-depleting refrigerant: repair when leaking more than 10 per cent a year | 40 CFR 82.157 Appliance maintenance and leak repair |
| Working space in front of electrical equipment | At least 762 mm (30 in) wide and, at the lowest voltage class, 0.9 m (3 ft) deep | 29 CFR 1910.303 Electrical: General |
| Fixed ladder rungs | 25 to 36 cm (10 to 14 in) apart; at least 41 cm (16 in) wide | 29 CFR 1910.23 Ladders |
Retail Tenancies (Base-Build)
| Measure | Threshold | Source |
|---|---|---|
| Clearance below sprinkler deflectors | At least 457 mm (18 in) to the top of storage | 29 CFR 1910.159 Automatic sprinkler systems |
Service Corridors
| Measure | Threshold | Source |
|---|---|---|
| Clearance below sprinkler deflectors | At least 457 mm (18 in) to the top of storage | 29 CFR 1910.159 Automatic sprinkler systems |
Storage & Archive Areas
| Measure | Threshold | Source |
|---|---|---|
| Floor imposed loads (IBC Table 1607.1, as adopted in Massachusetts) | Offices 50 psf (2.4 kPa); light storage 125 psf (6.0 kPa) | 780 CMR Table 1607.1 Minimum uniformly distributed live loads (Massachusetts State Building Code, adopting the IBC table) (quoted by a secondary source) |
| Clearance below sprinkler deflectors | At least 457 mm (18 in) to the top of storage | 29 CFR 1910.159 Automatic sprinkler systems |
External Elements
Fencing, Gates & Signage
| Measure | Threshold | Source |
|---|---|---|
| Doors and gates on accessible routes | At least 815 mm clear; no more than 22.2 N to open (interior) | 2010 ADA Standards for Accessible Design, 404 |
Pavements & Hardstand
| Measure | Threshold | Source |
|---|---|---|
| Changes in level | Up to 6.4 mm may be vertical; 6.4 to 13 mm bevelled no steeper than 1:2; higher changes are treated as a ramp or step | 2010 ADA Standards for Accessible Design, 303 |
| Accessible car spaces | At least 2440 mm wide, with an adjacent access aisle | 2010 ADA Standards for Accessible Design, 502 |
Mechanical Services
Central Cooling Plant
| Measure | Threshold | Source |
|---|---|---|
| Refrigerant leak repair trigger | Appliances holding 50 lb (about 23 kg) or more of ozone-depleting refrigerant: repair when leaking more than 10 per cent a year for comfort cooling, 20 per cent for commercial refrigeration, 30 per cent for industrial process refrigeration | 40 CFR 82.157 Appliance maintenance and leak repair |
Ductwork & Air Distribution
| Measure | Threshold | Source |
|---|---|---|
| Fire and smoke damper testing | One year after construction, then every 6 years | UFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026) |
Localised HVAC
| Measure | Threshold | Source |
|---|---|---|
| Refrigerant leak repair trigger | Appliances holding 50 lb (about 23 kg) or more of ozone-depleting refrigerant: repair when leaking more than 10 per cent a year for comfort cooling, 20 per cent for commercial refrigeration, 30 per cent for industrial process refrigeration | 40 CFR 82.157 Appliance maintenance and leak repair |
Ventilation Systems
| Measure | Threshold | Source |
|---|---|---|
| Carbon monoxide, workplace exposure | 50 ppm averaged over 8 hours | 29 CFR 1910.1000 Air contaminants (Table Z-1) |
Electrical Services
Emergency Lighting
| Measure | Threshold | Source |
|---|---|---|
| Full-duration test | Battery units run for at least 90 minutes each year | UFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026) |
Main Electrical Supply
| Measure | Threshold | Source |
|---|---|---|
| Working space in front of electrical equipment | At least 762 mm (30 in) wide and, at the lowest voltage class, 0.9 m (3 ft) deep | 29 CFR 1910.303 Electrical: General |
Fire Services
Automatic Sprinkler Systems
| Measure | Threshold | Source |
|---|---|---|
| Clearance below sprinkler deflectors | At least 457 mm (18 in) to the top of storage | 29 CFR 1910.159 Automatic sprinkler systems |
| Main drain test decline | More than 10 per cent below the previous reading: evaluate immediately; more than 20 per cent: treat as an emergency | UFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026) |
| Test intervals | Main drain flow test every 12 months; inspector’s test valve opened at least every 2 years | 29 CFR 1910.159 Automatic sprinkler systems |
Fire Detection & Alarm Systems
| Measure | Threshold | Source |
|---|---|---|
| Alarm level, public mode | At least 15 dB above the average ambient level; 75 dB(A) at the pillow in sleeping rooms | Audibility vs. intelligibility of fire alarm systems (FPE Extra, issue 69) (quoted by a secondary source) |
Fire Pumping Systems
| Measure | Threshold | Source |
|---|---|---|
| Weekly pump run | Electric pumps 10 minutes; engine-driven pumps 30 minutes | UFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026) |
| Flow test decline | More than 10 per cent below the previous or acceptance reading: evaluate immediately; more than 20 per cent: emergency | UFM 3-601-02 Fire protection systems inspection, testing, and maintenance (13 March 2026) |
Passive Fire Protection
| Measure | Threshold | Source |
|---|---|---|
| Fire door gaps (NFPA 80) | About 3 mm (1/8 in) at the head and jambs; up to 19 mm (3/4 in) at the bottom | Measuring door gaps around and under fire doors (quoted by a secondary source) |
| Fire door inspection (NFPA 80) | Every 12 months | Measuring door gaps around and under fire doors (quoted by a secondary source) |
Portable Fire Equipment
| Measure | Threshold | Source |
|---|---|---|
| Travel distance to an extinguisher (workplaces) | 22.9 m for Class A hazards; 15.2 m for Class B | 29 CFR 1910.157 Portable fire extinguishers |
Specialist Suppression Systems
| Measure | Threshold | Source |
|---|---|---|
| Clean agent hold time (NFPA 2001) | At least 10 minutes, or long enough for trained personnel to respond; end of hold commonly taken at 80 per cent of the minimum design concentration | Clean agent enclosure design (FPE Extra, issue 74) (quoted by a secondary source) |
| Halocarbon discharge time (NFPA 2001) | About 10 seconds | Leakage rates and hold times for clean agent fire suppression enclosures (quoted by a secondary source) |
Hydraulic Services
Pumping Systems
| Measure | Threshold | Source |
|---|---|---|
| Hydrogen sulfide, workplace exposure | Ceiling of 20 ppm; a single peak of 50 ppm for no more than 10 minutes | 29 CFR 1910.1000 Air contaminants (Table Z-1), Table Z-2 |
Vertical Transportation
Accessibility Lifts
| Measure | Threshold | Source |
|---|---|---|
| Levelling and sill gap | Within 13 mm (1/2 in) of the landing from rated load to no load; no more than 32 mm between car sill and landing | 2010 ADA Standards for Accessible Design, 407.4 |
Escalators & Moving Walks
| Measure | Threshold | Source |
|---|---|---|
| Rated speed at a 30° incline (ASME A17.1) | Up to 0.5 m/s | Innovative technologies that improve escalator passenger safety (Symposium on Lift and Escalator Technologies) (quoted by a secondary source) |
Passenger & Goods Lifts
| Measure | Threshold | Source |
|---|---|---|
| Levelling and sill gap | Within 13 mm (1/2 in) of the landing from rated load to no load; no more than 32 mm between car sill and landing | 2010 ADA Standards for Accessible Design, 407.4 |
| Car lighting | At least 54 lux at the car controls, platform and threshold | 2010 ADA Standards for Accessible Design, 407.4.5 |
Building Code Compliance
Disabled Access (DDA)
| Measure | Threshold | Source |
|---|---|---|
| Door clear width | At least 815 mm with the door open 90 degrees | 2010 ADA Standards for Accessible Design, 404.2.3 |
| Opening force, interior doors | No more than 22.2 N | 2010 ADA Standards for Accessible Design, 404.2.9 |
| Ramps and changes in level | Ramps no steeper than 1:12; level changes up to 6.4 mm vertical, 6.4 to 13 mm bevelled no steeper than 1:2 | 2010 ADA Standards for Accessible Design, 303 and 405 |
Hazardous Materials
| Measure | Threshold | Source |
|---|---|---|
| Lead-based paint | Lead at or above 1.0 mg/cm², or 0.5 per cent by weight | 24 CFR 35.86 Definitions (lead-based paint) |
Occupational Health & Safety (OHS)
| Measure | Threshold | Source |
|---|---|---|
| Guardrails (workplaces) | 1070 mm (42 in) high, plus or minus 75 mm | 29 CFR 1910.29 Fall protection systems and falling object protection criteria |
| Fixed ladder rungs | 25 to 36 cm (10 to 14 in) apart; at least 41 cm (16 in) wide | 29 CFR 1910.23 Ladders |