Every measured value the Technical Library records for the United Kingdom: 83 thresholds across 55 elements and spaces, each with the code or standard it comes from. Each element’s name opens its own page, where the value sits with how the element fails and what fixes it.

Substructure

Foundations

MeasureThresholdSource
Damage categories (BRE Digest 251)Category 0 under 0.1 mm; 1 up to 1 mm; 2 up to 5 mm; 3 from 5 to 15 mm; 4 from 15 to 25 mm; 5 above 25 mmBRE Digest 251 Assessment of damage in low-rise buildings (revised 1995)

Superstructure

Structural Frame

MeasureThresholdSource
Deflection (Eurocode 2 and former British practice)Sag beyond span/250 impairs appearance; after partitions, deflection may be limited to span/500; brittle finishes damaged at L/500 or 20 mm, whichever is lessDeflection and preliminary vibration effects on structural elements (The Structural Engineer, 89(5), 2011) (quoted by a secondary source)

Upper Floor Slabs & Structures

MeasureThresholdSource
Deflection (Eurocode 2 and former British practice)Sag beyond span/250 impairs appearance; after partitions, deflection may be limited to span/500; brittle finishes damaged at L/500 or 20 mm, whichever is lessDeflection and preliminary vibration effects on structural elements (The Structural Engineer, 89(5), 2011) (quoted by a secondary source)

Façades

Cladding & Wall Systems

MeasureThresholdSource
External wall surfaces, residential buildings (England)Class A2-s1, d0 or better where a storey is more than 11 m above groundApproved Document B, Volume 1: Dwellings (2026 online version), Table 10.1

Glazing Systems

MeasureThresholdSource
Critical locations for glazing (England)Below 800 mm in windows; up to 1500 mm in doors and in side panels within 300 mm of a doorApproved Document K (2013 edition incorporating 2016 and 2020 amendments)

Masonry/Brickwork

MeasureThresholdSource
Damage categories (BRE Digest 251)Category 0 under 0.1 mm; 1 up to 1 mm; 2 up to 5 mm; 3 from 5 to 15 mm; 4 from 15 to 25 mm; 5 above 25 mmBRE Digest 251 Assessment of damage in low-rise buildings (revised 1995)

Verandahs, Balconies & Balustrades

MeasureThresholdSource
Balcony guarding (England)At least 1100 mm high; no openings that pass a 100 mm sphereApproved Document K (2013 edition incorporating 2016 and 2020 amendments)

Roofs & Rainwater Goods

Chimney Stacks & Flues

MeasureThresholdSource
Kitchen extract grease (TR19 Grease)Deposits of no more than 200 microns; cleaning every 3, 6 or 12 months for heavy, moderate or light useVentilation hygiene standards (TR19)

Plant Screens & Parapets

MeasureThresholdSource
Roof edge guarding (England)At least 1100 mm highApproved Document K (2013 edition incorporating 2016 and 2020 amendments)

Roof Safety Systems

MeasureThresholdSource
Roof edge guarding (England)At least 1100 mm highApproved Document K (2013 edition incorporating 2016 and 2020 amendments)

Waterproofing Membranes

MeasureThresholdSource
Minimum finished fall, flat roofs1 in 80 (12.5 mm per metre)BS 6229:2025 Flat roofs with continuously supported flexible waterproof coverings

Internal Areas

Bathrooms & Wet Areas

MeasureThresholdSource
Bathroom extract (England, dwellings)At least 15 L/s run intermittently, or 8 L/s on a continuous system’s high rateApproved Document F, Volume 1: Dwellings (2021 edition), Table 1.1 and 1.2
Hot water temperatures (Legionella control)Stored at 60 °C or more; 50 °C at outlets within one minute (55 °C in healthcare)HSG274 Legionnaires’ disease: Technical guidance, Part 2: Hot and cold water systems

Commercial Kitchens

MeasureThresholdSource
Hot water temperatures (Legionella control)Stored at 60 °C or more; 50 °C at outlets within one minute (55 °C in healthcare)HSG274 Legionnaires’ disease: Technical guidance, Part 2: Hot and cold water systems
Grease in kitchen extract ductwork (TR19 Grease)Deposits of no more than 200 micronsVentilation hygiene standards (TR19)

Commercial Office Areas (Base-Build)

MeasureThresholdSource
Outside air, offices (England)10 L/s per personApproved Document F, Volume 2: Buildings other than dwellings
Carbon dioxide in occupied spacesBelow 800 ppm suggests good ventilation; consistently above 1500 ppm calls for actionApproved Document F, Volume 2: Buildings other than dwellings
Lighting at desksAverage 200 lux, with no point below 100 luxLighting at work (HSG38)
Workroom temperatureUsually at least 16 °CTemperature in the workplace: managing

Common Circulation Areas

MeasureThresholdSource
Fire door gaps (England)No more than 4 mm, except at the bottomFire Safety (England) Regulations 2022: fire door guidance
Fire door checks (England, storey over 11 m)Communal fire doors at least every 3 months; flat entrance doors every 12 monthsFire Safety (England) Regulations 2022: fire door guidance
Corridor smoke vent free area (England)At least 1.5 m² on an external wall, or 1 m² into a smoke shaftApproved Document B, Volume 1: Dwellings (2026 online version)

Common Internal Areas

MeasureThresholdSource
Fire door gaps (England)No more than 4 mm, except at the bottomFire Safety (England) Regulations 2022: fire door guidance
Fire door checks (England, storey over 11 m)Communal fire doors at least every 3 months; flat entrance doors every 12 monthsFire Safety (England) Regulations 2022: fire door guidance

Electrical & Communications Risers

MeasureThresholdSource
Fire door gaps (England)No more than 4 mm, except at the bottomFire Safety (England) Regulations 2022: fire door guidance

Flooring

MeasureThresholdSource
Separating floors in flats (England)New build: airborne at least 45 dB, impact no more than 62 dB; conversions: 43 dB and 64 dBApproved Document E (2003 edition incorporating 2004, 2010, 2013 and 2015 amendments), Table 1.1

Integrated Building Systems

MeasureThresholdSource
Alarm level in sleeping rooms75 dB(A) at the bedheadFire safety risk assessment: sleeping accommodation

Internal Doors & Hardware

MeasureThresholdSource
Fire door gaps (England)No more than 4 mm, except at the bottomFire Safety (England) Regulations 2022: fire door guidance
Opening force at the leading edge (England)No more than 30 N from closed to 30° open, and 22.5 N from 30° to 60°Approved Document M, Volume 2: Buildings other than dwellings (with 2024 amendments)

Internal Stairwells

MeasureThresholdSource
Rise and going, general access stairs (England)Rises 150 to 170 mm and goings 250 to 400 mmApproved Document K (2013 edition incorporating 2016 and 2020 amendments)
Handrail height (England)900 to 1000 mm above the pitch lineApproved Document K (2013 edition incorporating 2016 and 2020 amendments)
Fire door gaps (England)No more than 4 mm, except at the bottomFire Safety (England) Regulations 2022: fire door guidance

Kitchen

MeasureThresholdSource
Kitchen extract (England, dwellings)At least 30 L/s through a cooker hood ducted outside, 60 L/s from a fan elsewhere, or 13 L/s on a continuous system’s high rateApproved Document F, Volume 1: Dwellings (2021 edition), Table 1.1 and 1.2

Lift Cars & Machine Rooms

MeasureThresholdSource
Passenger lift car size (England, new lifts)At least 1100 mm wide and 1400 mm deepApproved Document M, Volume 2: Buildings other than dwellings (with 2024 amendments)
Thorough examination of liftsAt least every 6 months for equipment that lifts peopleThorough examination of lifting equipment (INDG422)

Lobbies & Atria

MeasureThresholdSource
Guarding (England)At least 1100 mm high; no openings that pass a 100 mm sphereApproved Document K (2013 edition incorporating 2016 and 2020 amendments)
Circulation routesAverage 20 lux, with no point below 5 luxLighting at work (HSG38)

Main Entrance & Reception Areas

MeasureThresholdSource
Opening force at the leading edge (England)No more than 30 N from 0 to 30 degrees, and 22.5 N from 30 to 60 degreesApproved Document M, Volume 2: Buildings other than dwellings (with 2024 amendments)

Maintenance Access Areas

MeasureThresholdSource
Guarding at edges (England)At least 1100 mm highApproved Document K (2013 edition incorporating 2016 and 2020 amendments)

Partitioning Systems

MeasureThresholdSource
Separating walls between dwellings (England)Airborne sound insulation at least 45 dB for purpose-built flats and houses; 43 dB in conversionsApproved Document E (2003 edition incorporating 2004, 2010, 2013 and 2015 amendments), Table 1a
Manifestation on glazed screens and doors (England)At two levels: 850 mm to 1000 mm and 1400 mm to 1600 mm; logos at least 150 mm high, or bands at least 50 mm highApproved Document K (2013 edition incorporating 2016 and 2020 amendments), 7.4

Public Amenities

MeasureThresholdSource
Hot water temperatures (Legionella control)Stored at 60 °C or more; 50 °C at outlets within one minute (55 °C in healthcare)HSG274 Legionnaires’ disease: Technical guidance, Part 2: Hot and cold water systems
Infrequently used outletsFlushed at least every 7 days, or as the risk assessment setsHSG274 Legionnaires’ disease: Technical guidance, Part 2: Hot and cold water systems

Residential Units/Guest Rooms

MeasureThresholdSource
Alarm level in sleeping rooms75 dB(A) at the bedheadFire safety risk assessment: sleeping accommodation
Bathroom extract (England, dwellings)At least 15 L/s run intermittently, or 8 L/s on a continuous system’s high rateApproved Document F, Volume 1: Dwellings (2021 edition)
Separating floors in flats (England)New build: airborne at least 45 dB, impact no more than 62 dB; conversions: 43 dB and 64 dBApproved Document E (2003 edition incorporating 2004, 2010, 2013 and 2015 amendments), Table 1.1

Retail Tenancies (Base-Build)

MeasureThresholdSource
Kitchen extract grease (TR19 Grease)Deposits of no more than 200 micronsVentilation hygiene standards (TR19)
Foul drain gradients (England)100 mm drain serving at least one WC: 1:80 or steeper; 150 mm drain serving at least five: 1:150; 75 mm or 100 mm drains with peak flow below 1 L/s: 1:40Approved Document H: Drainage and waste disposal (2015 edition), Table 6

Service Corridors

MeasureThresholdSource
Corridors and circulation routesAverage 20 lux, with no point below 5 luxLighting at work (HSG38)

External Elements

Stormwater Drainage

MeasureThresholdSource
Rainwater drain gradients (England)75 mm and 100 mm drains no flatter than 1:100; 150 mm at 1:150; 225 mm at 1:225Approved Document H: Drainage and waste disposal (2015 edition), paragraph 3.15

Mechanical Services

Air Handling Units (AHUs)

MeasureThresholdSource
Outside air, offices (England)10 L/s per personApproved Document F, Volume 2: Buildings other than dwellings
Carbon dioxide in occupied spacesBelow 800 ppm suggests good ventilation; consistently above 1500 ppm calls for actionApproved Document F, Volume 2: Buildings other than dwellings

Ductwork & Air Distribution

MeasureThresholdSource
Kitchen extract grease (TR19 Grease)Deposits of no more than 200 micronsVentilation hygiene standards (TR19)

Heat Rejection Plant

MeasureThresholdSource
Cooling tower general aerobic countUnder control up to 10,000 cfu/ml; corrective action above 100,000 cfu/mlHSG274 Legionnaires’ disease: Technical guidance, Part 1: Evaporative cooling systems
Cooling tower LegionellaReview above 100 cfu/litre; immediate action above 1,000 cfu/litreHSG274 Legionnaires’ disease: Technical guidance, Part 1: Evaporative cooling systems

Terminal Units

MeasureThresholdSource
Outside air, offices (England)10 L/s per personApproved Document F, Volume 2: Buildings other than dwellings
Carbon dioxide in occupied spacesBelow 800 ppm suggests good ventilation; consistently above 1500 ppm calls for actionApproved Document F, Volume 2: Buildings other than dwellings

Ventilation Systems

MeasureThresholdSource
Kitchen extract grease (TR19 Grease)Deposits of no more than 200 micronsVentilation hygiene standards (TR19)

Electrical Services

Emergency Lighting

MeasureThresholdSource
Rated durationDesigned for 1 to 3 hours, most often 3 hours where premises may be re-occupied straight after a failureFire safety risk assessment: offices and shops

Emergency Power

MeasureThresholdSource
Routine generator runsStandby diesel engines run for 30 minutes each weekFire safety risk assessment: offices and shops

Lighting

MeasureThresholdSource
Corridors and circulation routesAverage 20 lux, with no point below 5 luxLighting at work (HSG38)
Offices and fine workOffices: average 200 lux, minimum 100 lux; fine work: average 500 lux, minimum 200 luxLighting at work (HSG38)

Lightning Protection

MeasureThresholdSource
Rolling sphere radius by protection level (BS EN 62305)20 m, 30 m, 45 m and 60 m for levels I to IVBS EN 62305-1:2011 Protection against lightning: General principles

Fire Services

Automatic Sprinkler Systems

MeasureThresholdSource
When sprinklers are required (England)New residential buildings with a storey more than 11 m above ground, since 2020Approved Document B: Fire safety, volumes 1 and 2

Fire Detection & Alarm Systems

MeasureThresholdSource
Alarm level in sleeping rooms75 dB(A) at the bedheadFire safety risk assessment: sleeping accommodation

Hydrant & Hose Reel Systems

MeasureThresholdSource
Fire service access to dry main inlets (England)A pumping appliance within 18 m of each inlet, with the inlet visible from where it parksApproved Document B, Volume 2: Buildings other than dwellings (2026 online version)

Passive Fire Protection

MeasureThresholdSource
Fire door gaps (England)No more than 4 mm, except at the bottomFire Safety (England) Regulations 2022: fire door guidance
Fire door checks (England, storey over 11 m)Communal fire doors at least every 3 months; flat entrance doors at least every 12 monthsFire Safety (England) Regulations 2022: fire door guidance

Portable Fire Equipment

MeasureThresholdSource
Travel distance to an extinguisherNo more than 30 mFire safety risk assessment: offices and shops
Handle heightAbout 1 m for larger extinguishers and 1.5 m for smaller onesFire safety risk assessment: offices and shops

Smoke Management Systems

MeasureThresholdSource
Smoke vents and shafts (England)Corridor or lobby vent on an external wall: free area at least 1.5 m²; smoke shaft: section at least 1.5 m², with vents of at least 1 m²Approved Document B, Volume 1: Dwellings (2026 online version)
Smoke shaft outlet (England)At least 0.5 m above surrounding structures within 2 m, and at least 2.5 m above the ceiling of the highest storey servedApproved Document B, Volume 1: Dwellings (2026 online version)

Hydraulic Services

Hot & Warm Water Plant

MeasureThresholdSource
Hot water temperatures (Legionella control)Stored at 60 °C or more; 50 °C at outlets within one minute (55 °C in healthcare); return to the calorifier no less than 50 °CHSG274 Legionnaires’ disease: Technical guidance, Part 2: Hot and cold water systems

Sanitary & Drainage Systems

MeasureThresholdSource
Foul drain gradients (England)100 mm drain serving at least one WC: 1:80 or steeper; 150 mm drain serving at least five: 1:150; 75 mm or 100 mm drains with peak flow below 1 L/s: 1:40Approved Document H: Drainage and waste disposal (2015 edition), Table 6

Vertical Transportation

Accessibility Lifts

MeasureThresholdSource
Lifting platform speed (England)Rated speed no more than 0.15 m/sApproved Document M, Volume 2: Buildings other than dwellings (with 2024 amendments)
Thorough examination (lifting equipment)At least every 6 months for equipment that lifts people; every 12 months for other lifting equipment, unless an examination scheme sets otherwiseThorough examination of lifting equipment (INDG422)

Dock Levellers & Goods Hoists

MeasureThresholdSource
Thorough examination (lifting equipment)At least every 6 months for equipment that lifts people; every 12 months for other lifting equipment, unless an examination scheme sets otherwiseThorough examination of lifting equipment (INDG422)

Escalators & Moving Walks

MeasureThresholdSource
Step-to-skirt gap (BS EN 115)No more than 4 mm on either side of a step; 7 mm in total across both sidesInnovative technologies that improve escalator passenger safety (Symposium on Lift and Escalator Technologies) (quoted by a secondary source)
Rated speed at a 30° incline (BS EN 115-1)Up to 0.75 m/sInnovative technologies that improve escalator passenger safety (Symposium on Lift and Escalator Technologies) (quoted by a secondary source)

Passenger & Goods Lifts

MeasureThresholdSource
Passenger lift car size (England, new lifts)At least 1100 mm wide and 1400 mm deepApproved Document M, Volume 2: Buildings other than dwellings (with 2024 amendments)
Thorough examination (lifting equipment)At least every 6 months for equipment that lifts people; every 12 months for other lifting equipment, unless an examination scheme sets otherwiseThorough examination of lifting equipment (INDG422)

Building Code Compliance

Disabled Access (DDA)

MeasureThresholdSource
Opening force at the leading edge (England)No more than 30 N from 0 to 30 degrees, and 22.5 N from 30 to 60 degreesApproved Document M, Volume 2: Buildings other than dwellings (with 2024 amendments)

Occupational Health & Safety (OHS)

MeasureThresholdSource
Guarding at edges (England)At least 1100 mm highApproved Document K (2013 edition incorporating 2016 and 2020 amendments)